background image

37 

Outdoor Unit Installation Guidelines 

š

Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation
guidelines below.

š

For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4" (1200 mm) or
less.

10.2.2  Install The Outdoor Unit

š

After selecting the best location, start installation
to Indoor/Outdoor Unit Installation Diagram.
1. Firmly attach the unit horizontally to concrete

or a rigid frame with bolts and nuts (ø13/32"
(ø10 mm)).

2. When installing on a roof, please consider

strong winds and earthquakes.
Please fasten the installation stand firmly with
bolts or nails.

Model

A

B

C

D

CU-4E24*** 

24-13/32"
(620 mm)

6-11/16"

(170 mm)

25/32" 

(20 mm) 

14-31/32"

(380.5 mm)

10.2.3  Connect The Piping

š

Remove the cabinet side plate (metal) from the
unit by loosening six screws.

Connecting The Piping To Outdoor Unit 

Decide piping length and then cut by using pipe cutter. 
Remove burrs from cut edge. Make flare after 
inserting the flare nut (locate at valve) onto the copper 
pipe. 
Align center of piping to valves and then tighten with 
torque wrench to the specified torque as stated in the 
table. 

Do not over tighten, over tightening may cause gas leakage 

Piping size 

Torque 

1/4" [6.35 mm] 

13.3 Ibf•ft [18 N•m (1.8 kgf•m)] 

3/8" [9.52 mm] 

31.0 Ibf•ft [42 N•m (4.3 kgf•m)] 

1/2" [12.7 mm] 

40.6 Ibf•ft [55 N•m (5.6 kgf•m)] 

5/8" [15.88 mm] 

47.9 Ibf•ft [65 N•m (6.6 kgf•m)] 

3/4" [19.05 mm] 

73.8 Ibf•ft [100 N•m (10.2 kgf•m)] 

Gas Leak Checking 

Pressure test to system to 400 PSIG with dry nitrogen, 
in stages. 
Thoroughly leak check the system. 
If the pressure holds, release the nitrogen and 
proceed to section 10.2.4.

 

Wall facing one side

More than 3

15

/

16

" (100)

w

e

i

v

p

o

T

w

e

i

v

e

d

i

S

47

1

/

4

" (1200)

or less

More than
39

3

/

8

" (1000)

More than
39

3

/

8

" (1000)

More than
3

15

/

16

" (100)

More than
3

15

/

16

" (100)

More
than
3

15

/

16

"

(100)

More than
3

15

/

16

" (100)

More than
39

3

/

8

" (1000)

More than
11

13

/

16

" (300)

Walls facing two side

Walls facing three side

Top view

Unit : inch (mm)

A

B

C

D

A

B

C

D

Torque Wrench for Flare Nut
and Pipe Size Expander

Packing

Pipe Size
Expander

Flare Nut

(Connection Pipe)

Screw

Screw

Cabinet side plate

Flare Nut

Torque Wrench for
Flare Nut

(Connection Pipe)

(Connection Pipe)

Applicable to
Liquid and Gas side of
CS-ME5***,
CS-ME7***,
CS-E9***,
CS-E12***,
CS-E18***

Liquid side of
CS-E24***

Applicable to
Gas side of
CS-E24***

Torque Wrench for
Flare Nut

Flare Nut

Female side

Female side

Male side

Male side

Summary of Contents for CS-MKS7NKU

Page 1: ...laced with manufacturer s specified parts to prevent shock fire or other hazards Do not modify the original design without permission of manufacturer WARNING This service information is designed for e...

Page 2: ...YES YES YES YES YES YES YES YES YES YES NO YES YES CS MKS9NKU CS MKS12NKU CS MKS18NKU CS MKS24NKU Wall Mounted Type CU 3KS19NBU CU 4KS24NBU CU 4KS31NBU Multi Outdoor Unit Indoor Unit 3 Room 4 Room 4...

Page 3: ...connecting tube kit CZ 3F type Unit A Maximum pipe length 25 m 82 0 ft Unit B Maximum pipe length 25 m 82 0 ft Unit C Maximum pipe length 25 m 82 0 ft Indoor outdoor unit connection cables Flexible co...

Page 4: ...imum pipe length 25 m 82 0 ft Unit B Maximum pipe length 25 m 82 0 ft Unit C Maximum pipe length 25 m 82 0 ft Unit D Maximum pipe length 25 m 82 0 ft Indoor outdoor unit connection cables Flexible cor...

Page 5: ...ngth Outdoor Unit CU 3E19 Allowable piping length of each indoor unit min max 9 8 ft 82 0 ft 3 m 25 m Allowable total piping length of all indoor unit 164 0 ft 50 m or less Height difference between i...

Page 6: ...he copper pipe Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table Do not over tighten over tightening may cause gas leakage Piping size...

Page 7: ...3 3 Ibf ft 18 N m with a torque wrench 7 Remove the valve caps of both of the 2 way valve and 3 way valve Position both of the valves to Open using a hexagonal wrench 5 32 4 mm 8 Mount valve caps onto...

Page 8: ...it A Unit C Terminal Terminal Indoor Unit B Indoor Unit A Disconnect Switch Field supply Grounding wire Grounding wire min AWG16 Grounding wire min AWG16 Grounding wire min AWG16 Power Supply Single P...

Page 9: ...terial shall withstand 248 F 120 C or higher Gas side pipes 10 1 7 Disposal Of Outdoor Unit Drain Water If a drain elbow is used the unit should be placed on a stand which is taller than 1 31 32 50 mm...

Page 10: ...Unit Installation Diagram Allowable piping length Outdoor Unit CU 4E24 Allowable piping length of each indoor unit min max 9 8 ft 82 0 ft 3 m 25 m Allowable total piping length of all indoor unit 229...

Page 11: ...ench to the specified torque as stated in the table Do not over tighten over tightening may cause gas leakage Piping size Torque 1 4 6 35 mm 13 3 Ibf ft 18 N m 1 8 kgf m 3 8 9 52 mm 31 0 Ibf ft 42 N m...

Page 12: ...of 13 3 Ibf ft 18 N m with a torque wrench 7 Remove the valve caps of both the 2 way valve and 3 way valve Position both of the valves to Open using a hexagonal wrench 5 32 4 mm 8 Mount valve caps ont...

Page 13: ...g wire Power Supply Single Phase 208 230V 60Hz min AWG12 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG1...

Page 14: ...terial shall withstand 248 F 120 C or higher Gas side pipes 10 2 7 Disposal Of Outdoor Unit Drain Water If a drain elbow is used the unit should be placed on a stand which is taller than 1 31 32 50 mm...

Reviews: