background image

4479 ADDRESSABLE SOUNDER BASE 

 - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION

13

7.1. 

MOUNTING WITH INGRESS PROTECTION FOR SOUNDER 

BASE

If the sounder base is mounted with the cabling entering from above (through the inner ceiling), there is a need for an ingress pro

-

tection (type 4489) to maintain IP 21 of the sounder base. The ingress protection is white.

1.  Side towards ceiling

2.   Side towards sounder base

a)  Drill a hole in the inner ceiling.

b)  Gently cut off the top of the grades (marked red below) on the waterproof packing to open up the cable entry. Use a sharp 

knife.

c)  Draw the cables through the ceiling, through the ingress protection and through the sounder base. Connect the wires in the 

sounder base according to chapter 

8. INSTALLATION AND WIRING

 on page 15

.

d)  Fit the sounder base into the ingress protection.

e)  Mount the sounder base with screws onto the ceiling.

f)  Fit the detector onto the sounder base.

  3.  Ingress protection, type 4489

  4.  Sounder base

  5.  Wires

  6.  Detector

Ceiling

Summary of Contents for 4479

Page 1: ...4479 Fire alarm solutions technical description ADDRESSABLE SOUNDER BASE www panasonic fire security com...

Page 2: ...E 6 4 PROGRAMMABLE SOUNDER 6 4 1 PRIORITY LEVELS 6 4 2 NORMAL SPL 6 4 3 LOW POWER SPL 6 4 4 TONES 7 5 SET THE COM LOOP ADDRESS 9 5 1 AUTO ADDRESSING 9 5 2 MANUAL ADDRESSING 9 6 SET THE MODE 10 6 1 COM...

Page 3: ...FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 3 1 INTRODUCTION This document describes the Addressable sounder base type number 4479 The document contains information about the product and instructions o...

Page 4: ...4479 ADDRESSABLE SOUNDER BASE FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 4 2 ABBREVIATIONS dB Decibel SPL Sound Pressure Level dBA 1m...

Page 5: ...oor use and in dry premises The sounder base is mounted in the ceiling and the analog multi detector with isolator 4400I must be plugged in the base The base is connected to the COM loop The addressab...

Page 6: ...ve one tones for fire alarm activated somewhere in the whole building low priority another sound type for fire alarm activated on the same story floor medium priority and yet another sound type when t...

Page 7: ...75 105 135 165 15 45 75 105 135 165 SPL 78 9 85 4 87 1 85 1 77 1 81 5 83 6 78 8 86 6 86 8 78 6 84 With ingress protection type 4489 78 0 84 8 85 3 83 9 76 9 80 7 81 5 78 8 85 3 85 6 78 8 83 4 TONE 3...

Page 8: ...g NFS 32 001 Horizontal orientation L dB Vertical orientation L dB 554Hz 0 1s 440Hz 0 4s 15 45 75 105 135 165 15 45 75 105 135 165 SPL 78 4 83 2 84 1 83 7 77 0 80 1 82 2 77 6 84 2 84 7 78 6 82 8 With...

Page 9: ...4479 ADDRESSABLE SOUNDER BASE FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 9 Horizontal orientation Vertical orientation...

Page 10: ...lt address The 4479 has address 255 as default The 4400I has address 0 as default 5 2 MANUAL ADDRESSING If auto addressing is not used there is a possibility to manually set the address Each COM loop...

Page 11: ...MODE The 4479 is set to advanced mode by default 6 1 COMPATIBILITY TABLE Advanced mode NORMAL mode 2330 mode 2312 mode EBLOne V 3 3 Not used Not used Not used EBL512 G3 V 2 4 Not used Not used Not us...

Page 12: ...or 4400I you will have an open circuit If the addressable sounder base is mounted on an impenetrable ceiling for example concrete ceiling and with the cabling entering from the sides of the product th...

Page 13: ...under base a Drill a hole in the inner ceiling b Gently cut off the top of the grades marked red below on the waterproof packing to open up the cable entry Use a sharp knife c Draw the cables through...

Page 14: ...5 2 7 mm through the detector b Place the detector in the base with the detector s Mark in the same position as the Mark on the base and turn the detector clockwise c Attach the lock screw 1 5 mm Hex...

Page 15: ...28 mm 1 385 mm 1 50 mm SAo COM loop SA output SB COM loop SB input output X1 If necessary connect excess wires of fire alarm cable for 30DC or its ground only X2 If necessary connect excess wires of f...

Page 16: ...2 3 4 5 and 7 SPL Normal for tone 6 Sound Pressure Level Low power 90 3 dB A 87 3 dB A 84 dB A Not approved Address range 001 253 Address setting Auto addressing With address setting tool Short circui...

Page 17: ...10 APPROVALS Applicable directive Approval Applicable standards Notified body CPR EN 54 3 2001 A1 2002 A2 2006 VdS No 0786 CPR 21564 VdS EN54 3 VdS 2344 VdS 2543 VdS No G218002 EMC EN61000 6 3 Emissio...

Page 18: ...ESCRIPTION 4479 DOCUMENT NUMBER MEW02073 EN DATE OF ISSUE 2018 01 30 REV 4 DATE OF REVISION 2023 06 15 Panasonic Fire Security Europe AB Jungmansgatan 12 SE 211 11 Malm SE Tel 46 0 40 697 70 00 www pa...