4
Printed on
container box
For unit & PVC
tube connection
For drain hose
connection
Remarks
Q’ty
For full-scale
installation
diagram
1
2
4
4
4
4
2
1
For temporarily
suspending indoor
unit from ceiling
Flare
insulation
For wide /
narrow tube
connection
For wide /
narrow tube /
flare nut connection
For flare / drain
insulating
connection
For drain tube
connection
Insulation tape
Vinyl tie
Drain hose
insulation
Washer
AAA alkaline
battery
Remote
controller
Remote control
holder
Parts
Parts
Figure
Remarks
Q’ty
Figure
Drain hose
Full-scale
installation
diagram
5-1/2"(L140)
Hose band
Truss head screw
Truss head screw
Special screw
Cushion rubber
Tapping screw
8
2
set
2
8
1
1
1
2
1/8"(T3)
3/16"(T5)
13/32"(T10)
3/32"(T2)
Truss-head Phillips
5/32 5/8"
(4 16mm)
3/16 13/32"
(5 10mm)
5/32 15/32"
(4 12mm)
3/16 1-9/16"
(5 40mm)
Packed in the
outdoor unit
Packed in the
ceiling panel
Use M10 or 3/8" for suspension bolts.
Suspension bolts and nuts (locally purchased)
Model
Narrow Tube
Wide Tube
Outer Dia.
Thickness
Outer Dia.
Thickness
CS-KE12NB41
1/4" (6.35 mm)
0.0314" (0.8 mm)
3/8" (9.52 mm)
0.0314" (0.8 mm)
CS-KE18NB4UW
1/4" (6.35 mm)
0.0314" (0.8 mm)
1/2" (12.70 mm)
0.0314" (0.8 mm)
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instruc-
tions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
Table 1
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide
tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1.
Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4" (30 cm to 40 cm) to dampen vibration between units.
2.
Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness
of the insulation should be not less than 5/16" (8 mm).
3.
Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-7. Wiring
Instructions for details.
Table 2
CAUTION
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.