48
No.
Function name
Changes
during RUN
Setting range
Unit
Initial
value
P109
PWM Signal
Average Times
○
1 to 100
1[times]
1
P110
PWM Signal
Cycle
○
1.0 to 2000
0.1[msec]
1.0
P111
Analog Input
Filter
○
5 to 200
1[times]
10
P112
Bias Frequency
Setting
○
–99.0 to 250.0
0.1[%]
0.0
P113
Gain Frequency
Setting
○
0.0 to 500.0
0.1[%] 100.0
P114
Analog Direction
Mode
○
0: No setting
1: Analog input can be reversed.
(Forward
→
Reverse)
2: Analog input can be reversed.
(Reverse
→
Forward)
-
0
P115
2nd Bias
Frequency
Setting
○
–99.0 to 250.0
0.1[%]
0.0
P116
2nd Gain
Frequency
Setting
○
0.0 to 500.0
0.1[%] 100.0
P117
2nd Analog
Direction Mode
○
0: No setting
1: Analog input can be reversed.
(Forward
→
Reverse)
2: Analog input can be reversed.
(Reverse Forward)
-
0
P118
2nd Analog Input
Function
Selection
-
0: 2nd frequency setting signal
1: Measured value of PID control
(PV)
2: Base fre PID adjusted
value
3: Base frequency + Auxiliary
frequency setting signal
-
0
P119
2nd Analog Input
Signal
Selection
-
2
:
External control,0V to 5V
3
:
External control,0V to 10V
4
:
External control,4mA to 20mA
5
:
External control,0mA to 20mA
-
2
P120
Analog Output
Function
Selection
○
0: Output frequency
1: Output current
-
0
P121
PWM Output
Duty Ratio
Compensation
○
25 to 100
1[%]
100
Summary of Contents for AMK3000114