background image

4. MOUNTING 

TECHNICAL DESCRIPTION 4318 

• DOCUMENT NUMBER: MEW01961 • REVISION: 

 

E+ 

Ext. LED, for example External indicator 2218; J2:2 (+)  

 

E- 

Ext. LED, for example External indicator 2218; J2:3 (-)  

 

3.2

 

ZONE LINE INPUT 

The conventional detector is connected to a zone line input (for conventional detectors) in the c.i.e. The 
last unit on the zone line has an End-of-line device to be connected. The type of end-of-line device is 
depending on the c.i.e. and the type of zone line input. 

4

 

MOUNTING 

The detector is plugged in a base. 
Place the detector in the base with the detector's "Mark" in the same position as the "Mark" on the base 
and turn the detector clockwise. 
 
 

 

 

Summary of Contents for 4318

Page 1: ...PANASONIC FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 4318 COMBINATION HEAT DETECTOR...

Page 2: ...INFORMATION DOCUMENT NAME TECHNICAL DESCRIPTION 4318 DOCUMENT NUMBER MEW01961 DATE OF ISSUE 2016 01 11 REV 2 DATE OF REVISION 2021 01 25 Panasonic Fire Security Europe AB Jungmansgatan 12 SE 211 11 M...

Page 3: ...1 REVISION 2 TABLE OF CONTENTS 1 INTRODUCTION 3 2 ABBREVIATIONS 3 3 GENERAL DESCRIPTION 4 3 1 DETECTOR 4 3 1 1 LATCHING 4 3 1 2 EXTERNAL LED 4 3 2 ZONE LINE INPUT 5 4 MOUNTING 5 5 INSTALLATION AND WIR...

Page 4: ...SION 2 1 INTRODUCTION This document describes the combination heat detector type number 4318 The document contains information about the product and instructions on how to mount and connect it 2 ABBRE...

Page 5: ...ETECTOR The sensing element is a thermistor The detector and will give an alarm within a response temperature range Static response temperature Category Temperature range 59 C A1 R 54 65 C The rate of...

Page 6: ...ctor is connected to a zone line input for conventional detectors in the c i e The last unit on the zone line has an End of line device to be connected The type of end of line device is depending on t...

Page 7: ...nnected to the base NOTE Screen wire termination is not provided DATA 2324 Wire size Min 0 65 mm 0 3 mm Wire size Max 1 6 mm 2 mm 6 TEST MODE For information about how to set a zone in test mode see P...

Page 8: ...limitation 0 015 mA Must be minimum 3 Rate of rise response 6 C min Short circuit isolator No Internal battery No Material Modified polycarbonate Ambient temperature Operating Storage 10 to 50 C 25 t...

Page 9: ...01961 REVISION 2 8 APPROVALS Applicable directive Approval Applicable standards Notified body CPR EN54 5 VdS No 0786 CPR 21198 VdS EN54 5 VdS2344 VdS2503 VdS No G208048 EMC EN61000 6 3 Emission EN5013...