Voltage output range: -5 to +5 V
Output range: -5 to +5 V
Digital input value
(K)
Analog output
value
(V)
+32,000
+5
+16,000
+2.5
0
0
-16,000
-2.5
-32,000
-5
When exceeding the rated range
Digital input value
Analog output
value
+32,640 or more
Output at +5.1 V
-32,640 or less
Output at -5.1 V
■
Current output range: 0 to +20 mA
Output range: 0 to +20 mA
Digital input value
(K)
Analog output value
(mA)
+32,000
+20
+25,600
+16
+19,200
+12
+12,800
+8
+6,400
+4
0
0
When exceeding the rated range
Digital input value
Analog output value
+32,640 or more
Output at +20.4 mA
Negative value
Output at 0 mA
4.2 Output Conversion Characteristics
4-8
WUME-FPXHAIO-01