50
13.2 Protection Control For Cooling & Soft Dry Operation
13.2.1 Outdoor Air Temperature Control
•
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
•
This control will begin 1 minute after the compressor starts.
•
Compressor
frequency will adjust base on outdoor air temperature.
38°C
37°C
-5°C
-7°C
Outdoor
Air
Temperature
Free
OFF
Limited Frequency
13.2.2 Cooling Overload Control
•
Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation
frequency)
•
The compressor stop if outdoor pipe temperature exceeds 61°C.
•
If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95 indicated: outdoor high pressure rise
protection)
13.2.3 Freeze Prevention Control 1
1. When indoor heat exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stop
operating.
2. Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 5°C.
3. At the same time, indoor fan speed will be higher than during its normal operation.
4. If indoor heat exchanger temperature is higher than 5°C for 5 minutes, the fan speed will return to its normal
operation.
13.2.4 Freeze Prevention Control 2
1. Control start conditions
•
During Cooling operation and soft dry operation
o
During thermo OFF condition, indoor intake temperature is less than 10°C or
o
Compressor stops for freeze prevention control
•
Either one of the conditions above occurs 5 times in 60 minutes.
2. Control
contents
•
Operation
stops
•
Timer LED blinks and “H99” indicated
13.2.5 Dew Prevention Control 1
•
To prevent dew formation at indoor unit discharge area.
•
This control will be activated if:
o
Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled.
o
When Cooling or Dry mode is operated more than 20 minutes or more.
•
This control stopped if:
o
Compressor
stopped.
o
Remote control setting changed (fan speed / temperature).
o
Outdoor air temperature and indoor intake temperature changed.
•
Fan speed, angle of louver (vertical airflow angle) will be adjusted accordingly in this control.
o
Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
Summary of Contents for CS-AE9NKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 29: ...29 ...
Page 91: ...91 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Page 93: ...93 Figure 8 Figure 9 ...
Page 94: ...94 Figure 10 ...