Fire alarm systems 

Duct detector 

chamber 

6367 

 

Only one pipe is required 

 

Simple installation 

 

For conventional as well as analog and addressable systems 

General 

The Uniguard Duct detector chamber 

6367

 

is used when smoke is to be detected in a 
ventilation duct.  Both the "venturi pipe" and 
the housing, where a smoke detector is to be 
placed, are especially designed for optimum 
airflow through the detector.  The housing is 
made of grey ABS and the venturi pipe is 
made of aluminium.  Supplied with two 
compression glands for cable entry. 

6367 can be used in conventional as well as 
analog fire alarm systems, depending on the 
detector placed inside the housing. 

The Photoelectric smoke detector 4352, 
plugged in the base 2324, is used in a 
conventional system (zone line input).  An 
attached space ring (11 mm) is required 
between the base and the housing. 

The Analog photoelectric smoke detector 
4301, plugged in the analog base 3312, is 
used in an analog and addressable system.  
An attached space ring (19 mm) is required 
between the base and the housing. 

Venturi pipe 6371 

The venturi pipe is available in three lengths 
and can easily be shortened to suit the 
ventilation duct.  An attached plug is to be 
placed in the end of the pipe. 

A ventilation duct with a width < 0.6 m 
(diameter) requires a 0.6 m venturi pipe 
(6371-06), ended inside the duct. 

A ventilation duct with a width > 0.6 m 
(diameter) requires an 1.5 or 2.8 m venturi 
pipe (6371-15 / -28), ended outside the duct. 

See figure on the opposite page. 

Air flow indicator 

A built-in air flow indicator gives a 
confirmation that the air from the ventilation 
duct is flowing through the venturi pipe and 
the detector.  If not, a booster fan 6373 is 
available as an option. 

Accessories 

Bracket 

6372

, to be used when 6367 shall be 

mounted on a round ventilation duct.  See 
figure on the opposite page. 

Booster fan 

6373

, to be used when the air 

flow indicator is indicating no or very small 
air flow.  The fan shall be mounted inside 
the housing and connected to the terminal 
block.  External power supply (24 V AC, 50 
mA) is required. 

Filter 

6374

, can be used in an extremely 

dirty environment, as in a saw mill, a timber 
yard, etc.  The filter shall be placed inside 
the housing, in a slot just before the detector. 

Product applications 

The Duct detector chamber can be used in 
the systems EBL500 / 512 / 128 / 1000 / 
2000.  It is intended for indoor use and in 
dry premises. 