Components of „I” -form tube radiant heater, assembly distances
Components of „U”-form tube radiant heater, assembly distances
Straight execution tube radiant heate
r appliance: see fig
. 1
For 3m (total length) long appliances only 2 hangers should be placed 1800mm apart, and 700 mm far from the beginning of burner tube�
During assembling of straight system the installation of 1 pc 90° elbow is allowed but it must be placed minimum 6m far from the burner�
„U”-pipe-execution tube radiant heater appli
ance: see fig. 2
At the „U”-pipe appliance in case of non side-wall-placing execution – which is not suspended at an angle – the burner head can be in-
stalled into optional side of „U” pipe, just taking it into consideration that the turbulant unit be at the end of last tube before flue gas outlet.
Combi hanger
Burner
Reflector hanger
Tube connection
Reflector
Connection element
1. picture: “I”-form appliance
Combi hanger
Burner
Reflector hanger
Tube connection
U element
2. picture: “U”- form appliance
5.
Installation