8. Removal and evacuation

• When breaking into the refrigerant circuit 

to make repairs – or for any other purpose 
– conventional procedures shall be used. 
However, it is important that best practice is 
followed since fl ammability is a consideration. 
The following procedure shall be adhered to: 
remove refrigerant -> purge the circuit with 
inert gas -> evacuate -> purge with inert gas 
-> open the circuit by cutting or brazing.

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be purged with OFN to 

render the appliance safe.

• This process may need to be repeated 

several times.

• Compressed air or oxygen shall not be used 

for this task.

• Purging shall be achieved by breaking 

the vacuum in the system with OFN and 
continuing to fi ll until the working pressure is 
achieved, then venting to atmosphere, and 
fi nally pulling down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the fi nal OFN charge is used, the 

system shall be vented down to atmospheric 
pressure to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any potential ignition sources and 
there is ventilation available.

OFN =  oxygen free nitrogen, type of 

inert gas.

 

9. Charging procedures

• In addition to conventional charging 

procedures, the following requirements shall 
be followed.

 

- Ensure that contamination of diff erent 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible 

to minimize the amount of refrigerant 
contained in them. 

 

- Cylinders shall be kept in an appropriate 

position according to the instructions.

 

- Ensure that the refrigerating system is 

earthed prior to charging the system with 
refrigerant. 

 

- Label the system when charging is 

complete (if not already). 

 

- Extreme care shall be taken not to over fi ll 

the refrigerating system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on 

completion of charging but prior to 
commissioning.

• A follow up leak test shall be carried out prior 

to leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant. To avoid fi re 
or explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

 

Summary of Contents for CS-MZ16ZKE

Page 1: ...ZKE CU Z50ZKE CS XZ20ZKEW H CS XZ25ZKEW H CS XZ35ZKEW H CS XZ42ZKEW H CU Z20ZKE CU Z25ZKE CU Z35ZKE CU Z42ZKE Multi Split CU 2Z35TBE CU 2Z41TBE CU 2Z50TBE CU 3Z52TBE CU 3Z68TBE CU 4Z68TBE CU 4Z80TBE C...

Page 2: ...e Split System or Multi Split System Air Conditioner to suit your needs For complete product features please refer to catalogue Inserting the batteries 1 2 3 1 Pull out the back cover of remote contro...

Page 3: ...control display 3 Press TEMP UP TEMP DOWN to select the desired temperature Up Down Selection range 16 0 C 30 0 C 60 F 86 F Press for approximately 10 seconds to show the temperature as C or F 2 Pres...

Page 4: ...cialist to clean the internal parts repair install remove disassemble and reinstall the unit Improper installation and handling will cause leakage electric shock or re Con rm with authorised dealer or...

Page 5: ...cal shock or re Prevent electric shock by switching o the power supply and unplug Before cleaning or servicing When extended non use or During abnormally strong lightning activity CAUTION Indoor unit...

Page 6: ...he working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especially when replacing a refrigerant R22 model with a new refrige...

Page 7: ...ironmental e ects such as the danger of water collecting and freezing in relief pipes or the accumulation of dirt and debris h Expansion and contraction of long runs piping in refrigerating systems sh...

Page 8: ...ignition and hot metal surfaces away 2 3 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is a...

Page 9: ...e refrigerant containing components unless the components are constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded 2 8 Checks t...

Page 10: ...nt in the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental e ects The check shall a...

Page 11: ...pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available OFN oxygen free nitrogen type of inert gas 9 Ch...

Page 12: ...ardous condition when charging or discharging the refrigerant To avoid re or explosion dissipate static electricity during transfer by grounding and bonding containers and equipment before charging di...

Page 13: ...acuated to an acceptable level to make certain that ammable refrigerant does not remain within the lubricant The evacuation process shall be carried out prior to returning the compressor to the suppli...

Page 14: ...ow the remote control setting If nanoe X is activated before the unit is turned o the nanoe X operation will resume when the unit is turned on This includes when TIMER ON is set Press the button again...

Page 15: ...time This operation provides you with a comfortable environment while sleeping It will automatically adjust the sleep pattern temperature during the activation period The indoor unit indicator will di...

Page 16: ...ion This control is not applicable when TIMER is set To Learn More Single Single split system Multi Multi split system Operation mode It is possible to operate the indoor units individually or simulta...

Page 17: ...Z50ZKE CU Z71ZKE 2 CU 2Z35TBE CU 2Z41TBE CU 2Z50TBE CU 3Z52TBE CU 3Z68TBE CU 4Z68TBE CU 4Z80TBE CU 5Z90TBE Inside Cleaning This function is to enhance the inside cleaning of the air conditioner indoo...

Page 18: ...ugh items e g ngernails tools rings etc Wipe the unit gently with a soft damp cloth The coils and fans should be cleaned periodically by an authorised dealer Outdoor unit Clean the debris that surroun...

Page 19: ...hen room temperature increase Indoor fan stops occasionally during heating operation To avoid unintended cooling e ect Indoor fan stops occasionally during automatic fan speed setting This is to help...

Page 20: ...ly Remote control does not work Display is dim or transmission signal is weak Insert the batteries correctly Replace weak batteries The unit does not work Check if the circuit breaker is tripped Check...

Page 21: ...the air inlets and outlet vents Use AUTO OFF ON on the unit to select COOL or HEAT mode For details refer The remote control is missing or a malfunction has occurred above After 15 minutes of operatio...

Page 22: ...35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mismatch brand cod...

Page 23: ...y or dealer and ask for the correct method of disposal Note for the battery symbol bottom two symbol examples This symbol might be used in combination with a chemical symbol In this case it complies w...

Page 24: ...a branch of Panasonic Marketing Europe GmbH Maxis 2 Western Road Bracknell Berkshire RG12 1RT Manufactured by Panasonic Corporation 1006 Oaza Kadoma Kadoma City Osaka 571 8501 Japan Importer Panasonic...

Reviews: