Diagnostics
11
USA & Canada (800) 472-5555 • (707) 283-5900 • Fax (707) 283-5901
Battery Features
(continued)
Battery Replacement Procedure
2.
Remove the two retaining screws of the
cable protection cover then remove the cover.
6.
Slide a new battery pack into the unit.
Assemble the screws, cover, cable and front
panel in the reverse sequence of above steps.
7.
Recharge the unit for 4-8 hours to ensure
the UPS performs expected runtime.
4.
Remove the four retaining screws.
3.
Disconnect the black and red cable.
1.
Remove the right side front panel using
pull-out handles.
5.
Pull the battery pack out from the unit.
Battery pullout tab handle
Power
On LED
On
On
On
On
Off
Off
On/Off
Off
On
Off
On/Off
Wiring
Fault LED
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
AVR LED
Off
Slow Flash
Rapid Flash
On
Off
Off
On/Off/Flash
Off
On/Off/Flash
Off
On/Off/Flash
Using
Battery LED
Off
Off
Off
Off
On
On
On/Off
On
Off
Off
On/Off
Circuit
Breaker
Set
Set
Set
Set
Set
Set
Set
Up
Set
Set
Set/Up
Audible
Alarm
Off
Off
Off
Off
Two Beeps
Rapid Beeps
Long Beep
Long Beep
None
Off
None
Condition
Normal
AVR-
Max. boost 13% of input voltage for output regulation while input voltage is
from 8% to 15% under nominal.
AVR-
Max. boost 26% of input voltage for output regulation while input voltage is
from 15% to 26% under nominal.
AVR-
Max. buck 15% of input voltage for output regulation while input voltage is
from 8% to 26% over nominal.
Utility Failure-
The UPS is providing battery power to the connected equipment.
Utility Failure-
The UPS is providing battery power. Rapid beeps indicate the battery
will run out of charge within a few minutes.
Overload-
Turn the UPS off and unplug at least one piece of equipment from the UPS.
Wait 5 seconds, reset the circuit breaker and restart the UPS.
Overload-
Turn the UPS off and unplug at least one piece of equipment from the UPS.
Wait 5 seconds, reset the circuit breaker and restart the UPS.
Weak Battery-
Recharge the battery for at least 8 hours. If Check Battery is illuminat-
ed, contact Panamax for battery replacement information.
Surge Protection Malfunction-
Power surge has damaged the unit. Please contact
Panamax.
Electrical Wiring Fault-
Indicates wiring problems such as a bad ground, missed
ground or reversed wiring within the AC outlet. User is advised to disconnect all
electrical equipment from the outlet and have the outlet checked by an electrician.