52
█
P2 Parameter List
No.
Function name
Changes
during RUN
Setting range
Unit
Initial
value
P201
Load Rating
-
0: Heavy load rating
1: Light load rating
-
0
P202
Automatic Tuning
-
0: No tuning
1: All tuning
-
0
P203
Motor Capacity
-
0.2
:
0.2kW
0.4
:
0.4kW
0.7
:
0.75kW
1.5
:
1.5kW
2.2
:
2.2kW
3.7
:
3.7kW
5.5
:
5.5kW
7.5
:
7.5kW
11.
:
11kW
15.
:
15kW
-
*4
P204
Pole Number of
Motor
-
2
:
2-pole 4
:
4-pole 6
:
6-pole
Pole
4
P205
Motor Rated
Voltage
-
0 to 500
1[V]
*5
P206
Motor Rated
Frequency
-
10.0 to 120.0
0.1[Hz]
50.0
P207
Motor Rated
Current
-
0.01 to 99.99
0.01[A]
*4
P208
Primary Resistor
-
0.00 to 99.99 (*8)
0.01[
Ω
]
*4
P209
Secondary Resistor
-
0.00 to 99.99 (*8)
0.01[
Ω
]
*4
P210
Exciting Inductance
-
0.0 to 999.9 ,1000 to 5000 (in increments of
1 mH)
0.1[mH]
*4
P211
Leakage
Inductance
-
0.0 to 999.9
0.1[mH]
*4
P212
Exciting Current
-
0.01 to 99.99
0.01[A]
*4
P213
Speed Control
Proportion Amplitude
-
0.01 to 10.00
0.01
*4
P214
Speed Control
Integral Amplitude
-
0.01 to 10.00
0.01
*4
P215
Torque Limit Level
-
50 to 400
1[%]
*4
P216 2nd Motor Capacity
0.2
:
0.2kW
0.4
:
0.4kW
0.7
:
0.75kW
1.5
:
1.5kW
2.2
:
2.2kW
3.7
:
3.7kW
5.5
:
5.5kW
7.5
:
7.5kW
11.
:
11kW
15.
:
15kW
-
*4
P217 Pole Number of 2nd
Motor
2
:
2 Pole 4
:
4 Pole 6
:
6 Pole
Pole
4
P218 Rated Voltage of 2nd
Motor
0 to 500
1[V]
*5
P219
Rated Frequency of
2nd Motor
10.0 to 120.0
0.1[Hz]
50.0
P220 Rated Current of 2nd
Motor
0.01 to 99.99
0.01[A]
*4
P221
Primary Resistor of
2nd Motor
0.00 to 99.99 (*8)
0.01[
Ω
]
*4
P222
Secondary Resistor
of
2nd Motor
0.00 to 99.99 (*8)
0.01[
Ω
]
*4