3. GENERAL DESCRIPTION 

TECHNICAL DESCRIPTION 4318 

• DOCUMENT NUMBER: MEW01961 • REVISION: 

3

 

GENERAL DESCRIPTION 

The combination heat detector is a conventional fixed temperature detector, category A1R. The detector 
will give an alarm at a certain fixed temperature (59 °C) and/or at a certain temperature rise, "rate-of-
rise" function. 
Used in system EBL512 G3, EBL128, and EBL512.  
 
The unit is intended for indoor use and in dry premises. 

(Measures in mm) 
 

3.1

 

DETECTOR 

The sensing element is a thermistor. The detector and will give an alarm within a response temperature 
range. 
 

Static response temperature 

Category  Temperature range 

59 °C 

A1 R 

54-65 °C 

 
The rate-of-rise function (deltaT) will detect a fast temperature rise > 6 °C per minute. 

3.1.1

 

LATCHING 

The detector is latching. The detector will not be automatically reset if the temperature, after the alarm, 
falls below the detector's static response temperature. The detector's LED and a connected external 
LED will be lit until the detector is reset via the c.i.e. 

3.1.2

 

EXTERNAL LED 

One External Indicator (LED) can be connected to the screw terminals 

E+ 

and 

E-

:  

Summary of Contents for 4318

Page 1: ...PANASONIC FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 4318 COMBINATION HEAT DETECTOR...

Page 2: ...INFORMATION DOCUMENT NAME TECHNICAL DESCRIPTION 4318 DOCUMENT NUMBER MEW01961 DATE OF ISSUE 2016 01 11 REV 2 DATE OF REVISION 2021 01 25 Panasonic Fire Security Europe AB Jungmansgatan 12 SE 211 11 M...

Page 3: ...1 REVISION 2 TABLE OF CONTENTS 1 INTRODUCTION 3 2 ABBREVIATIONS 3 3 GENERAL DESCRIPTION 4 3 1 DETECTOR 4 3 1 1 LATCHING 4 3 1 2 EXTERNAL LED 4 3 2 ZONE LINE INPUT 5 4 MOUNTING 5 5 INSTALLATION AND WIR...

Page 4: ...SION 2 1 INTRODUCTION This document describes the combination heat detector type number 4318 The document contains information about the product and instructions on how to mount and connect it 2 ABBRE...

Page 5: ...ETECTOR The sensing element is a thermistor The detector and will give an alarm within a response temperature range Static response temperature Category Temperature range 59 C A1 R 54 65 C The rate of...

Page 6: ...ctor is connected to a zone line input for conventional detectors in the c i e The last unit on the zone line has an End of line device to be connected The type of end of line device is depending on t...

Page 7: ...nnected to the base NOTE Screen wire termination is not provided DATA 2324 Wire size Min 0 65 mm 0 3 mm Wire size Max 1 6 mm 2 mm 6 TEST MODE For information about how to set a zone in test mode see P...

Page 8: ...limitation 0 015 mA Must be minimum 3 Rate of rise response 6 C min Short circuit isolator No Internal battery No Material Modified polycarbonate Ambient temperature Operating Storage 10 to 50 C 25 t...

Page 9: ...01961 REVISION 2 8 APPROVALS Applicable directive Approval Applicable standards Notified body CPR EN54 5 VdS No 0786 CPR 21198 VdS EN54 5 VdS2344 VdS2503 VdS No G208048 EMC EN61000 6 3 Emission EN5013...

Reviews: