background image

 
 
 

Panasonic Electric Works Fire & Security Technology Europe AB 

 

Citadellsvägen 23, SE-211 18 Malmö, Sweden 

Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 

info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com 

 

Fire alarm systems 

External Fire Brigade 

Panel 1828 

 

Control (key required) and indicating panel for the fire brigade personnel, etc. 

 

Compact size 

Ext. Fire Brigade Panel 

This unit (S/W V1.2) is primarily intended 
to be used by the fire brigade personnel, i.e. 
for pre-warning, co-incidence, fire and 
heavy smoke / heat alarm presentation. 

 

Point or zone alarm presentation and fire 
alarm reset are as in the c.i.e. it is connected 
to.  You can scroll amongst two or more 
alarms in the system.  All or selected alarms 
will be presented in a display (LCD, 2x40 
characters with back-light).  An alarm text 
will be presented together with each alarm, 
if programmed in the c.i.e.  Furthermore, 
>617 texts for selected alarms can be stored 
in the unit and will in such a case be shown, 
instead of the texts sent from the c.i.e. for 
these alarms.  A built-in buzzer will sound 
like in the c.i.e.  Any fault in the system will 
be presented as "General fault in system" 
and the buzzer will sound.  The unit is 
power supplied via the c.i.e. or ext. power 
supply. 

LEDs, push buttons etc. 

The unit has the following LEDs: 

 

Fire

 and 

Alarms queued

, indicating 

pre-warning, co-incidence, fire and 
heavy smoke / heat alarm 

 

Operation

, indicating that the unit is 

connected to a c.i.e. and power 
supplied, i.e. it is in operation. 

 

Extinguishing

, indicating activated 

output for Extinguishing equipment. 

 

Ventilation

, indicating activated output 

for Ventilation equipment. 

 

Fire brigade tx

, indicating activated 

output for Fire brigade tx (routing 
equipm.). 

The unit has the following push buttons: 

 

Alarms queued

, used to scroll amongst 

the alarms. 

 

Silence buzzer

, used to silence the 

buzzer (it will re-sound for a new 
alarm. 

 

Silence alarm devices

, used to silence 

the alarm devices (they will re-sound 
for a new alarm. 

 

Reset

, used to reset the fire alarms. 

The designation texts on the front are in 
1828SE in Swedish but a neutral front for 
other languages is available (1828CC). 

Compact size 

The compact size enclosure is made of grey 
high impact ABS.  Fitted with a supple-
mentary "O" ring gasket, it will comply with 
IP61, in respect of dust and moisture.  A key 
is required to get access to the push buttons 
and they are disabled until they are supposed 
to be used.  A key is not required for the 
alarm presentation and to silence the buzzer.  
Two compression glands are attached.  The 
unit shall be wall mounted. 

SW mode and address setting 

The display and the push buttons are used to 
set the 

SW mode 

and 

address

, see the 

opposite side of this page. 

Product application 

The 1828 unit is intended for indoor use and 
in dry premises.  SW mode 

1826/28 - 1587

 

is intended to be used in the systems 
EBL512 and EBL128 SW mode 

1826/28 – 

1582

 in the systems EBL500 / 512 / 1000 / 

2000.  

Reviews: