3.2 Stored Data of the Input Contact (WX)
3.2.1 Analog Input Values
Digital conversion values corresponding to the analog input are stored.
■
Applicable model
Model
Channel
AFPXHEAD4
CH0 to CH3
AFPXHEAD8
CH0 to CH7
AFPXHEA21
CH0 to CH1
■
Digital conversion values
Digital conversion values for each input range are as follows.
Input range
Digital conversion value
For -10 to +10 V, -5 to +5 V
K-32000 to K+32000
For 0 to +10 V, 0 to +5 V
K0 to K+32000
For +1 to +5 V
K0 to K+25600
For 0 to +20 mA
K0 to K+32000
For +4 to +20 mA
K0 to K+25600
■
Disconnection detection
● The disconnection detection is valid only when the range setting is set to +4 to +20 mA or +1
to +5 V.
● If a disconnection state is detected, H8000 (K-32768) is stored.
● The detection level for disconnection detection is as follows.
Input range
Detection level
For +1 to +5 V
0.7 V or less
For +4 to +20 mA
2.8 mA or less
■
I/O allocation
Channel
Expansion location
1st unit
2nd unit
3rd unit
4th unit
5th unit
6th unit
7th unit
8th unit
CH0
WX30
WX40
WX50
WX60
WX70
WX80
WX90
WX100
CH1
WX31
WX41
WX51
WX61
WX71
WX81
WX91
WX101
CH2
WX32
WX42
WX52
WX62
WX72
WX82
WX92
WX102
CH3
WX33
WX43
WX53
WX63
WX73
WX83
WX93
WX103
CH4
WX34
WX44
WX54
WX64
WX74
WX84
WX94
WX104
CH5
WX35
WX45
WX55
WX65
WX75
WX85
WX95
WX105
CH6
WX36
WX46
WX56
WX66
WX76
WX86
WX96
WX106
3.2 Stored Data of the Input Contact (WX)
3-6
WUME-FPXHAIO-01
Summary of Contents for AFPXHEAD4
Page 2: ...MEMO 2 WUME FPXHAIO 01...
Page 5: ...Indicates operation procedures WUME FPXHAIO 01 v...
Page 6: ...MEMO vi WUME FPXHAIO 01...
Page 26: ...MEMO 2 10 WUME FPXHAIO 01...
Page 42: ...3 4 Analog Input Functions 3 16 WUME FPXHAIO 01...
Page 46: ...3 5 Analog Output Functions 3 20 WUME FPXHAIO 01...
Page 56: ...MEMO 4 10 WUME FPXHAIO 01...
Page 62: ...MEMO 5 6 WUME FPXHAIO 01...
Page 72: ...MEMO 7 6 WUME FPXHAIO 01...
Page 75: ...MEMO WUME FPXHAIO 01...