Designation
Description
Details
Action
9
FLO
Flow detection status
Should be ON when flow is detected and
OFF otherwise.
If not possible causes:
If a FLO error message,
go to FLO section
Pump 1 low isn’t running
Go to case #5
The system is running a flow checking
sequence
Wait approximately 2 minutes
The flow rate is too low
Make sure the installation respects the
flow rate requirements
Issue on remote heater
Change remote heater
10
KIN
KINETIC protection
status
Should be OFF on normal situation.
If ON, possible causes:
If a FLO error message,
go to FLO section
KINETIC state: No flow detected for more
than 2 hours
Wait 2 hours and validate the status of the
LED KIN again to confirm that KINETIC
error is permanent
Flashing: internal communication between
the remote heater and the pack
n/a
Issue on remote heater
Change the remote heater
11
D3
Light & RGB cmd status
Is ON only when the Light is turned ON by
the user, and OFF otherwise.
If not possible causes:
No POWER
Go to case #1
The error codes indicate a failure or problem that must be rectified to ensure proper functioning of the system.
The error code and the water temperature are displayed alternately on the keypad.
The error messages listed below display on the LCD and LED keypads. If your spa is equipped with a colour keypad, please refer your
Techbook for more information on error messages.
FLO
The system has detected no water flow during the main
pumps operation.
UPL
No low-level configuration is present in the control system
memory, insert a valid in.stik to program the control unit.
OH
The spas water temperature has reached 108°F (42°C)
Do not enter spa water!
AOH
The temperature inside the spa skirt is too high and
causes an increase of the internal temperature of the
control system above normal limits.
ERROR CODES ON IN.YJ, IN.YE, IN.YT AND IN.XE CONTROL SYSTEMS
HL
The water temperature in the water heater has reached
119°F (48°C).
Do not enter spa water!
Prr
The system detects a problem with the regulation probe.
The system constantly verifies if the temperatures read by
the probe are inside the normal limits.
Hr
An internal error with the system hardware has been
detected.