57
H37
Outdoor liquid pipe temperature sensor
abnormality
Continuous for 5s Cooling protection
operation only
• Outdoor liquid pipe
temperature sensor
open or short circuit
• Outdoor liquid pipe
temperature sensor
lead wire and
connector
H38
Indoor / outdoor mismatch
(brand code)
—
—
• Brand code not
match
• Check indoor unit
and outdoor unit
H39
Abnormal indoor operating unit or
standby units
3 times happen
within 40 minutes
—
• Wrong wiring and
connecting pipe,
expansion valve
abnormality, indoor
heat exchanger
sensor open circuit
• Check indoor /
outdoor connection
wire and connection
pipe, indoor heat
exchanger sensor
lead wire and
connector,
expansion valve and
lead wire and
connector
H41
Abnormal wiring or piping connection
—
—
• Wrong wiring and
connecting pipe,
expansion valve
abnormality
• Check indoor /
outdoor connection
wire and connection
pipe, expansion valve
and lead wire and
connector
H58
Indoor gas sensor abnormality
Continuous for 6
hours
—
• Indoor gas sensor
open or short circuit
• Indoor gas sensor,
indoor PCB
H59
Eco Patrol sensor abnormality
Continuous for 70
sec.
—
• Eco Patrol sensor
open or short circuit
• Eco Patrol sensor
• Eco Patrol & indoor
PCB
H64
Outdoor high pressure sensor
abnormality
Continuous for 1
minutes
—
• High pressure
sensor open circuit
during compressor
stop
• High pressure
sensor, lead wire and
connector
H97
Outdoor fan motor mechanism lock
2 times happen
within 30 minutes
—
• Outdoor fan motor
lock or feedback
abnormal
• Outdoor fan motor
lead wire and
connector, fan motor
lock or block
H98
Indoor high pressure protection
—
—
• Indoor high pressure
protection (Heating)
• Check indoor heat
exchanger, air filter
dirty, air circulation
short circuit
H99
Indoor operating unit freeze protection
—
—
• Indoor freeze
protection (Cooling)
• Check indoor heat
exchanger, air filter
dirty, air circulation
short circuit
F11
4-way valve switching abnormality
4 times happen
within 30 minutes
—
• 4-way valve
switching abnormal
• 4-way valve, lead
wire and connector
F17
Indoor standby units freezing
abnormality
3 times happen
within 40 minutes
—
• Wrong wiring and
connecting pipe,
expansion valve
leakage, indoor heat
exchanger sensor
open circuit
• Check indoor /
outdoor connection
wire and pipe, indoor
heat exchanger
sensor lead wire and
connector,
expansion valve lead
wire and connector
F90
Power factor correction (PFC) circuit
protection
4 times happen
within 10 minutes
—
• Power factor
correction circuit
abnormal
• Outdoor PCB faulty
F91
Refrigeration cycle abnormality
2 times happen
within 20 minutes
—
• Refrigeration cycle
abnormal
• Insufficient
refrigerant or valve
close
F93
Compressor abnormal revolution
4 times happen
within 20 minutes
—
• Compressor
abnormal revolution
• Power transistor
module faulty or
compressor lock
F94
Compressor discharge pressure
overshoot protection
4 times happen
within 30 minutes
—
• Compressor
discharge pressure
overshoot
• Check refrigeration
system
F95
Outdoor cooling high pressure
protection
4 times happen
within 20 minutes
—
• Cooling high
pressure protection
• Check refrigeration
system, outdoor air
circuit
Summary of Contents for CS-E24LKES
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 12: ...12 6 Refrigeration Cycle Diagram ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit 8 2 1 CU E24LKE ...
Page 16: ...16 8 2 2 CU E28LKE ...
Page 17: ...17 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 18: ...18 9 2 Outdoor Unit 9 2 1 CU E24LKE ...
Page 19: ...19 9 2 2 CU E28LKE ...
Page 20: ...20 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 24: ...24 10 2 2 Power Printed Circuit Board ...
Page 90: ...90 16 1 3 To remove power electronic controller ...
Page 91: ...91 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Page 92: ...92 16 1 6 To remove cross flow fan and indoor fan motor ...
Page 93: ...93 ...