28
11.2.4. Connect the Cable to the Indoor Unit
1. The inside and outside connecting cable can be
connected without removing the front grille.
2.
Connecting cable
between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 4 x 1.5 mm
2
flexible cord, type designation 245 IEC 57 or heavier
cord.
3. Bind all the indoor and outdoor connecting cable with
tape and route the connecting cable via the escapement.
4. Remove the tapes and connect the connecting cable
between indoor unit and outdoor unit according to the
diagram below.
5. Secure the connecting cable onto the control board with
the holder (clamper).
• Ensure the colour of wires of outdoor unit and the
terminal Nos. are the same to the indoor’s respectively.
• Earth wire shall be Yellow/Green (Y/G) in colour and
longer than other AC wires for safety reason.
Summary of Contents for CS-NE9LKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit...
Page 14: ...14 5 2 Outdoor Unit...
Page 15: ...15 6 Refrigeration Cycle Diagram...
Page 16: ...16 7 Block Diagram...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit...
Page 18: ...18 8 2 Outdoor Unit...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Page 20: ...20 9 2 Outdoor Unit...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Page 22: ...22 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board...
Page 24: ...24 10 2 Outdoor Unit...
Page 80: ...80 16 1 3 To remove discharge grille...
Page 81: ...81 16 1 4 To remove control board 16 1 5 To remove cross flow fan and indoor fan motor...
Page 82: ...82...
Page 84: ...84 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU NE9LKE...
Page 85: ...85...
Page 86: ...86...
Page 87: ...87...
Page 88: ...88 17 1 2 CU NE12LKE...
Page 89: ...89...
Page 90: ...90...
Page 91: ...91...