background image

Troubleshooting

 

 363-753-142-01, Revision 01

8

July 23, 1999

 FRC-753 List 4B

 

C

USTOMER

 R

EPORTED

 P

ROBLEMS

Table 2

 provides troubleshooting procedures based on customer reported problems.

Table 2.

FRC-753 RT Channel Unit Troubleshooting

Problem

Cause

Action

No dial tone, 
can not dial

faulty RT or COT Channel 
Unit

facility short/open

CO switch problem

1

Lift the subscriber pair at the network interface. If dial tone is present and you 
can place a call, refer the problem to the customer per local practice.

2

If you cannot hear dial tone or cannot place a call at the network interface (with 
the subscriber pair lifted), check for dial tone at the RT. If dial tone is present, 
check the pair between the RT and the network interface. If no dial tone is 
present, replace the RT Channel Unit.

3

If the problem still exists, re-insert the original RT Channel Unit and replace the 
COT Channel Unit. Test for operation.

4

If the problem still exists, refer the problem to the CO switch.

Phone does 
not ring

high-resistance subscriber 
line short

faulty RT or CO Channel 
Unit

•loop length too long

1

Lift the subscriber pair at the network interface. If ringing is present, refer the 
problem to the customer per local practice.

2

If ringing is not present, check for ringing at the RT. If ringing is present, check 
the pair between the RT and the network interface. If no ringing is present, 
replace the RT Channel Unit. If ringing is still not present, check a circuit on 
another Channel Unit. If ringing is still not present, replace the RTLU.

3

If ringing is still not present at the RT, re-insert the original Channel Unit and 
Line Unit. Test for ringing at the COT shelf.

4

Test for ringing into the COT from the CO switch. If no ringing is present, refer 
the trouble to the CO switch. If ringing is present, replace the COT Channel Unit. 
Test again for ringing at the network interface. If ringing is still not present, 
contact PairGain technical assistance (refer to 

“Technical Support” on Inside 

back cover

).

5

Verify the resistance of the copper loop between the RT Enclosure and the 
network interface is less than 530 

.

Phone does 
not stop 
ringing

faulty subscriber 
instrument

faulty RT Channel Unit

loop length too long

1

Test for ring trip at the network interface. If the ringing is tripped, refer the 
trouble to the customer per local practice.

2

If the ringing is not tripped, test for tripping at the RT. If ring trip does occur, 
check the loop for excessive length. If ring trip does not occur, replace the RT 
Channel Unit. If ring trip still does not occur, contact PairGain technical 
assistance (refer to 

“Technical Support” on Inside back cover

).

3

Verify the resistance of the copper loop between the RTE and the network 
interface is less than 530 

.

Can not 
hear, can 
not be heard

subscriber problem

faulty RT or COT Channel 
Unit

1

Lift the subscriber line at the network interface and check the signal level. If 
correct, refer trouble to the customer per local practice.

2

If the level is too low, check the level at the RT. If the level is correct at the RT, 
check the pair between the RT and the network interface. If the level is too low 
at the RT, replace the RT Channel Unit.

3

If the level is still too low, re-insert the original RT Channel Unit.

4

Check the level at the COT shelf coming from the CO switch. If it is correct, 
replace the COT Channel Unit. If it is not correct, refer the problem to the CO 
regarding the switch.

5

If the level is still not correct, re-insert the original COT Channel Unit. Contact 
PairGain technical assistance (refer to 

“Technical Support” on Inside back 

cover

).

Summary of Contents for PG-Flex FRC-753 4B

Page 1: ...T GROUND START UNIT PAIRGAIN TECHNOLOGIES INC ENGINEERING SERVICES TECHNICAL PRACTICE SECTION 363 753 142 01 Model List Number Part Number CLEI Code FRC 753 4B 150 1353 42 VARHCKTC PairGain 1 A C T I...

Page 2: ...ined in this document is company private to PairGain Technologies Inc and shall not be modified used copied reproduced or disclosed in whole or in part without the written consent of PairGain Other pr...

Page 3: ...ny and to PairGain Order replacement equipment if necessary Check the packing list to ensure complete and accurate shipment of each listed item If the shipment is short or irregular contact PairGain a...

Page 4: ...ions 5 Installation and Test ___________________________________________________________________ 6 Installing the FRC 753 into the RT Enclosure 6 Provisioning the FRC 753 6 Verify Operation 6 Troubles...

Page 5: ...bscriber line connection through an optional metallic bypass pair Perform metallic bypass testing either manually or through the Pair Gain Test Controller PGTC Features of the FRC 753 are eight LS GS...

Page 6: ...criber Each FRC 753 detects loop current Ring tip Ring ground The subscriber line battery is supplied by a constant current supply It is sufficient to operate a telephone set over the indicated loop T...

Page 7: ...tion is a Tip lead open and Ring lead negative into the COT and Tip lead open and Ring lead negative at the RT The following occurs when a PBX requests service for an outgoing call by grounding the Ri...

Page 8: ...wer at the RT the LEDs extinguish after a 2 minute timeout period Press and hold the ACO button on the RTLU for two seconds to re activate the LEDs for another two minutes Table 1 FRC 753 Front Panel...

Page 9: ...r Output 40 V RMS 3 lines simultaneous 5 REN each End to End Loss 2 5 dB 1 0 dB Lightning Protection GR CORE 1089 Section 4 Environmental Operating Elevation 200 ft to 13 000 ft 60 m to 4 000 m Temper...

Page 10: ...s off no calls are in progress 2 Test circuits for loop start a Place an outgoing call for each subscriber circuit provisioned and observe that the Active LED tracks the progress of the call b Place a...

Page 11: ...this connection to the COT where it can be switched onto the test access bus or to the corresponding subscriber line on the COT channel card Activate test access through the RS 232 maintenance port lo...

Page 12: ...from the CO switch If no ringing is present refer the trouble to the CO switch If ringing is present replace the COT Channel Unit Test again for ringing at the network interface If ringing is still no...

Page 13: ...Services CO Central Office COLU Central Office Line Unit COT Central Office Terminal DTMF Dual Tone Multi Frequency LS GS Loop Start Ground Start MLT Mechanized Loop Testing PBX Private Branch Exchan...

Page 14: ......

Page 15: ...uthorization RMA number at 800 638 0031 Return the defective unit freight prepaid along with a brief description of the problem to PairGain Technologies Inc 14352 Franklin Avenue Tustin CA 92780 ATTN...

Page 16: ...Corporate Office 14402 Franklin Avenue Tustin CA 92780 Tel 714 832 9922 Fax 714 832 9924 For Technical Assistance 800 638 0031...

Reviews: