background image

 

DICHIARAZIONE DI CONFORMITÀ UE 

EU DECLARATION OF CONFORMITY

 

 

10/12

 

Il sottoscritto, Dr. Ing. Luigi Moretti, rappresentante il seguente costruttore 

The undersigned, Dr. Ing. Luigi Moretti, representing the following manufacturer 

 

Palazzoli S.p.A.

 

25128 - BRESCIA 

– Italy – Via F. Palazzoli, 31 

Tel. +39 30 2015.1Fax +39 30 2015.217 

http://www.palazzoli.it

  -  E-mail: 

palazzoli@palazzoli.it

 

 
Dichiara, sotto la propria esclusiva responsabilità, che i prodotti: 

Hereby declare, under the own sole responsibility, that the products: 

 

ENCLOSURES WITH TYPE OF PROTECTION nR ALUPRES-EX series 

CONTENITORI CON MODO DI PROTEZIONE nR serie ALUPRES-EX 

 
With the following main features / 

Con le seguenti principali caratteristiche: 

 

Description/ 

Descrizione 

Empty enclosure in aluminum alloy 

Contenitori vuoti in lega d'alluminio 

 

Code 

Codice

 

External dimensions 

Dimensioni esterne

 

[mm] 

Equipment protection Level 

Livello di Protezione delle apparecchiature

 

( EPL ) 

511914EX 

125x125x113 

Gc 
Db 

511919EX 

252x125x113 

Gc 
Db 

 

TECHNICAL DATA /

 

CARATTERISTICHE TECNICHE

 

Insulating class /

 Classe Isolamento 

Degree of protection (IP code) /

 Grado di protezione (codice IP)

 

IP66

 

 
Satisfies the Requirements defined by following Directives

Soddisfa i Requisiti definiti dalle seguenti Direttive: 

 

2014/35/UE 

LVD 

 

 

and that the following harmonized standards and/or technical specifications, have been applied: 

e che sono state applicate le norme armonizzate e/o specifiche tecniche indicate di seguito: 

 

Standard 

Norma 

Title 

Titolo 

EN 62208:2011

 

Empty enclosures for low-voltage switchgear and controlgear assemblies -General requirements 

Involucri vuoti per apparecchiature assiemate di protezione e manovra per bassa tensione - Prescrizioni generali 

 

 

 
 

Brescia, 2018-12-21 

 

 

 

 

 

 

       Il Legale Rappresentante 

 
 
 
 

 
 
 

Summary of Contents for ALUPRES-EX Series

Page 1: ...xed installation ALUPRES EX Series ATEX EXECUTION CONTENITORI CON MODO DI PROTEZIONE nR Per installazione fissa Serie ALUPRES EX ESECUZIONE ATEX Execution Esecuzione Group II Category 3G 2D Ex nR IIC Gc Ex tb IIIC Db SAFETY USE and MAINTENANCE INSTRUCTIONS ISTRUZIONI DI SICUREZZA USO E MANUTENZIONE IN COMPLIANCE WITH THE DIRECTIVE 2014 34 EU PALAZZOLI S p A Via F Palazzoli 31 25128 BRESCIA Italy T...

Page 2: ... 60079 series for presumption of conformity to 2014 34 EC which provides a level of protection against explosive atmospheres ignition suitable for the installation in the declared Zone Apparecchiatura progettata e costruita in accordi con le norme armonizzate della serie EN 60079 per presunzione di conformità alla direttiva 2014 34 UE che garantisce un livello di protezione contro le atmosfere esp...

Page 3: ...rea in cui durante le normali attività è probabile la formazione di un atmosfera esplosiva consistente in una miscela di aria e di sostanze infiammabili sotto forma di gas vapore o nebbia Zone 21 A place in which an explosive atmosphere in the form of a cloud or combustible dust is likely to occur in normal operation occasionally Area in cui occasionalmente durante le normali attività è probabile ...

Page 4: ...sonale esperto formato e addestrato alla regola dell arte alle leggi norme nazionali e o internazionali applicabili per esempio EN 60079 14 Atmosfere esplosive Parte 14 Progettazione scelta e installazione degli impianti elettrici TABLE OF ZONES WHERE THE PALAZZOLI ENCLOSURES CAN BE INSTALLED TABELLA DELLE ZONE DOVE I CONTENITORI POSSONO ESSERE INSTALLATE 2014 34 EU Group and Category 2014 34 UE G...

Page 5: ...n cable M16x1 5 Pressacavo M16x1 5 su cavo 2 5 ND Cable gland on cable M20x1 5 Pressacavo M20x1 5 su cavo 3 5 ND Cable gland on cable M25x1 5 Pressacavo M25x1 5 su cavo 4 ND Cable gland on cable M32x1 5 Pressacavo M32x1 5 su cavo 8 5 ND Cable gland on cable M40x1 5 Pressacavo M40x1 5 su cavo 10 ND The equipment shall be installed according to this instructions This equipment is intended for fixed ...

Page 6: ...LI PER UN USO SICURO Assembly and start up must only be done by experienced and authorised personnel according to the applicable code of practice national rules and or international standards and on the basis of these instructions Position the equipment so that they are easily accessible for cleaning and maintenance operations Install the equipment as far away as possible from heat sources or area...

Page 7: ...ent requires grounding The equipment is provided with an internal connection terminal for earthing for earthing of circuits load if required by relevant code of practice The conductors must be equipped with ring terminal Tighten the screw of the earthing terminal with the tightening torque indicated in clause 2 of this document L apparecchiatura richiede messa a terra L apparecchiatura è provvista...

Page 8: ...cambio Check that the screws are in place free of corrosion Controllare che le viti siano in corretta posizione e non corrose Each time the enclosure is reclosed Ogni volta la custodia viene aperta e richiusa In case of fault contact manufacturer for substitution In caso di guasto contattare il costruttore per il ricambio Check that the screws are tight with correct torque Controllare che le viti ...

Page 9: ...ative pressure of 3 kPa 3 mbar o Stop the application of the negative pressure o Verify that the time interval required for return to half the initial value shall be not less than 90 s Quando montate in quadri presa come punto di test di respirazione limitata si deve utilizzare la bocca presa Per l esecuzione del test una speciale attrezzatura finta spina deve essere usata si rimanda alle istruzio...

Page 10: ...vuoti in lega d alluminio Code Codice External dimensions Dimensioni esterne mm Equipment protection Level Livello di Protezione delle apparecchiature EPL 511914EX 125x125x113 Gc Db 511919EX 252x125x113 Gc Db TECHNICAL DATA CARATTERISTICHE TECNICHE Insulating class Classe Isolamento I Degree of protection IP code Grado di protezione codice IP IP66 Satisfies the Requirements defined by following Di...

Page 11: ...imensioni esterne mm Equipment protection Level Livello di Protezione delle apparecchiature EPL 511914EX 125x125x113 Gc Db 511919EX 252x125x113 Gc Db TECHNICAL DATA CARATTERISTICHE TECNICHE Insulating class Classe Isolamento I Degree of protection IP code Grado di protezione codice IP IP66 Satisfies the Requirements defined by following Directives Soddisfa i Requisiti definiti dalle seguenti Diret...

Page 12: ...losive Parte 31 Apparecchi con modo di protezione t destinati ad essere utilizzati in presenza di polveri combustibili In addition the products covered by this declaration are in conformity with the following IEC standards I prodotti oggetto della presente dichiarazione sono in oltre conformi alle seguenti norme IEC IEC standard Norme IEC ed Title Titolo IEC 60079 0 2011 ISH1 2013 ISH2 2014 COR 20...

Reviews: