SECTION 2 SPECIFICATIONS
12
2.1.1 INPUT POWER REQUIREMENTS
(cont.)
MODEL 320-AMX
INPUT VOLTAGE AND INPUT CURRENT
The Model 320-AMX three phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
INPUT
CURRENT
(360-440 Hz optional)
INPUT
CURRENT
SERVICE
RECOMMENDED
1) 208
VAC
∆
±10%, 47-63 Hz
11 A
rms
20
A
2) 220
VAC
∆
±10%, 47-63 Hz
10 A
rms
20
A
3) 240
VAC
∆
±10%, 47-63 Hz
9 A
rms
20
A
4) 220/380 VAC ±10%, 47-63 Hz
6 A
rms
15
A
5) 230/400 VAC ±10%, 47-63 Hz
6 A
rms
15
A
6) 240/416 VAC ±10%, 47-63 Hz
6 A
rms
15
A
( cost option )
7) 277/480 VAC ±10%, 47-63 Hz
5 A
rms
15
A
MODEL 345-AMX
INPUT VOLTAGE AND INPUT CURRENT
The Model 345-AMX three phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
INPUT
CURRENT
(360-440 Hz optional)
INPUT
CURRENT
SERVICE
RECOMMENDED
1) 208
VAC
∆
±10%, 47-63 Hz
23 A
rms
40
A
2) 220
VAC
∆
±10%, 47-63 Hz
22 A
rms
40
A
3) 230
VAC
∆
±10%, 47-63 Hz
21 A
rms
40
A
4) 240
VAC
∆
±10%, 47-63 Hz
20 A
rms
40
A
5) 220/380 VAC ±10%, 47-63 Hz
13 A
rms
20
A
6) 230/400 VAC ±10%, 47-63 Hz
12 A
rms
20
A
7) 240/416 VAC ±10%, 47-63 Hz
12 A
rms
20
A
( cost option )
8) 277/480 VAC ±10%, 47-63 Hz
11 A
rms
20
A