Direct calibration of P1 / P9 speeds: parameters UUE / UEn
To regulate on air the
P1 / P9
fan speeds follow the procedure:
Chose modality MANUAL
Set the fan’s speed
P01
o
P9
Enter the SECONDARY Menu following the above procedure
Select the parameter
UUE / UEn
and modify it until the desired value:
in this way it is possible to control the two speeds directly
Memorise pushing button
P4
To exit wait about 5 seconds
4.2 PLUGGING IN PROBE – THERMOSTAT
4.2.1 Aeraulic probe
Installing the probe on the aeraulic tube (hot air) 30 cm far
from the fireplace’s exit or 30 cm far from the mouth’s exit .
To install:
1.
Drill the tube
2.
Insert in the probe’s support a washer and insert the probe in the tube
3.
In the internal part of the tube screw the nut to fix the probe’s support to the tube
4.
Insert the probe through the probe-locker
5.
Screw the probe- locker in the probe’s support to block the probe without moving the support
4.2.2 Thermostat
Switch the thermostat in the right screwed place (M4) in the fireplace.
4.3 CHANGE THE INPUT CONFIGURATION
To enter the
Cod
parameter enter the secondary menu
Push together buttons
P2
and
P3
for about 5 seconds to enter modify parameters
Visualise parameters using the button
P2 or P3
, until the parameter
Cod
Visualise the parameter’s value
Cod
pushing
P4
Modify the parameter’s value
Cod
with buttons
P2
or
P3:
In Probe:
‘1’
In Thermostat: ‘2‘
Memorise data with button
P4
Wait for about 5 seconds to exit
Stop and give supply to the controller
If the input is a
Probe
the parameter
Cod
should be:
[
Cod
= 1
]
If the input is a
Thermostat
the parameter
Cod
should be:
[
Cod
= 2
]
4.3.1 Particular case tangential Fan (002520016) with thermostat
If the thermostat is wired in series to the fan make a bridge on the probe connector (9-10)
4.4
ELECTRICAL CONNECTION SPARK KIT
Connect the contact PULS of the kit Spark to the connectors 5-6 of the controller
Connect the contact SPR of the kit Spark to the connectors 7-8 of the controller
Now feeding the spark kit and pushing the flame icon the spark kit is active.
4.5 Configuration
errors
There could be two error’s conditions in the product’s configuration:
A.
Cod = 1
but input
Thermostat
Fire off appears
Lo
Fire on appears
Hi
with acoustic signal on.
B.
Cod = 2
but input aeraulic
Sensor
Feeding the controller appears on the display
Err
.
4.6 INSTALLING RULES
ATTENTION
-
Avoid join together the probe’s cables with power’s cables.
-
Provide the system’s feeding with a bipolar switch according to the actual rules and with opening
distance of the contacts of at least 3 mm for each pole.
-
Installation and the electrical connection of the device have to be made by experienced personal and
with appropriate equipping.
-
Before the connection be aware that the electrical feeding is not connected..