11

4 Troubleshooting Guide

4.1.

During twin operation

System example

1. The main power is turned on while the transmission wires between the indoor units are not connected.

(open circuit at A or B)
Symptom
Remote control unit: “check” flashes
Error code: F30-01 (connected indoor capacity error)
Indoor unit No. 1: LED1 on P.C.B flashes
Indoor unit No. 2: no power supply
Outdoor unit: LED6, 7 on P.C.B flashes (connected indoor capacity error)

2. The main power is turned on while the transmission wires between the indoor units are not connected.

(open circuit at section C)
Symptom
Remote control unit: “check” flashes
Error code: F30-01 (connected indoor capacity error)
Indoor unit No. 1: LED1 on P.C.B flashes
Indoor unit No. 2: no power supply
Outdoor unit: LED5, 6 on P.C.B flashes (connected indoor capacity error)

3. The main power is turned on and the connection wire is all ok.

If operation starts in this condition, combination of the B50DBE8 outdoor unit and F24DB4E5 indoor unit will result in
abnormal operation.
Symptom
Remote control unit: “check” flashes
Error code: F30-01 (connected indoor capacity error)

Summary of Contents for CS-F14DB4E5

Page 1: ...F14DB4E5 CU J28DBE5 3 2 2 CS F14DB4E5 CU J28DBE8 4 2 3 CS F18DB4E5 CU J34DBE5 5 2 4 CS F18DB4E5 CU J34DBE8 6 2 5 CS F24DB4E5 CU J43DBE8 7 2 6 CS F28DB4E5 CU J50DBE8 8 3 Twin Systems 9 3 1 Installation...

Page 2: ...ible Indoor units with same horsepowers can even be used in combination Master unit and slave units can be set automatically in twin systems No address setting is necessary Multiple indoor units can b...

Page 3: ...ype Drain mm O D 20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 1 phase brushless motor Rated Output kW 2 0 Fan Type Number of Set Turbo...

Page 4: ...O D 20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 2 0 Fan Type Number of Set Turbo fan 1 Mix f...

Page 5: ...0 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 1 phase brushless motor Rated Output kW 3 0 Fan Type Number of Set Turbo fan 1 Mix flow fa...

Page 6: ...20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 3 0 Fan Type Number of Set Turbo fan 1 Mix flow...

Page 7: ...D 20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 3 75 Fan Type Number of Set Turbo fan 1 Mix flo...

Page 8: ...D 20 I D 20 Compressor Type Number of Set Hermetic 1 Starting Method Permanent Split Capacitor Motor Type 2 pole 3 phase brushless motor Rated Output kW 4 5 Fan Type Number of Set Turbo fan 1 Mix flow...

Page 9: ...9 3 Twin Systems 3 1 Installation Manual...

Page 10: ...10...

Page 11: ...er is turned on while the transmission wires between the indoor units are not connected open circuit at section C Symptom Remote control unit check flashes Error code F30 01 connected indoor capacity...

Page 12: ...unit check flashes Error code F30 01 connected indoor capacity error Indoor unit LED1 on P C B flashes Outdoor unit LED6 7 on P C B flashes connected indoor capacity error Remedy 1 Turn off the main...

Reviews: