SECTION 2 SPECIFICATIONS
11
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 308-AMX
INPUT VOLTAGE AND INPUT CURRENT
The Model 308-AMX single phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
INPUT
CURRENT
(360-440 Hz optional)
INPUT
CURRENT
SERVICE
RECOMMENDED
1) 100 VAC ±10%, 47-63 Hz
17 A
rms
25
A
2) 110 VAC ±10%, 47-63 Hz
16 A
rms
25
A
3) 120 VAC ±10%, 47-63 Hz
15 A
rms
25
A
4) 200 VAC ±10%, 47-63 Hz
8 A
rms
15
A
5) 208 VAC ±10%, 47-63 Hz
8 A
rms
15
A
6) 220 VAC ±10%, 47-63 Hz
8 A
rms
15
A
7) 230 VAC ±10%, 47-63 Hz
8 A
rms
15
A
8) 240 VAC ±10%, 47-63 Hz
7 A
rms
15
A
MODEL 312-AMX
INPUT VOLTAGE AND INPUT CURRENT
The Model 312-AMX single phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
INPUT CURRENT
INPUT
CURRENT
SERVICE
RECOMMENDED
1) 100 VAC ±10%, 47-63 Hz
20 A
rms
25
A
2) 110 VAC ±10%, 47-63 Hz
18 A
rms
25
A
3) 120 VAC ±10%, 47-63 Hz
18 A
rms
25
A
4) 200 VAC ±10%, 47-63 Hz
11 A
rms
15
A
5) 208 VAC ±10%, 47-63 Hz
10 A
rms
15
A
6) 220 VAC ±10%, 47-63 Hz
10 A
rms
15
A
7) 230 VAC ±10%, 47-63 Hz
9 A
rms
15
A
8) 240 VAC ±10%, 47-63 Hz
9 A
rms
15
A