Symbol
Diagnosis
Diagnosis method
H99
Indoor operating unit
freezing
The restriction on the compressor frequency is started when the indoor unit heat exchanger temperature is
between 8 °C and 12 °C. Operation stops if a temperature below 0 °C continues for 6 minutes. Three minutes
later, operation is started up at a temperature from 3 °C to 8 °C. The restriction on the compressor frequency
is released at a temperature between 13 °C and 14 °C.
<Diagnosis checkpoint>
1.
A cooling or dry mode operation conducted at a low outside air temperature is mainly to blame:
this is not indicative of any malfunctioning.
If the outside air temperature rises during automatic operation in the winter months, the dry mode
operation is selected. The H99 diagnostic display also appears at such a time.
2.
Check the refrigerating cycle: Gas may be leaking (the amount of refrigerant is low) or a pipe may be
broken, etc.
3.
Check also for short circuits indoors and clogging of the air filters.
F11
4-way valve switching
failure
When a difference of 0 °C to 5 °C has been detected between the outdoor unit heat exchanger temperature
and liquid side pipe temperature on 5 occasions, the trouble display appears.
<Diagnosis checkpoint>
1.
Check the 4-way valve coil: Check that no power is supplied to the coil during cooling and dry mode
operations, and that power is supplied during heating operations. Inspect the coil for broken wires (open
circuits).
2.
If the coil is trouble-free, the switching action of the 4-way valve may be defective.
F17
Indoor standby units
freezing
When the difference of an intake temperature (room temperature sensor) and the indoor unit heat exchanger
temperature (piping sensor) is higher than 10 °C or an indoor unit heat exchanger temperature of below -1 °C
has been detected continuously for 5 minutes, operation stops. Three minutes later, it is started up, and the
trouble display appears when this has occurred on 3 consecutive occasions.
<Diagnosis checkpoint>
1.
Check the refrigerating cycle: Expansion valve leakage
2.
Check the indoor unit pipe temperature sensor (check for changes in its characteristics and check its
resistance).
F90
PFC circuit protection When a DC voltage over 393V to 424V has been detected on 16 occasions, this trouble display appears.
<Diagnosis checkpoint>
1.
To check whether the shutting valve has been left close by mistake, operation is performed for one to
several minutes after the compressor has started up, F93 is stored in the memory as the symptom, and
operation stops.
2.
Check the inverter circuit (for open circuits) in the control P.C. Board: Check the IPM base current (6
locations) within 3 minutes after the power has been turned back on. As the symptom, F93 is stored in the
memory 30 seconds after the compressor has started up, and operation stops. The trouble display
appears after 4 restarts.
3.
Check for broken wires (open circuits) in the compressor winding: Approximately 1 ohm under normal
conditions for each phase (same symptom as in 2.)
4.
Check the power supply voltage has been fluctuating or not.
F91
Refrigeration cycle
abnormality
When the compressor frequency is above 55 Hz and the current drops below the prescribed level continuously
for 7 minutes, operation stops, and it is restarted 3 minutes later.
When the compressor discharge temperature has exceeded the setting and the expansion valve has remained
fully open for 80 seconds, operation stops, and it is restarted 3 minutes later.
When the stopping described above has occurred on 4 occasions, operation stops, and the trouble display
appears.
<Diagnosis checkpoint>
1.
Check the refrigerating cycle: Gas may be leaking (more than one-half of the volume of the gas has gone).
The diagnostic displays resulting from a gas leak generally change in the following sequence depending
on the extent of the gas leak: H99
→
F97
→
F91
→
H16.
The range of this trouble (F91) is limited. (Compressor protection at the start of the season)
F93
Compressor
abnormal revolution
When a state in which the rotation of the compressor is not synchronized with the control signal has been
detected on 8 successive occasions, operation stops, and the trouble display appears.
<Diagnosis checkpoint>
1.
To check whether the shutting valve has been left close by mistake, operation is performed for one to
several minutes after the compressor has started up, F93 is stored in the memory as the symptom, and
operation stops.
2.
Check the inverter circuit (for open circuits) in the control P.C. Board: Check the IPM base current (6
locations) within 3 minutes after the power has been turned back on. As the symptom, F93 is stored in the
memory 30 seconds after the compressor has started up, and operation stops. The trouble display
appears after 4 restarts.
3.
Check for broken wires (open circuits) in the compressor winding: Approximately 1 ohm under normal
conditions for each phase (same symptom as in 2.)
F95
Outdoor high
pressure protection
CU-2E only
When the temperature of the outdoor unit heat exchanger temperature sensor exceeds 62 °C, the F95
diagnostic symbol is stored in the memory, and operation stops. 13 minutes later, operation is restarted at a
temperature below 48 °C. This trouble display appears when this happens on 4 occasions in a 20-minute
period.
<Diagnosis checkpoint>
1.
Check the outdoor unit heat exchanger temperature sensor (check for changes in its characteristics and
check its resistance).
2.
Check whether something is interfering with the dissipation of the heat outdoors.
28
CS-ME7CB1P / CS-ME10CB1P / CS-ME12CB1P / CS-ME14CB1P / CS-ME10CD3P / CS-ME14CD3P
Summary of Contents for CS-ME7CB1P
Page 5: ...3 2 INDOOR UNIT 5 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P...
Page 6: ...6 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P...
Page 9: ...9 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P...
Page 10: ...5 2 Grille 10 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P...
Page 11: ...5 3 Duct Type 11 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P...
Page 19: ...19 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P...
Page 60: ...60 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P...
Page 61: ...61 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P...
Page 62: ...62 CS ME7CB1P CS ME10CB1P CS ME12CB1P CS ME14CB1P CS ME10CD3P CS ME14CD3P...