8.2.3. Indoor Power Relay Control
Power relay will turn on during operation or in progress of stopping operation. Although operation stops, the power relay continues
on for three minutes.
However, during instantaneous power failure (< 0.5s), power relay will turn off. Then, it will turn on 3 minutes after power recover
and the unit will operate as previous operation condition.
8.2.4. Time Delay Safety Control
This control is applicable to all kinds of operation mode.
1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
8.2.5. 30 Seconds Forced Operation
This control is applicable to all kinds of operation mode.
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.
8.2.6. Total Running Current Control
This control is applicable to all kinds of operation mode.
1. When the total outdoor unit running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased a step to smaller frequency number.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased a step at one time
to bigger frequency number.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for three minutes.
Operation Mode
E9CKP
E12CKP/E15CKP
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (I)
4.5
17.0
6.5
17.0
Cooling/Soft Dry (II)
4.0
17.0
6.0
17.0
Heating
6.1
17.0
9.2
17.0
4. The first 30 minutes of cooling operation, (I) will be applied.
24
CS-E15CKP CU-E15CKP5
Summary of Contents for CS-E15CKP
Page 8: ...4 Dimensions 8 CS E15CKP CU E15CKP5 ...
Page 9: ...9 CS E15CKP CU E15CKP5 ...
Page 10: ...5 Refrigeration Cycle Diagram 10 CS E15CKP CU E15CKP5 ...
Page 11: ...6 Block Diagram 11 CS E15CKP CU E15CKP5 ...
Page 12: ...7 Wiring Diagram 12 CS E15CKP CU E15CKP5 ...
Page 39: ...IONIZE 42 43 44 41 39 CS E15CKP CU E15CKP5 ...
Page 40: ...IONIZER IONIZER IONIZER IONIZER 40 CS E15CKP CU E15CKP5 ...
Page 41: ...CZ SFD72P 41 CS E15CKP CU E15CKP5 ...
Page 42: ...42 CS E15CKP CU E15CKP5 ...
Page 43: ... H23 H27 H28 43 CS E15CKP CU E15CKP5 ...
Page 44: ...44 CS E15CKP CU E15CKP5 ...
Page 45: ...45 CS E15CKP CU E15CKP5 ...
Page 75: ...13 Technical Data 75 CS E15CKP CU E15CKP5 ...
Page 87: ...87 CS E15CKP CU E15CKP5 ...
Page 88: ...How to use electronic circuit diagram 88 CS E15CKP CU E15CKP5 ...
Page 89: ...18 1 REMOTE CONTROL 89 CS E15CKP CU E15CKP5 ...
Page 90: ...18 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD 90 CS E15CKP CU E15CKP5 ...
Page 91: ...18 3 PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD VIEW 91 CS E15CKP CU E15CKP5 ...
Page 92: ...92 CS E15CKP CU E15CKP5 ...
Page 93: ...93 CS E15CKP CU E15CKP5 MAICO Printed in Malaysia ...
Page 94: ......