GTV
FORCED CONVECTION AIR HEATERS
User’s Manual
12
The GTV-type warm air blowers apart from the checking of suspension and cleaning of cover, lamellas and circulating fan do not need
extra maintenances but to be able to preserve the long lifetime of appliance it is recommended to have yearly supervision done with a
qualified service or expert.
Maintenance supervisions by the costumer: (recommended half a yearly)
•
supervision of circulating fan, if needed clean it (by high pressure air),
•
supervision of outblowing apertures (lamellas)
•
supervision of suspension points/surfaces by survey
WARNING! Before every maintenance the appliance must be detached from the electrical supply
by switching off the main-switch and disconnecting the connection plug located on the back side
of appliance!
ATTENTION! In case operational circumstances of appliance (atmosphere is contaminated with cor-
rosive substances,dirt) need it, then supervision and cleaning may have done more often! The main
reason of this that dirt placed on the fan may damage efficiency of appliance!
Maintenance procedures
10.
Maintance
Maintenance supervision solely by a qualified service department
(all kinds of interventions for which disassembly of appliance is necessary):
• supervision of nozzle pressure (at the outlet of solenoid valve),
•
check of the condition of pressure regulator
•
check of the protective ground
•
check of the electrical connection
•
check of the exhaust fan and circulating fan: check the free rotation of fan and remove the possible contaminations from the
impellers
•
supervision of the heat exchanger
•
supervision of working of the temperature controller
• check of the ignition and ionization electrode, if necessary change it
•
check of the exhaust fan and circulating fan, if necessary clean those
• supervision of the quality of combustion
• dismounting and clean of the gas filter by high pressure air
ATTENTION! After every maintenance the appliance must be again adjusted !
Constructional components,which ensure the suitable operation:
•
double-closed solenoid valve
•
automatic burner control
•
electrical board (sign processing)
•
differential pressure switch
•
exhaust fan
•
combined thermostat (bimetal),
•
heat-limiter thermostat (100oc),
•
circulating fan
WARNING! Never block the outflow of fume and inflow of combustion air!
Never change the original adjustments what the expert made!
Never allow that water or water –vapour can be got on the appliance!
Apart from cleaning of exhaust fan and circulating fan the a�m� components do not need maintenance! The cleaning of fans is expe-
dient to carry out by high pressure air�