Precautions
•
Be sure to read the instructions for the vacuum pump,
vacuum pump adaptor and manifold gauge prior to use,
and follow the instructions carefully.
•
Make sure that the vacuum pump is filled with oil up to
the designated line on the oil gauge.
•
The gas pressure back flow prevention valve on the
charging hose is generally open during use. When you
are removing the charging hose from the service port, it
will come off more easily if you close this valve.
Fig. 12 Vacuum pump air purging configuration
b. Copper pipes
Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is
exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily
distinguished from other piping materials, to prevent mistaken use.
3. Precautions during refrigerant piping work
Take the following precautions on-site when connecting pipes. (Keep in mind that the need to control the entry of moisture and
dust is even more important that in conventional piping).
a. Keep the open ends of all pipes sealed until connection with AC equipment is complete.
b. Take special care when doing piping work on rainy days. The entering of moisture will degrade the refrigerating machine oil,
and lead to malfunctions in the equipment.
c.
Complete all pipe connections in as short a time as possible. If the pipe must be left standing for a long time after removing
the seal, it must be thoroughly purged with nitrogen, or dried with a vacuum pump.
10.4. INSTALLATION, TRANSFERRING, SERVICING
10.4.1. Inspecting Gas Leaks with a Vacuum Pump for New Installations (Using New
Refrigerant Piping)
1. From the viewpoint of protecting the global environment, please do not release refrigerant into the atmosphere.
a. Connect the projecting side (pin-pushing side) of the charging hose for the manifold gauge to the service port of the 3-way
valve. (1)
b. Fully open the handle Lo of the manifold gauge and run the vacuum pump. (2) (If the needle of the low-pressure gauge
instantly reaches vacuum, re-check step a).)
c.
Continue the vacuum process for at least 15 minutes, then check to make sure the low-pressure gauge has reached -0.1
MPa (-76 cmHg). Once the vacuum process has finished, fully close the handle Lo of the manifold gauge and stop the
vacuum pump operation, then remove the charging hose that is connected to the vacuum pump adaptor. (Leave the unit in
that condition for 1-2 minutes, and make sure that the needle of the manifold gauge does not return.) (2) and (3)
d. Turn the valve stem of the 2-way valve 90 counter-clockwise to open it, then, after 10 seconds, close it and inspect for a gas
leak (4)
e. Remove the charging hose from the 3-way valve service port, then open both the 2-way valve and 3-way valve. (1) (4) (Turn
the valve stem in the counter-clockwise direction until it gently makes contact. Do not turn it forcefully).
f.
Tighten the service port cap with a torque wrench (18 N.m (1.8 kgf.m)). (5) Then tighten the 2-way valve and 3-way valve
caps with a torque wrench (42 N.m (4.2 kgf.m)) or (55 N.m (5.5 kgf.m)).
g. After attaching each of the caps, inspect for a gas leak around the cap area. (5) (6)
53
CS-E15CKP CU-E15CKP5
Summary of Contents for CS-E15CKP
Page 8: ...4 Dimensions 8 CS E15CKP CU E15CKP5 ...
Page 9: ...9 CS E15CKP CU E15CKP5 ...
Page 10: ...5 Refrigeration Cycle Diagram 10 CS E15CKP CU E15CKP5 ...
Page 11: ...6 Block Diagram 11 CS E15CKP CU E15CKP5 ...
Page 12: ...7 Wiring Diagram 12 CS E15CKP CU E15CKP5 ...
Page 39: ...IONIZE 42 43 44 41 39 CS E15CKP CU E15CKP5 ...
Page 40: ...IONIZER IONIZER IONIZER IONIZER 40 CS E15CKP CU E15CKP5 ...
Page 41: ...CZ SFD72P 41 CS E15CKP CU E15CKP5 ...
Page 42: ...42 CS E15CKP CU E15CKP5 ...
Page 43: ... H23 H27 H28 43 CS E15CKP CU E15CKP5 ...
Page 44: ...44 CS E15CKP CU E15CKP5 ...
Page 45: ...45 CS E15CKP CU E15CKP5 ...
Page 75: ...13 Technical Data 75 CS E15CKP CU E15CKP5 ...
Page 87: ...87 CS E15CKP CU E15CKP5 ...
Page 88: ...How to use electronic circuit diagram 88 CS E15CKP CU E15CKP5 ...
Page 89: ...18 1 REMOTE CONTROL 89 CS E15CKP CU E15CKP5 ...
Page 90: ...18 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD 90 CS E15CKP CU E15CKP5 ...
Page 91: ...18 3 PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD VIEW 91 CS E15CKP CU E15CKP5 ...
Page 92: ...92 CS E15CKP CU E15CKP5 ...
Page 93: ...93 CS E15CKP CU E15CKP5 MAICO Printed in Malaysia ...
Page 94: ......