14.20 Compressor Reverse Rotation Protection Control
•
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between
intake air and indoor heat exchanger is 2.5°C (cooling mode)/5°C (heating mode) or less for continuous 2
minutes, compressor will stop and restart automatically.
•
Time Delay Safety Control is activated before the compressor restart.
▲
T = Indoor heat exchange temperature - Intake air temperature (heating mode)
▲
T = Intake air temperature - Indoor heat exchanger temperature (cooling mode)
•
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
•
If this condition happens continuously for 5 times within 50 minutes, unit will turn OFF with TIMER LED blinks.
•
The 5 Times counter can be reset when either one of the following condition happen:
o
Unit is OFF by remote control or AUTO OFF/ON button.
o
Indoor intake temperature – Indoor piping temperature > 5°C for one minute or more.
o
Operation mode change.
•
The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
•
TIMER LED blinking will be reset if:
o
Indoor intake temperature – Indoor piping temperature > 5°C for one minute or more.
o
Power supply reset.
14.21 Dew Prevention Control
•
To prevent dew formation at indoor unit discharge area.
•
This control starts if:
o
Cooling mode or Quiet mode is activated.
o
Remote Control setting temperature is less than 25°C.
o
Fan speed is at Lo or QLo.
o
Room temperature is constant (±1°C) for 30 minutes.
o
Compressor is continuously running.
•
Fan speed, angle of horizontal louver (vertical airflow angle) and angle of vertical louver (horizontal airflow angle)
will be adjusted accordingly in this control.
o
Fan speed will be increased slowly if the unit is in quiet mode and Lo fan speed.
o
The angle of horizontal louver will be changed as table below:
o
The angle of vertical louver will be changed as table below:
•
Dew prevention stop condition
o
Remote control setting temperature is more than 25°C.
o
Fan speed is not set to Lo or QLo.
o
Select Powerful operation.
Summary of Contents for CS-A12PKD
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS A9PKD CS A12PKD...
Page 14: ...14 5 1 2 CS A18PKD CS A24PKD CS A28PKD...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU A9PKD 5 2 2 CU A12PKD...
Page 16: ...16 5 2 3 CU A18PKD...
Page 17: ...17 5 2 4 CU A24PKD CU A28PKD...
Page 18: ...18 6 Refrigeration Cycle Diagram 6 1 CS A9PKD CU A9PKD CS A12PKD CU A12PKD...
Page 19: ...19 6 2 CS A18PKD CU A18PKD CS A24PKD CU A24PKD CS A28PKD CU A28PKD...
Page 20: ...20 7 Block Diagram 7 1 CS A9PKD CU A9PKD...
Page 21: ...21 7 2 CS A12PKD CU A12PKD...
Page 22: ...22 7 3 CS A18PKD CU A18PKD CS A24PKD CU A24PKD...
Page 23: ...23 7 4 CS A28PKD CU A28PKD...
Page 28: ...28 9 Electronic Circuit Diagram 9 1 CS A9PKD CU A9PKD...
Page 29: ...29 9 2 CS A12PKD CU A12PKD...
Page 30: ...30 9 3 CS A18PKD CU A18PKD CS A24PKD CU A24PKD...
Page 31: ...31 9 4 CS A28PKD CU A28PKD...
Page 34: ...34 10 1 4 Comparator Printed Circuit Board 10 1 5 Human Activity Sensor Printed Circuit Board...
Page 40: ...40 11 2 5 Wire Stripping And Connecting Requirement...
Page 48: ...48 12 2 5 Wire Stripping And Connecting Requirement...
Page 87: ...87 Normal Deice Time Diagram Overload Deice Time Diagram...
Page 92: ...92 a Normal Deice Time Diagram b Overload Deice Time Diagram...
Page 98: ...98 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5...
Page 100: ...100 Figure 9 Figure 10...
Page 104: ...104 Figure 20 Figure 21...
Page 105: ...105 18 Technical Data 18 1 Thermostat Characteristics...