50
No.
Function name
Changes
during RUN
Setting range
Unit
Initial
value
P127
Detection
Frequency
(Output TR)
○
0.0, 0.2 to 400.0
0.1[Hz]
0.2
P128
Detection
Frequency
(Output RY)
○
0.0, 0.2 to 400.0
0.1[Hz]
0.2
P129 Current Detection
Level
○
0.1 to 100.0
0.1[A]
*4
P130 Current Detection
Delay Time
○
0.1 to 10.0
0.1[sec]
0.1
P131
RS485
Communication
Protocol*6
○
0
:
MEWTOCOL
1
:
Modbus
-
RTU
2
:
Modbus
-
ASCII
-
0
P132
RS485
Communication
Station No.*6
○
01 to 31
-
01
P133
RS485
Communication
Speed*6
○
48
:
4800
96
:
9600
192
:
19200
384
:
38400
576
:
57600
1152
:
115200
bps
1152
P134 RS485 Stop Bit
Length*6
○
1
:
1bit
2
:
2bit
bit
1
P135 RS485 Parity
Check*6
○
0: Without parity check
1: Odd parity
2: Even parity
-
0
P136 RS485 Timeout
Detection*6
○
0.0 · 0.1 to 60.0
0.1[sec]
0.0
P137
Waiting Time
for RS485
Transmission *6
○
1 to 1000
1[msec]
1
P138
Judging Time
for RS485 TEXT
Completion *6
○
3 to 200
1[msec]
3
P139 2nd Base
Frequency
45.0 to 400.0
0.1[Hz]
50.0
P140 2nd Torque Boost*7
○
0 to 40: Manual torque boost
Auto: Automatic torque boost
1[%]
*4
P141
2nd Electronic
Thermal Selection
○
0: OL trip occurs with current up to
140% of its rating for 1 minute.
1: Without output frequency derating
2: With output frequency derating
3: Forced air-cooled motor specification
-
2
P142 2nd Thermal
Current Setting
○
0.1 to 100.0
0.1[A]
*4
P143 2nd Change Point
Frequency 1
○
0.2 to 400.0
0.1[Hz]
0.2
P144
2nd Change Point
Voltage 1
○
0.0 to 100.0
0.1[%]
0.0
Summary of Contents for AMK3000114