41
No.
Function
name
Changes
during RUN
Setting range
Unit
Initial
value
P020 JOG
Acceleration
○
0.04 to 3600
0.01
[sec]*9
*4
P021 JOG
Deceleration
○
0.04 to 3600
0.01
[sec]*9
*4
P022
JOG
Operation
by Panel
-
0: JOG operation by panel disabled
1: JOG operation by panel enabled (JOG operation
by external control disabled)
2: JOG operation by panel enabled (JOG operation
by external control enabled)
-
0
P023
Electronic
Thermal
Selection
○
0: OL trip occurs with current up to 140% of its
rating for 1 minute.
1: Without output frequency derated
2: With output frequency derated
3: Forced air-cooled motor specification
-
2
P024
Thermal
Current
Setting
○
0.1 to 100.0
0.1[A]
*4
P025
Overcurrent
Stall
Prevention
Function
○
0: Overcurrent stall prevention function OFF
Overcurrent trip prevention function OFF
1: Overcurrent stall prevention function ON
Overcurrent trip prevention function ON
2: Overcurrent stall prevention function OFF
Overcurrent trip prevention function ON
3: Overcurrent stall prevention function ON
Overcurrent trip prevention function OFF
-
1
P026
Overvoltage
Stall
Prevention
Function
○
0: Stall prevention function OFF
1: Stall prevention function ON (Regenerative
braking resistor ON/OFF function disabled)
-
1
P027
Current
Limit
Function
○
0.0 · 0.1 to 9.9
0.1[sec]
0.0
P028 OCS Level
○
1 to 200
1[%]
140
P029
Retry
Function
Selection
○
0: No retry function
1: Only for abnormal overcurrent
2: Only for abnormal overvoltage
3: Only for abnormal overcurrent/overvoltage
-
0
P030
Retry
Count
○
1 to 10
1[times]
1
P031
Start Mode
-
0: Run
1: OP stop
2: Run after standby time elapse
3: OP stop (standby time)
-
1
P032
Ride-
through
Restart
Selection
-
0: Restart mode 1
1: Restart mode 2
2: Restart mode 3
3: Restart mode 4
-
0
P033
Standby
Time
○
0.1 to 100.0
0.1[sec]
0.1
Summary of Contents for AMK3000114
Page 59: ...58 ...