FOR SEASONAL INSPECTION AFTER EXTENDED NON-USE

•  Checking of remote control batteries.

•  No obstruction at air inlet and air outlet vents.

•  Use Auto OFF/ON button to select Cooling operation. After 

15 minutes of operation, it is normal to have the following 

temperature difference between air inlet and air outlet vents:   

Cooling: ≥ 8°C           Heating: ≥ 14°C

NON SERVICEABLE CRITERIAS

TURN OFF POWER SUPPLY then please consult 

authorized dealer under the following conditions:

•  Abnormal noise during operation.

•  Water/foreign particles have entered the remote 

control.

•  Water leaks from Indoor unit.

•  Circuit breaker switches off frequently.

•  Power cord becomes unnaturally warm.

•  Switches or buttons are not functioning 

properly.

•  The timer indicator blinks and the unit can not 

be operated.

FOR EXTENDED NON-USE

•  Activate Heat mode for 2~3 hours as an alternative to remove 

moisture left in the internal parts thoroughly to prevent mould growth.

•  Turn off the power supply.

•  Remove the remote control batteries.

ПЕРИОДИЧЕСКАЯ (СЕЗОННАЯ) ПРОВЕРКА ПОСЛЕ 

ПРОДОЛЖИТЕЛЬНОГО ПЕРИОДА БЕЗ ЭКСПЛУАТАЦИИ

•  Проверка батареек из пульта дистанционного управления.  

•  Убедитесь в отсутствии инородных тел, блокирующих 

воздухозаборное и воздуховыпускное отверстия.

•  С помощью кнопки “АВТОМАТИЧЕСКОЕ ВКЛ/ВЫКЛ” 

(AUTO OFF/ON) выберите режим охлаждения. После 15 

минут работы следующая разница температур между 

воздухозаборным и воздуховыпускным отверстиями 

считается нормальной:

  При охлаждении: ≥ 8°C

  При обогреве: ≥ 14°C  

КРИТЕРИИ НЕРАБОТОСПОСОБНОСТИ

ВЫКЛЮЧИТЕ ПИТАНИЕ и обратитесь 

к авторизованному дилеру при наличии 

следующих проблем:

•  Ненормальный шум во время работы.  

•  Попадание воды/посторонних частиц в пульт 

дистанционного управления.

•  Течь воды из внутреннего блока.

•  Автоматический выключатель часто 

срабатывает.

•  Штепсельная вилка/сетевой шнур сильно 

нагревается.

•  Неправильно функционируют кнопки или 

переключатели.

•  Индикатор таймера мигает, и управление 

кондиционером невозможно.

ПРИ ДЛИТЕЛЬНОМ ПЕРИОДЕ БЕЗ ЭКСПЛУАТАЦИИ  

•  Включите режим нагрева на 2~3 часа для удаления 

влаги на внутренних деталях устройства, чтобы избежать 

образования плесени.

•  Выключите питание устройства.

•  Извлеките батарейки из пульта дистанционного управления.  

ОГЛЯД ПЕРЕД ПОЧАТКОМ СЕЗОНУ ПІСЛЯ ТРИВАЛОГО 

ПЕРІОДУ БЕЗ ЕКСПЛУАТАЦІЇ

•  Перевірте чи не час міняти батарейки пульта дистанційного 

управління. 

•  Перевірте чи ніщо не перекриває який-небудь із отворів для 

входу й виходу повітря.  

•  Кнопкою АВТОМАТИЧНЕ ВИМКНЕННЯ/УВІМКНЕННЯ 

(AUTO OFF/ON) виберіть режим охолодження. Якщо 

кондиціонер працює нормально, через 15 хвилин після 

початку роботи різниця температур повітря на вході та 

виході повітря внутрішнього блоку повинна становити:

  Охолодження: ≥ 8°C      Обігрів: ≥ 14°C

ВИПАДКИ, ЩО ПОТРЕБУЮТЬ 

КВАЛІФІКОВАНОГО РЕМОНТУ  

ВИМКНІТЬ ЕЛЕКТРОЖИВЛЕННЯ і зверніться 

до уповноваженого дилера в таких випадках:

•  Незвичайний шум під час роботи.

•  Усередину пульта дистанційного управління 

потрапила вода або сторонні частки.

•  Із внутрішнього блоку витікає вода.

•  Часто спрацьовує автоматичний вимикач.

•  Шнур живлення є теплішим, ніж звичайно.

•  Невірно функціонують кнопки та перемикачі.

•  Індикатор таймера мигає і прилад не працює. 

ВИВЕДЕННЯ З ЕКСПЛУАТАЦІЇ НА ТРИВАЛИЙ ПЕРІОД  

•  Увімкніть кондиціонер в режимі обігріву на 2~3 години для 

того, щоб ретельно видалити вологу із внутрішніх частин і 

запобігти розростанню плісняви. 

•  Вимкніть електроживлення.

•  Вийміть батарейки з пульта дистанційного управління. 

F567313_cover_CS4.indd   39

2009-12-28   15:16:14

Downloaded from AC-Manual.com Manuals

Summary of Contents for CS-PA7KKD

Page 1: ...8 13 KPA HCbKA 14 19 ESPA OL 20 25 Antes de utilizar la unidad s rvase leer atentamente estas instrucciones de funcionamiento y conservarlas como futuro elemento de consulta FRAN AIS 26 31 Avant d uti...

Page 2: ...c shock or fire Do not install the unit in a potentially explosive or flammable atmosphere Failure to do so could result in fire accident Do not insert your fingers or other objects into the air condi...

Page 3: ...batteries of the same type must be inserted following the polarity stated to prevent malfunction of the remote control WARNING POWER SUPPLY Do not use modified cord joint cord extension cord or unspe...

Page 4: ...emperature Operation mode Standard setting temperature 2 C 2 C 23 C above Cool 25 C 27 C 23 C Below 23 C Dry 22 C 24 C 20 C Below 20 C Heat 21 C 23 C 19 C HEAT MODE TO ENJOY WARM AIR In heat mode it m...

Page 5: ...2 Press the button to select the delay hour 3 Press the button to confirm the timer setting The ON TIMER can only be set while the air conditioner is not in operation To cancel ON or OFF timer press T...

Page 6: ...for approximately 10 seconds until you hear double beep sound 2 Repeat above step within 60 seconds and then signal receiving sound will be switched OFF ON Procedure of switching OFF ON auto restart...

Page 7: ...el the Auto Restart Control please refer to page 6 Power indicator blinks during heating operation and the indoor fan is stopped The unit is in defrost mode and the melted frost is drained from the ou...

Page 8: ...8 C DBT WBT 32 23 16 11 30 16 C DBT WBT 43 26 16 11 24 18 5 6 DBT WBT Panasonic 8 9 10 11 12 13 38 40 41 42 F567313_RU_CS4 indd 8 2009 12 28 15 19 05 Downloaded from AC Manual com Manuals...

Page 9: ...CCK 9 ELCB RCD ON Ni Cd F567313_RU_CS4 indd 9 2009 12 28 15 19 10 Downloaded from AC Manual com Manuals...

Page 10: ...4 C DRY 1 C 2 C 3 2 C 2 C 23 C 25 C 27 C 23 C 23 C 22 C 24 C 20 C 20 C 21 C 23 C 19 C POWER 3 4 5 1 2 4 3 FAN SPEED AUTO 5 5 AIR SWING COOL DRY AUTO AUTO HEAT AUT O HEA T COO L DRY FAN SPE ED AIR SWI...

Page 11: ...CCK 11 12 5 1 Delay OFF TIMER 2 3 OFF TIMER 2 1 Delay ON TIMER 2 3 ON TIMER F567313_RU_CS4 indd 11 2009 12 28 15 19 18 Downloaded from AC Manual com Manuals...

Page 12: ...12 2 5 6 7 1 4 3 8 1 2 3 4 5 6 7 1 1 AUTO OFF ON 10 2 60 1 AUTO OFF ON 15 2 60 8 pH7 40 C F567313_RU_CS4 indd 12 2009 12 28 15 19 24 Downloaded from AC Manual com Manuals...

Page 13: ...CCK 13 Auto Restart 12 F567313_RU_CS4 indd 13 2009 12 28 15 19 27 Downloaded from AC Manual com Manuals...

Page 14: ...14 C DBT WBT 32 23 16 11 30 16 C DBT WBT 43 26 16 11 24 18 5 6 DBT WBT Panasonic 14 15 16 17 18 19 38 40 41 42 F567313_UK_CS4 indd 14 2009 12 28 15 19 52 Downloaded from AC Manual com Manuals...

Page 15: ...KPA HCBKA 15 ON Ni Cd F567313_UK_CS4 indd 15 2009 12 28 15 19 56 Downloaded from AC Manual com Manuals...

Page 16: ...1 OFF 2 16 C 30 C COOL 26 C 28 C HEAT 20 C 24 C DRY 1 C 2 C 3 2 C 2 C 23 C 25 C 27 C 23 C 23 C 22 C 24 C 20 C 20 C 21 C 23 C 19 C POWER 8 3 4 5 1 2 4 3 FAN SPEED AUTO 5 5 AIR SWING COOL DRY AUTO HEAT...

Page 17: ...KPA HCBKA 17 12 5 1 Delay OFF TIMER 2 3 OFF TIMER 2 1 Delay ON TIMER 2 3 ON TIMER ON OFF F567313_UK_CS4 indd 17 2009 12 28 15 20 05 Downloaded from AC Manual com Manuals...

Page 18: ...18 1 2 3 4 5 6 7 1 AUTO OFF ON 10 2 60 1 AUTO OFF ON 15 2 60 8 2 5 6 7 1 4 3 8 pH7 40 C F567313_UK_CS4 indd 18 2009 12 28 15 20 10 Downloaded from AC Manual com Manuals...

Page 19: ...KPA HCBKA 19 Auto Restart 18 F567313_UK_CS4 indd 19 2009 12 28 15 20 14 Downloaded from AC Manual com Manuals...

Page 20: ...aire acondicionado ya que las partes rotatorias podr an provocarle lesiones No toque la unidad exterior durante un rel mpago ya que podr a causar una descarga el ctrica MANDO A DISTANCIA No permita qu...

Page 21: ...funcione bien es necesario insertar las pilas seg n la polaridad indicada DAD ADVERTENCIA FUENTE DE ENERG A No utilice un cable modificado unido con otro un cable de extensi n o un cable no especific...

Page 22: ...odo FR O 26 C 28 C Modo CALOR 20 C 24 C Modo DESHUMIDIFICACI N 1 C 2 C menos que la temperatura ambiente 3 SELECCIONAR MODO DE OPERACI N Modo AUTOM TICO Para su comodidad La unidad selecciona autom ti...

Page 23: ...el bot n para seleccionar el tiempo del temporizador 3 Pulse el bot n para confirmar la configuraci n del temporizador El TEMPORIZADOR DE ENCENDIDO ON TIMER s lo puede configurarse cuando el aire acon...

Page 24: ...ior durante 60 segundos en ese momento la alerta sonora se activar desactivar Procedimiento de ACTIVACI N DESACTIVACI N del control de reinicio autom tico 1 Mantenga pulsado el bot n APAGADO ENCENDIDO...

Page 25: ...la alimentaci n despu s de un fallo de corriente Para cancelar el Control de Reinicio Autom tico por favor refi rase a la p gina 24 El indicador de encendido parpadea durante el funcionamiento y el ve...

Page 26: ...lammable Sinon il y a un risque d incendie N ins rez jamais vos doigts ou des objets dans l unit int rieure ou ext rieure du climatiseur les parties tournantes peuvent causer des blessures Ne touchez...

Page 27: ...i doivent tre remplac es et introduisez les en respectant la polarit indiqu e afin d viter un mauvais fonctionnement de la t l commande AVERTISSEMENT AVERTISSEMENT ALIMENTATION N utilisez pas de cordo...

Page 28: ...CTIONNER UN MODE DE FONCTIONNEMENT Mode Auto Selon vos pr f rences Cet appareil s lectionne le mode de fonctionnement en fonction de la temp rature de la pi ce Une fois le mode automatique s lectionn...

Page 29: ...IMER appuyez une fois sur le bouton 2 Appuyez sur le bouton pour s lectionner l heure de mise en marche de l unit 3 Appuyez sur le bouton pour confirmer le r glage du minuteur Le MINUTEUR DE MISE EN M...

Page 30: ...Proc dure d ACTIVATION DESACTIVATION du contr le de la fonction de red marrage automatique 1 Maintenez enfonc le bouton ACTIVATION DESACTIVATION AUTOMATIQUE AUTO OFF ON pendant environ 15 secondes ju...

Page 31: ...commande de red marrage automatique veuillez vous r f rer la page 30 Le t moin d alimentation clignote lors du fonctionnement et le ventilateur de l unit int rieure s arr te L appareil est en mode de...

Page 32: ...32 33 32 35 34 36 37 40 38 42 41 DBT WBT 32 23 16 11 30 16 DBT WBT 43 26 16 11 24 18 5 6 DBT WBT F567313_AR_CS4 indd 32 2009 12 28 3 37 04 MD Downloaded from AC Manual com Manuals...

Page 33: ...33 RCD ELCB Ni Cd F567313_AR_CS4 indd 33 2009 12 28 3 37 07 MD Downloaded from AC Manual com Manuals...

Page 34: ...WI NG AUTO AUTO COOL DRY AUTO HEAT OFF 28 26 24 20 2 2 23 27 20 24 19 23 21 20 POWER 8 POWER TIMER AUTO HEAT COOL DRY FAN SPEED AIR SWING AIR SWING FAN SPEED F567313_AR_CS4 indd 34 2009 12 28 3 37 10...

Page 35: ...35 12 OFF ON 5 Delay OFF TIMER 1 2 3 OFF TIMER Delay ON TIMER 1 2 3 ON TIMER OFF ON F567313_AR_CS4 indd 35 2009 12 28 3 37 12 MD Downloaded from AC Manual com Manuals...

Page 36: ...36 ON OFF AUTO OFF ON 1 10 AUTO OFF ON 60 2 1 15 AUTO OFF ON 60 2 pH7 F567313_AR_CS4 indd 36 2009 12 28 3 37 16 MD Downloaded from AC Manual com Manuals...

Page 37: ...37 36 F567313_AR_CS4 indd 37 2009 12 28 3 37 17 MD Downloaded from AC Manual com Manuals...

Page 38: ...s Union Europ enne veuillez vous renseigner aupr s des autorit s locales comp tentes ou de votre distributeur Note relative au pictogramme apposer sur les piles voir les 2 exemples ci contre Le pictog...

Page 39: ...Abnormal noise during operation Water foreign particles have entered the remote control Water leaks from Indoor unit Circuit breaker switches off frequently Power cord becomes unnaturally warm Switch...

Page 40: ...ation Retirez les piles de la t l commande PARA INSPECCI N ESTACIONAL DESPU S DE UN LARGO PER ODO EN DESUSO Verifique las pilas del mando a distancia Compruebe que las tomas de entrada y salida de las...

Page 41: ...onditions 1m Distance Max cooling 47 48 47 47 48 49 Air Circulation m3 min 10 8 11 0 10 8 11 0 Product Weight kg 9 0 9 0 22 25 Dimensions H W D mm 848 204 290 848 204 290 650 230 530 650 230 530 PRODU...

Page 42: ...39 39 42 42 40 40 Conditions 1m Distance Max cooling 49 49 50 50 50 50 52 52 Air Circulation m3 min 11 8 12 0 12 2 12 4 Product Weight kg 9 0 9 0 34 40 Dimensions H W D mm 848 204 290 848 204 290 780...

Page 43: ...k 43 F567313_cover_CS4 indd 43 2009 12 28 15 16 30 Downloaded from AC Manual com Manuals...

Page 44: ...tionnez la temp rature souhait e 3 AUTO HEAT COOL DRY FAN SPEED AIR SWING 3 2 1 QUICK GUIDE GU A R PIDA GUIDE RAPIDE Remote Control Preparation Preparaci n Del Mando a Distancia Pr paration De La T l...

Reviews: