48
13.1.5.
Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency
are as below figure.
If compressor discharge temperature exceeds 112
°
C, compressor will be stop, occurs 4 times per 20 minutes, timer LED will be
blinking (“F97” is to be confirmed).
13.1.6.
Low Pressure Prevention Control (Gas Leakage Detection)
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4
°
C.
• During Heating operations :
Indoor piping temperature - indoor suction is under 5
°
C.
b. Control contents
• Compressor stops (and restart after 3 minutes).
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated.
13.1.7.
Low Frequency Protection Control 1
• When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency will be changed
to 23 Hz for 2 minutes.
13.1.8.
Low Frequency Protection Control 2
• When all the below conditions comply, the compressor frequency will change to lower frequency.
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (
°
C)
T < 15 or T
30
—
Outdoor air (
°
C)
T < 16 or T
38
T < 4 or T
24
Indoor heat exchanger (
°
C)
T < 30
T
0
Summary of Contents for CS-E24LKES
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 12: ...12 6 Refrigeration Cycle Diagram ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit 8 2 1 CU E24LKE ...
Page 16: ...16 8 2 2 CU E28LKE ...
Page 17: ...17 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 18: ...18 9 2 Outdoor Unit 9 2 1 CU E24LKE ...
Page 19: ...19 9 2 2 CU E28LKE ...
Page 20: ...20 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 24: ...24 10 2 2 Power Printed Circuit Board ...
Page 90: ...90 16 1 3 To remove power electronic controller ...
Page 91: ...91 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Page 92: ...92 16 1 6 To remove cross flow fan and indoor fan motor ...
Page 93: ...93 ...