SECTION 6 CALIBRATION
92
6.3 CALIBRATION
PROCEDURE
This calibration procedure verifies that system gains are set properly and that the system per-
formance, relative to output power capability, is intact. Gains in various signal paths within
the controller are adjusted by the procedure of Paragraph 6.3.1. Output power capability of
the power source is tested by the procedure of Paragraph 6.3.2. The procedure is written for
three phase systems. When calibrating single phase systems, ignore all instructions relating
to phase C.
WARNING
THIS EQUIPMENT CONTAINS HIGH ENERGY, LOW IMPEDANCE CIRCUITS!! LETHAL POTENTIALS
ARE CONTAINED WITHIN THE CABINET.
CARE MUST BE EXERCISED WHEN SERVICING THIS EQUIPMENT IN ORDER TO PREVENT SERIOUS
OPERATOR INJURY OR EQUIPMENT DAMAGE.
VOLTAGE AT THE TERMINALS RESPONDS INSTANTLY WHEN THE OUTPUT IS ACTIVATED.
OBSERVE THE FOLLOWING WHEN SERVICE, MAINTENANCE, OR CALIBRATION ARE REQUIRED:
1) REMOVE ALL JEWELRY FROM HANDS, ARMS AND NECK WHEN SERVICING THIS
EQUIPMENT. THIS PREVENTS THE POSSIBILITY OF SHORTING THROUGH THE JEWELRY AND
CAUSING BURNS OR ELECTROCUTION OF THE OPERATOR.
2) WEAR SAFETY GLASSES WHEN SERVICING THIS EQUIPMENT TO PREVENT EYE
INJURY DUE TO FLYING PARTICLES CAUSED BY ACCIDENTAL SHORT CIRCUIT CONDITIONS.
3) DO NOT REMOVE ANY PANEL OR COVER WITHOUT FIRST REMOVING THE INPUT
SERVICE BY OPENING ALL CIRCUIT BREAKERS.
4) SERVICE OTHER THAN EXTERNAL CLEANING SHOULD BE REFERRED TO
PERSONNEL AUTHORIZED BY THE FACTORY TO SERVICE THIS EQUIPMENT.
6.3.1 CALIBRATE
CONTROLLER
The first step in system calibration is to calibrate the controller. The controller calibration
procedure is unique to the installed controller. Calibrate the controller as stated in the
appropriate controller manual.
UPC Controller - Refer to Section 8 of the
UPC-Series Operation Manual
.