13 Protection Control
13.1. Freeze Prevention Control
• After compressor starts operation for 4 minutes, the outdoor unit will stop its operation if indoor pipe temperature falls below 2ºC
for 6 minutes.
• After 3 minutes stops, compressor restarts operation if indoor pipe temperature is 3ºC or more.
• This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid from
returning to the compressor.
13.2. Dew Form Prevention Control
• During Cooling Operation, dew form prevention control activates if:
• Indoor temperature falls between 24ºC and 30ºC.
• Compressor and thermostat is ON.
• Indoor fan speed is Low speed.
• Setting temperature is less than 25ºC.
• During dew form prevention control, the louver is fixed at 30º.
• Fan speed and angle of horizontal louver (vertical airflow angle) will be adjusted accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
- The angle of horizontal louver will be changed as below figure.
Note:
A = Normal operation angle of rotation
B = Dew prevention angle of rotation
Horizontal Louver Angle
During dew prevention, the horizontal louver angle in Auto-control are as below figure.
During dew prevention, the horizontal louver angle in Manual are as below figure.
• Dew prevention control will be cancel when:
- Any one of the condition above does not comply.
Operation Mode
Airflow direction auto-control
Airflow direction manual control
Cooling, Soft Dry
A
3
°
~ 27
°
3
°
, 11
°
, 19
°
, 27
°
B
11
°
~ 19
°
11
°
, 14
°
, 17
°
, 19
°
Summary of Contents for CS-PC36HKV
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS PC36HKV...
Page 10: ...10 5 2 Outdoor Unit 5 2 1 CU PC36HKV...
Page 11: ...11 6 Refrigeration Cycle Diagram...
Page 12: ...12 7 Block Diagram...
Page 13: ...13 8 Wiring Connection Diagram...
Page 14: ...14 9 Electronic Circuit Diagram 9 1 CS PC36HKV...
Page 15: ...15 9 2 CU PC36HKV...
Page 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit...
Page 17: ...17 10 2 Outdoor Unit...
Page 18: ...18 10 3 Indicator...
Page 22: ...22 This can be used for left rear piping and left bottom piping also...
Page 45: ...45 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry...
Page 46: ...46 17 2 Operation Characteristics 17 2 1 CS PC36HKV CU PC36HKV...
Page 47: ...47...
Page 50: ...50 18 2 Outdoor Unit 18 2 1 CU PC36HKV...
Page 51: ...51...