GTV

 

FORCED CONVECTION AIR HEATERS   

User’s Manual

10

From flammable materials it is obligatory to keep 

SAFETY OF OPERATION

 and

 FIRE PREVENTION

 distances! 

Minimal dimensions of protective distances:

25. picture: Protective distances

Protective distances

Warning: In case of between 68-116 KW power of devices this fixing mode is not applicable!

 

The properly installed appliance according to the control sign received from temperature regulator - in the present case heating – starts 

the exhaust fan,which executes the 30 seconds prepurge time� This time period is also enough for biggest power appliance to ensure 

the satisfactory air exchange namely the triple of combustion air volume� When the ventilation happened the sparking is started and the 

dual magnetic valves are opened the gas ignites� 

If the continuous burning is formed within 5-10 seconds the appliance is operating normally the green control lamp is lighting��During 

operation the appliance continuously monitors the status/sign of differential pressure switch and flame detector, if needed the electronic 

control intervenes in the process�  

If the status of differential air pressure switch is changed during operation namely switches over from work/switched on position to ba

-

sic/standstill position in that case the automatic electronic control stops the gas supply by closing of magnetic valves and controls the 

appliance in error mode moreover the red control lamp located on front side of device is lighting�

In case the flame detector of automatic burner control does not sense flame formation during ignition in that case stops the gas supply 

and controls the appliance in error mode moreover the red control lamp is lighting�

In case during burning process the pressure difference decreases under the permissible minimal value on the air pressure switch than 

the automatic control prohibits the operation as follows:

• 

stops the gas supply

• 

stops the operation of exhaust fan

• 

controls the appliance in error mode and red control lamp is lighting

ATTENTION! The restart of appliance, which is in safety status can only be possible by 

pushing of „RESET” push button located on the PCB (inside of appliance) or on the tem-

perature regulator!

 

General information: 

The flame detector is self-checking and can just operate with the burner, other environmental effects (ambient 

temperature,lights) can not influence it. 

7.

  

Appliance operation

Start, restart

Summary of Contents for GTV Series

Page 1: ...TURAL GAS FIRED GTV TYPE WARM AIR BLOWERS User s manual GTV 68A GTV 78A GTV 87A GTV 97A GTV 107A GTV 116A Appliance types GTV 20A C CL GTV 27A C CL GTV 33A C CL GTV 40A C CL GTV 48A C CL GTV 58A C CL...

Page 2: ...9 Optional accessories 10 6 Appliance specification 10 Ventilation 10 Protective distances 11 7 Appliance operation 11 Start restart 11 Control and regulation of appliance 12 10 Maintance 13 Maintena...

Page 3: ...each your gas supplier call the Fire Department The GTV type warm air blower appliances have been developed and certified in compliance with MSZ EN 1020 standard and qualified for heating of industria...

Page 4: ...leave it to grow old Do not use seriously aged equipment any longer Fix the appliance on such stable surface which during operation despite warming of appliance preserves its stability If the applian...

Page 5: ...orma tions ATTENTION COMPULSORY EARTHING ATTENTION ONLY QUALIFIED PERSON CAUTION DANGER CAUTION ELECTRIC SUPPLY According to the installation project install the electric power lines Always make sure...

Page 6: ...attachment investigate the device if it is not damaged during the transportation if it is damaged in that case notify the retailer from whom the device was bought There is an envelope inside the unit...

Page 7: ...las or through the attached air duct to the demanded places 5 picture Axial fan type warm air blower 6 picture Centrifugal fan type with lamella execution Features suction in of heater air can be from...

Page 8: ...Possible regulation mode controlled by AHP 1 type thermostat Regulation possibilities Applicable regulatory options according to regulation ECO DESIGN EU2016 426 3 point modulation GTV 20 78 kW L N A...

Page 9: ...between the programme clock and warm air blower is solved by just one wire namely by control cable The automatic burner control located in the appliance receives and processes the transmitted control...

Page 10: ...he status of differential air pressure switch is changed during operation namely switches over from work switched on position to ba sic standstill position in that case the automatic electronic contro...

Page 11: ...e room temperature You have a chance daily and weekly programming with time switch Thermostat and appliance Appliance is under voltage with selector In this case the green lamp is lighting and you can...

Page 12: ...which disassembly of appliance is necessary supervision of nozzle pressure at the outlet of solenoid valve check of the condition of pressure regulator check of the protective ground check of the elec...

Page 13: ...al authorized representative or a qualified service department Gas change ATTENTION This action can only be realized by outhorized expert or service ATTENTION If the heater appliance is working than i...

Page 14: ...on A 0 9 0 9 1 77 1 77 1 9 1 9 Electrical performance W 0 21 0 21 0 41 0 41 0 44 0 44 Noise level dB A 53 53 55 55 55 57 Weight kg 64 86 95 IP protection of device IP21 Modell GTV 68A GTV 78A GTV 87A...

Page 15: ...5 8 3 5 9 2 6 9 2 6 Electrical performance kW 943 943 1150 1150 1380 1380 Noise level dB A 56 58 56 58 58 58 Weight C kg 70 93 121 Weight CL kg 75 98 126 IP protection of device IP21 Type Input Output...

Page 16: ...10 510 625 805 187 GTV 40A 610 510 625 805 187 GTV 48A 750 650 625 805 252 GTV 58A 750 650 625 805 252 Type A a b M e GTV 68A 810 700 840 970 238 GTV 78A 810 700 840 970 238 GTV 87A 960 850 840 970 31...

Page 17: ...CL GTV 33A C CL GTV 40A C CL GTV 48A C CL GTV 58A C CL Venting set type Maximal lenght of venting set 100 mm m B22 3 4 6 6 8 8 C12 3 4 6 6 8 8 C32 3 4 6 6 8 8 C52 3 4 6 6 8 8 Venting set type Maximal...

Page 18: ...2E3P 20 37 PL GTV 20A C CL GTV 58A C CL I2HS3P 25 28 30 50 HU GTV 68A GTV 116A I2H3P 25 28 30 50 HU I3P 50 NL The appliances were tested together with the flue system recommended by the manufacturer T...

Page 19: ...mission efficiency hs flow 94 21 Seasonal space heating energy efficiency hs h 72 7 Model GTV 20A C CL MOD Modulated Indirect gas fired forced convection air heater with axial fan B1 Warm air heater N...

Page 20: ...s flow 93 70 Seasonal space heating energy efficiency hs h 72 8 Model GTV 27A C CL MOD Modulated Indirect gas fired forced convection air heater with axial fan B1 Warm air heater No C2 Warm air heater...

Page 21: ...s flow 93 71 Seasonal space heating energy efficiency hs h 72 6 Model GTV 33A C CL MOD Modulated Indirect gas fired forced convection air heater with axial fan B1 Warm air heater No C2 Warm air heater...

Page 22: ...s flow 93 70 Seasonal space heating energy efficiency hs h 72 7 Model GTV 40A C CL MOD Modulated Indirect gas fired forced convection air heater with axial fan B1 Warm air heater No C2 Warm air heater...

Page 23: ...s flow 93 87 Seasonal space heating energy efficiency hs h 72 7 Model GTV 48A C CL MOD Modulated Indirect gas fired forced convection air heater with axial fan B1 Warm air heater No C2 Warm air heater...

Page 24: ...s flow 93 54 Seasonal space heating energy efficiency hs h 72 8 Model GTV 58A C CL MOD Modulated Indirect gas fired forced convection air heater with axial fan B1 Warm air heater No C2 Warm air heater...

Page 25: ...s flow 93 70 Seasonal space heating energy efficiency hs h 73 5 Model GTV 68A MOD Modulated Indirect gas fired forced convection air heater with axial fan B1 Warm air heater No C2 Warm air heater No C...

Page 26: ...s flow 92 64 Seasonal space heating energy efficiency hs h 72 4 Model GTV 78A MOD Modulated Indirect gas fired forced convection air heater with axial fan B1 Warm air heater No C2 Warm air heater No C...

Page 27: ...rized retailer or service station The regular maintenance is the owner s responsibility The manufacturer does not assume the responsibility in case of accidentally happened or directly caused mistake...

Page 28: ...PAKOLE TRADE Ipari s Kereskedelmi Kft H 8000 Sz kesfeh rv r B rg ndi t 8 10 http www pakole com E mail mail pakole hu Tel 36 22 316 484 Fax 36 22 316 074 www pakole com...

Reviews: