background image

12

3-6-5.  Checking After Installation

Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling sur-
face. Gaps may cause water leakage and condensation.

Check that the wiring is securely connected. 
If it is not securely connected, the auto flap will not operate. In addition, water leakage and condensation may occur.

3-6-6.  When Removing the Ceiling Panel for Servicing

When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the flap and the indi-
cator wiring connectors inside the control box, and then remove the 4 mounting screws.

3-6-7.  Adjusting the Auto Flap

The air-direction flap on the ceiling panel outlet can be adjusted as follows.

Adjust the flap to the desired angle using the remote controller. The flap also has an automatic air-sweeping mecha-
nism.

Never attempt to move the flap by hand.

Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or
heating seems inadequate, try changing the direction of the air flow.

3-7.  Wiring Instructions

General precautions on wiring

(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely fol-

lowing the wiring diagram.

(2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit breaker for

overcurrent protection provided in the exclusive line.

(3) To prevent possible hazards due to insulation failure, the unit must be grounded.

(4) Each wiring connection must be done tightly and in accordance with the wiring system diagram. Wrong wiring may

cause the unit to misoperate or become damaged.

(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility

for any damage or misoperation that occurs as a result of such unauthorized changes.

NOT

E

Fig. 8

1

3

2

Earth screw

Clamping strap

(Conduit)

Inter unit

Power wiring 
(Locally purchased)

3-8.  Wiring Instructions for Inter-unit Connections

(1) Remove the 1 screw from the terminal cover, then open the

cover. Be careful that the cover does not fall.

(2) Remove the 3 screws from the power box cover, then open

the cover. Be careful that the cover does not fall.

(3) Use the screw to securely fasten the ground wire from the

outdoor unit in place.

(4) Remove the transparent plastic cover from the 3P terminal

plate.

(5) While viewing the wiring diagram, connect the inter-unit and

power supply line to terminals 1, 2 and 3 on the 3P terminal
plate.

(6) Remount the transparent plastic cover onto the 3P terminal

plate.

(7) Be sure to use the clamping strap to fasten the wires in place.

(8) Tighten the screws to remount the terminal and the power

box cover.

Summary of Contents for CS-MKS9NB4U

Page 1: ...A 3 INSTALLATION INSTRUCTIONS CS MKS9NB4U CZ 18BT1U CS MKS12NB4U CZ 18BT1U CS KS18NB4UW CZ 18BT1U APPENDIX C 852 6 4190 582 00 0...

Page 2: ...THE INDOOR UNIT 7 3 1 Preparation for Suspending 3 2 Suspending the Indoor Unit 3 3 Placing the Unit Inside the Ceiling 3 4 Installing the Drain Piping 3 5 Checking the Drainage 3 6 How to Install the...

Page 3: ...zard 7R SUHYHQW SRVVLEOH KD DUGV IURP LQVXODWLRQ IDLOXUH the unit must be grounded When Transporting Be careful when picking up and moving the indoor and out door units Get a partner to help and bend...

Page 4: ...ILQJHUV DQG FORWKLQJ DZD IURP DQ PRYLQJ parts OHDQ XS WKH VLWH DIWHU RX ILQLVK UHPHPEHULQJ WR FKHFN that no metal scraps or bits of wiring have been left inside the unit being serviced Others 9HQWLODW...

Page 5: ...its and make sure all accessory parts listed are with the system before beginning 1 1 Tools Required for Installation not supplied 1 Standard screwdriver 2 Phillips head screwdriver 3 Knife or wire st...

Page 6: ...tion from which every corner of the room can be uniformly cooled select a location that will hold the weight of the unit select a location where tubing and drain hose have the shortest run to the outs...

Page 7: ...s securely If a tube is left open for an extended time moisture in the air inside the tubing may condense into water droplets and lead to water contamination of the refrig erant circuit In order to pr...

Page 8: ...am The dia gram shows the relationship between the positions of the suspension fitting unit and panel Fig 6 2 3 3 Placing the Unit Inside the Ceiling 1 Be sure to remove the fan protection 4pcs for tr...

Page 9: ...l the drain hose first place 1 of the 2 hose bands over the unit drain port and the other hose band over the hard PVC pipe not supplied Then connect both ends of the supplied drain hose Fig 6 5 3 On t...

Page 10: ...it position 1 Check that the ceiling hole is 23 5 8 600 mm 23 5 8 600 mm Fig 6 11 2 Confirm that the position of the indoor unit and the ceiling as shown in the diagram If the positions of the ceiling...

Page 11: ...the unit and the ceiling panel or between the ceiling panel and the ceiling surface If there is a gap between the panel and the ceiling leave the ceiling panel attached and make fine adjustments to th...

Page 12: ...gnal will not be received If the connectors are not connected the auto flap will not operate Be sure to connect them securely A Attaching the corner cover 1 Check that the safety strap from the corner...

Page 13: ...sed exclusively for each unit with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line 3 To prevent possible hazards due to insulation failure the u...

Page 14: ...the terminal screw 4 Shape the loop wire properly place it on the termi nal plate and fix it securely with the removed termi nal screw using a screwdriver For stranded wiring 1 Cut the wire end with a...

Page 15: ...PLQXWHV WKH V VWHP VKLIWV LQWR FRROLQJ operation and cool air will start to be felt Cooling mode test run is unaffected by the room tempera ture 3 Press the ON OFF operation button of the remote cont...

Page 16: ...re is an obstacle between the remote con troller and the air conditioner since a check signal is sent from the remote controller every 5 minutes 5 1 Mounting on a Wall Before mounting the remote contr...

Page 17: ...hen SUHVV DQG KROG WKH 5HVHW EXWWRQ ZLWK D pointed object such as the tip of a pen After 5 VHFRQGV UHOHDVH WKH EXWWRQ ILUVW WKHQ release the HIGH POWER and 1HR TIMER but tons oP 1 Test Run appears bli...

Page 18: ...stalled level and vertically The power and voltage are as specified Inter unit cables are securely inserted into the terminal block Inter unit cables are securely fixed The power cable and inter unit...

Reviews: