background image

16 

6. Refrigeration Cycle Diagram 

 

INDOOR

OUTDOOR

INTAKE

AIR

TEMP.

SENSOR

PIPE

TEMP.

SENSOR 2

COMPRESSOR

TEMP.

SENSOR

PIPE

TEMP.

SENSOR 1

PIPE

TEMP.

SENSOR

OUTDOOR

AIR TEMP.

SENSOR

LIQUID

SIDE

2-WAY
VALVE

3-WAY
VALVE

GAS

SIDE

COOLING

HEAT EXCHANGER

(EVAPORATOR)

HEATING

COMPRESSOR

4-WAYS VALVE

CONDENSER

MUFFLER

MUFFLER

STRAINER

EXPANSION

VALVE

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for CS-RE9QKE

Page 1: ...WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical...

Page 2: ...art Control 42 12 8 Indication Panel 42 13 Protection Control 43 13 1 Protection Control For All Operations 43 13 2 Protection Control For Cooling Soft Dry Operation 45 13 3 Protection Control For Hea...

Page 3: ...Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdown 10 Do not use joint cable for indoor outdoor connection cable Use the specified Indoor Outdoor con...

Page 4: ...g point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20 F 370 10 C Pb free solder will tend to sp...

Page 5: ...42 30 22 Indoor Noise Power Level dB 57 58 dB A 47 48 Cooling Outdoor Noise Power Level dB 62 63 kW 0 80 3 30 4 10 0 80 4 00 5 10 BTU h 2730 11300 14000 2730 13600 17400 Capacity kcal h 690 2840 3530...

Page 6: ...moval L h Pt h 1 5 3 2 2 0 4 2 Cool m 3 min ft 3 min 5 74 203 5 69 201 QLo Heat m 3 min ft 3 min 7 03 248 6 79 240 Cool m 3 min ft 3 min 6 68 236 7 59 268 Lo Heat m 3 min ft 3 min 7 62 269 8 85 312 Co...

Page 7: ...tion Range Heating Minimum C 15 16 15 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry B...

Page 8: ...1 29 Indoor Noise Power Level dB 60 dB A 49 Cooling Outdoor Noise Power Level dB 64 kW 0 80 5 00 6 80 BTU h 2730 17100 23200 Capacity kcal h 690 4300 5850 Running Current A 6 00 Input Power W 200 1 35...

Page 9: ...910 Moisture Removal L h Pt h 2 4 5 1 Cool m 3 min ft 3 min 6 94 245 QLo Heat m 3 min ft 3 min 8 17 288 Cool m 3 min ft 3 min 7 81 276 Lo Heat m 3 min ft 3 min 10 03 354 Cool m 3 min ft 3 min 10 16 35...

Page 10: ...Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 F Dry Bulb and outdoor air te...

Page 11: ...on substances refrigerant R410A Long Installation Piping o CS CU RE9 12 15QKE long piping up to 15 meters Easy to use remote control Quality Improvement o Random auto restart after power failure for s...

Page 12: ...direction louver Do not adjust by hand Horizontal Airflow direction louver Manually adjust INDICATOR POWER Green TIMER Orange 4 2 Outdoor Unit 4 3 Remote Control MODE TEMP OFF ON TIMER SET CANCEL ON O...

Page 13: ...Control Remote Control Holder 22 47 134 61 51 870 1 2 1 2 214 61 45 Right piping hole 290 214 125 115 60 60 410 41 61 Gas side Liquid side Relative position between the indoor unit and the installati...

Page 14: ...e View Side View Anchor Bolt Pitch 330 540 Space necessary for installation 100 mm 100 mm 1000 mm Unit mm 3 way valve at Gas side Low Pressure 2 way valve at Liquid side High Pressure 69 6 18 61 6 542...

Page 15: ...w Side View Side View Anchor Bolt Pitch 330 540 Space necessary for installation 100mm 100mm 1000mm Unit mm 3 way valve at Gas side Low Pressure 2 way valve at Liquid side High Pressure 22 124 62 6 33...

Page 16: ...SOR PIPE TEMP SENSOR 2 COMPRESSOR TEMP SENSOR PIPE TEMP SENSOR 1 PIPE TEMP SENSOR OUTDOOR AIR TEMP SENSOR LIQUID SIDE 2 WAY VALVE 3 WAY VALVE GAS SIDE COOLING HEAT EXCHANGER EVAPORATOR HEATING COMPRES...

Page 17: ...FUSE101 FUSE104 REACTOR FUSE102 RY PWR PTC1 PTC NTC TH3 CT102 4 WAYS VALVE RY AC FUSE103 IC19 MS 3 MS 3 RY PWR RY PWR2 FUSE301 TEMP FUSE TEMP FUSE SC L U M INDOOR UNIT OUTDOOR UNIT SC 2 3 N SINGLE PH...

Page 18: ...1 FUSE101 FUSE104 REACTOR FUSE102 RY PWR PTC1 PTC NTC TH3 CT102 4 WAYS VALVE RY AC FUSE103 P N IC20 Q1 MS 3 MS 3 RY PWR RY PWR2 FUSE301 TEMP FUSE TEMP FUSE SC L U M INDOOR UNIT OUTDOOR UNIT SC 2 3 N S...

Page 19: ...PLY 1 230V 50Hz ELECTRONIC CONTROLLER MAIN UP DOWN LOUVER MOTOR CN STM1 WHT BR 1 5 1 5 R O M Y P REMARKS B BLUE P PINK BR BROWN O ORANGE BL BLACK Y YELLOW W WHITE G GREEN R RED Y G YELLOW GREEN CN DIS...

Page 20: ...YS VALVE 1 3 CN HOT WHT CN TH WHT P N SWITCHING POWER SUPPLY CIRCUIT FUSE102 T3 15A L250V FUSE101 20A 250V 3 2 1 COMMUNICATION CIRCUIT PFC CIRCUIT W U V FAN MOTOR ELECTRONIC CONTROLLER MS 3 FUSE104 15...

Page 21: ...E 1 3 CN HOT WHT CN TH WHT P N SWITCHING POWER SUPPLY CIRCUIT FUSE102 T3 15A L250V FUSE101 20A 250V 3 2 1 COMMUNICATION CIRCUIT PFC CIRCUIT W U V FAN MOTOR ELECTRONIC CONTROLLER MS 3 FUSE104 15A 250V...

Page 22: ...e Temp Sensor Intake Air Temp Sensor 1 1 2 2 CN DISP YELLOW UP DOWN LOUVER MOTOR CN STM1 WHITE 1 5 4 3 2 12V 74 144 70 64 61 M 12V 1 2 3 4 5 6 7 16 9 8 15 14 13 12 11 10 IC03 R47 1 2W 68 5 143 R46 1 2...

Page 23: ...N SWITCHING POWER SUPPLY CIRCUIT FUSE102 T3 15A L250V FUSE101 20A 250V 3 RED 2 WHITE S1 BLACK COMMUNICATION CIRCUIT PFC CIRCUIT W U V ELECTRONIC CONTROLLER MS 3 FUSE104 15A 250V NOISE FILTER CIRCUIT...

Page 24: ...WER SUPPLY CIRCUIT FUSE102 T3 15A L250V FUSE101 20A 250V 3 RED 2 WHITE S1 BLACK COMMUNICATION CIRCUIT PFC CIRCUIT W U V ELECTRONIC CONTROLLER MS 3 FUSE104 15A 250V NOISE FILTER CIRCUIT RECTIFICATION C...

Page 25: ...25 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board CN FM CN STM1 CN TH CN DISP CN RMT RY PWR AC303 G301 AC304 RY PWR2 JP1 Random Auto Restart enable disable...

Page 26: ...26 10 1 2 Indicator Receiver Printed Circuit Board CN DISP...

Page 27: ...27 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU RE9QKE CN HOT CN STM CN TH CN MTR1 CN MTR2 CN TANK AC BLK DATA AC WHT POWER TRANSISTOR IPM CURRENT TRANSFORMER CT...

Page 28: ...28 10 2 1 2 CU RE12QKE CU RE15QKE CN HOT CN MTR1 CN MTR2 CN TH CN STM CN TANK AC BLK DATA AC WHT POWER TRANSISTOR IPM CURRENT TRANSFORMER CT...

Page 29: ...1 4 5 7 5 20 15 3 15 7 5 20 15 3 15 7 5 20 15 3 15 7 5 20 15 3 15 10 30 30 3 20 P H 5 1 2 1 E Y 2 1 E U 2 1 E R RE15 1 75HP 12 7mm 1 2 UE18 2 0HP 7 5 20 20 3 15 8 1 E R RE24 2 5HP 15 88mm 5 8 Example...

Page 30: ...ith 5 screws or more at least 5 screws If mounting the unit on the concrete wall consider using anchor bolts o Always mount the installation plate horizontally by aligning the marking off line with th...

Page 31: ...necting the piping column in outdoor unit section Below steps are done after connecting the outdoor piping and gas leakage confirmation Step 7 Insulate and finish the piping Step 8 Secure the Indoor U...

Page 32: ...Isolating Devices Disconnecting means o Connect approved type polychloroprene sheathed power supply cord 3 1 5 mm2 1 0 1 75HP 3 2 5 mm2 2 0 2 5HP type designation 60245 IEC 57 or heavier cord to the t...

Page 33: ...ew and close the front panel Recommended length mm Tape Connection cable Tape Power supply cord Recommended length mm a 55 b 35 c 35 d 50 e 40 f 35 g 60 Terminal Board Control Board Earth wire longer...

Page 34: ...NG REQUIREMENT Conductor fully inserted Conductor not fully inserted gap between wires WARNING RISK OF FIRE JOINING OF WIRES MAY CAUSE OVERHEATING AND FIRE Do not joint wires OR OR OR Use complete wir...

Page 35: ...at joint portion of tube assembly onto the copper pipe In case of using long piping Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten t...

Page 36: ...e that the needle in the gauge does not move after approximately five minutes Note BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE 5 Disconnect the charging hose from the vacu...

Page 37: ...ly earthed Earth wire shall be Yellow Green Y G in colour and longer than other AC wires for safety reason 11 3 5 Piping Insulation 1 Please carry out insulation at pipe connection portion as mentione...

Page 38: ...ting temperature and it is updated continuously whenever the electrical power is supplied to the unit 12 1 2 Cooling Operation 12 1 2 1 Thermostat control Compressor is OFF when Intake Air Temperature...

Page 39: ...3 C if previous operate in DRY mode then continue in DRY mode otherwise COOL mode is decided o If 2 C indoor intake temperature remote control setting temperature 3 C maintain with previous mode o If...

Page 40: ...then H19 fan motor error is detected Operation stops and cannot on back 12 3 Outdoor Fan Motor Operation Outdoor fan motor is operated with one fan speed only It starts when compressor starts operatio...

Page 41: ...e For heating mode operation the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below It does not swing during fan motor stop When the air conditioner is stopped using...

Page 42: ...be selected randomly after power supply resumes This type of control is not applicable during ON OFF Timer setting This control can be omitted by open the circuit of JP1 at indoor unit printed circui...

Page 43: ...oft Dry A 4 41 6 07 7 94 Cooling Soft Dry B 3 94 5 52 7 42 Cooling Soft Dry C 3 94 5 52 7 42 Heating 4 65 15 02 6 00 15 02 9 13 15 02 4 The first 30 minutes of cooling operation A will be applied 13 1...

Page 44: ...nd Soft Dry operations Indoor suction temperature indoor piping temperature is below 4 C o During Heating operations Indoor piping temperature indoor suction is under 5 C Control contents o Compressor...

Page 45: ...anger is higher than 5 C At the same time indoor fan speed will be higher than during its normal operation If indoor heat exchanger temperature is higher than 5 C for 5 minutes the fan speed will retu...

Page 46: ...13 3 2 Outdoor Air Temperature Control The Max current value is regulated when the outdoor air temperature rise above 14 C in order to avoid compressor overloading 13 3 3 Overload Protection Control T...

Page 47: ...NTROL NUMBER SWITCH MODE The Remote Control Number Switch Mode will be activated if the Auto OFF ON button is pressed continuously for more than 11 seconds 3 beep sounds will occur at 11th seconds to...

Page 48: ...ote Control Receiving Sound OFF ON Mode is restarted 14 2 Remote Control Button 14 2 1 SET Button To check remote control transmission code and store the transmission code to EEPROM o Press Set button...

Page 49: ...problems before inspecting the refrigeration cycle Such problems include insufficient insulation problem with the power source malfunction of a compressor and a fan The normal outlet air temperature a...

Page 50: ...lectric current during operation Low Pressure High Pressure Electric current during operation Insufficient refrigerant gas leakage Clogged capillary tube or Strainer Short circuit in the indoor unit H...

Page 51: ...ly for 5 seconds 3 will be displayed on the remote controller display Note Display only for No transmitting signal no receiving sound and no Power LED blinking 4 Press the TIMER or button on the remot...

Page 52: ...lity Port is ON for 10s during ion device off ion device PCB H27 Outdoor air temperature sensor abnormality Continuous for 5s Outdoor air temperature sensor open or short circuit Outdoor air temperatu...

Page 53: ...ing abnormality 3 times happen within 40 minutes Wrong wiring and connecting pipe expansion valve leakage indoor heat exchanger sensor open circuit Check indoor outdoor connection wire and pipe Indoor...

Page 54: ...ved from outdoor unit in indoor unit signal transmission is checked whether it is normal Malfunction Caused Faulty indoor unit PCB Faulty outdoor unit PCB Indoor unit outdoor unit signal transmission...

Page 55: ...re interconnected Malfunction Caused Wrong models interconnected Wrong indoor unit or outdoor unit PCBs mounted Indoor unit or outdoor unit PCBs defective Indoor outdoor unit signal transmission error...

Page 56: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Cause...

Page 57: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors Malfunction Caused F...

Page 58: ...on Conditions An input current detected by Current Transformer CT is below threshold value when the compressor is operating at certain frequency value for 3 minutes Malfunction Caused Lack of gas Brok...

Page 59: ...termine abnormal fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the...

Page 60: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused...

Page 61: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors Malfunction Caused Faul...

Page 62: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Fau...

Page 63: ...ion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors Malfunction C...

Page 64: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors Malfunction...

Page 65: ...lfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused Wrong models interconnected Wrong indoor unit and outdoor unit PCBs...

Page 66: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor heat sink temperature sensor are used to determine sensor errors Malfunction Cause...

Page 67: ...ecision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors Malfunction Caused Fault...

Page 68: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors Malfunction Cau...

Page 69: ...pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation Phenomena unit is stopping and re starting very often in heating mod...

Page 70: ...ecision Conditions Freeze prevention control takes place when indoor pipe temperature is lower than 2 C Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit he...

Page 71: ...old during heating except deice or when indoor heat exchanger is hot during cooling and compressor operating the 4 way valve is detected as malfunction Malfunction Caused Indoor heat exchanger pipe th...

Page 72: ...ature and indoor pipe temperature is above 10 C or indoor pipe temperature is below 1 0 C Remark When the indoor standby unit is freezing the outdoor unit transfers F17 error code to the corresponding...

Page 73: ...tartup and operation of cooling and heating when Power Factor Correction PFC protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors When DC voltage de...

Page 74: ...igeration Cycle Abnormality Malfunction Decision Conditions The input current is low while the compressor is running at higher than the setting frequency Malfunction Caused Lack of gas 3 way valve clo...

Page 75: ...lfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused Compressor terminal disco...

Page 76: ...the outdoor unit heat exchanger thermistor Malfunction Caused Outdoor heat exchanger temperature rise due to short circuit of hot discharge air flow Outdoor heat exchanger temperature rise due to defe...

Page 77: ...ated o Heat Sink Overheating During operation of cooling and heating when heat sink temperature data 90 C is detected by the heat sink temperature sensor Malfunction Caused IPM overheats due to short...

Page 78: ...n of cooling and heating when compressor tank temperature data 103 C is detected by the compressor tank temperature sensor Malfunction Caused Refrigerant shortage refrigerant leakage 2 3 way valve clo...

Page 79: ...urrent Control is detected by checking the input current value being detected by current transformer CT with the compressor running Malfunction Caused Over current due to compressor failure Over curre...

Page 80: ...t peak due to short circuit Troubleshooting Checking the power transistor Never touch any live parts for at least 10 minutes after turning off the circuit breaker If unavoidable necessary to touch a l...

Page 81: ...or Ensure that the capacitor has discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 16 1 Indoor Electronic Controllers Cross Flow Fan...

Page 82: ...M CN STM1 CN TH CN DISP CN RMT RY PWR AC303 G301 AC304 RY PWR2 Figure 3 Figure 4 16 1 4 To remove discharge grille 10 Pull out to remove the drain hose from the discharge grille 11 Then pull the disch...

Page 83: ...oard then pull out the control board Figure 6 16 1 6 To remove cross flow fan and indoor fan motor 13 Remove the screw that holding the cross flow fan and fan motor axis Figure 7 15 Remove the bearing...

Page 84: ...fan Reminder To reinstall the fan motor adjust the fan motor connector to 45 towards you before fixing control board 17 Remove the cross flow fan from the unit by pulling it to the left and downward E...

Page 85: ...controller be careful of electrostatic discharge 1 Remove the 3 screws of the Top Panel Fig 1 2 Remove the 6 screws of the Front Panel Fig 2 3 Remove the screw of the Terminal Board Cover 4 Remove th...

Page 86: ...l of electrostatic discharge 1 Remove the 5 screws of the Top Panel Fig 1 2 Remove the 8 screws of the Front Panel Fig 2 3 Remove the screw of the Terminal Board Cover 4 Remove the Top Cover of the Co...

Page 87: ...0 2948 1000 27 22 0 3691 2223 582 3536 2123 657 3802 2222 570 3538 2123 638 4397 2478 667 4047 2339 827 3669 1750 1013 15 7 2901 2619 656 2926 2657 657 2869 2601 656 3005 2772 580 3558 3064 660 3248 2...

Page 88: ...KE CU RE12QKE Indoor C Outdoor WB C 15 7 2 7 12 DB TC IP TC IP TC IP TC IP TC IP 24 2379 1099 3290 1434 3647 1314 3702 1110 4074 1183 20 2449 1059 3300 1380 3700 1260 4000 1050 4237 1135 16 2287 1012...

Page 89: ...ed cooling at 16 C Hi fan Compressor frequency Rated for cooling operation Piping length 5m Voltage 230V 18 1 1 CS CU RE9QKE Outlet Air C Outlet Air C Outdoor Air Temperature C Low Pressure MPa Outdoo...

Page 90: ...re MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 2 00 2 40 2 80 3 20 3 60 4 00 4 40 4 80 5 20 12 16 20 24 28 32 36 40 44 48 0 60 0 70 0 80 0 90 1 00 1 10 1 20 1 30 12 16 20 24 28 3...

Page 91: ...ure MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 1 50 2 50 3 50 4 50 5 50 6 50 7 50 12 16 20 24 28 32 36 40 44 48 0 60 0 70 0 80 0 90 1 00 1 10 12 16 20 24 28 32 36 40 44 48 12 00...

Page 92: ...ompressor frequency Rated for Heating operation Piping length 5m Voltage 230V 18 2 1 CS CU RE9QKE Outlet Air C Outlet Air C Outdoor Air Temperature C High Pressure MPa Outdoor Air Temperature C Curren...

Page 93: ...igh Pressure MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 20 24 28 32 36 40 44 20 15 10 5 0 5 10 15 2 70 2 90 3 10 3 30 3 50 3 70 3 90 4 10 4 30 4 50 4 70 4 90 5 10 20 15 10 5 0 5...

Page 94: ...Temperature C High Pressure MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 4 00 4 50 5 00 5 50 6 00 6 50 7 00 20 15 10 5 0 5 10 15 1 80 2 00 2 20 2 40 2 60 2 80 3 00 3 20 3 40 3 60...

Page 95: ...CU RE12QKE CS CU RE15QKE 0 92 0 94 0 96 0 98 1 00 1 02 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Cooling Capacity Correction Factor Heating Capacity Correction Factor Pipe Length m 0 90 0 92 0 94 0 96 0 9...

Page 96: ...36 33 45 62 57 58 59 60 61 I I I I I I I I I I O I 46 47 48 54 55 56 40 3 4 2 5 1 27 23 11 16 26 34 28 29 30 39 9 37 35 7 38 8 41 42 43 50 53 52 51 44 10 49 Note The above exploded view is for the pur...

Page 97: ...28 FULCRUM 1 CWH621131 29 VERTICAL VANE 8 CWE241374 30 CONNECTING BAR 2 CWE261251 33 AIR SWING MOTOR 1 CWA981264 O 34 CAP DRAIN TRAY 1 CWH521259 35 HORIZONTAL VANE COMPLETE 1 CWE24C1385 36 REMOTE CON...

Page 98: ...K 59 INSTALLATION INSTRUCTION 1 CWF616278 60 INSTALLATION INSTRUCTION 1 CWF616279 61 INSTALLATION INSTRUCTION 1 CWF616280 62 OPERATING INSTRUCTION 1 CWF569460 NOTE All parts are supplied from PAPAMY M...

Page 99: ...30 17 16 10 11 4 12 22 21 19 26 25 38 39 9 2 1 23A 43 42 23B 31 35 33 20 14 24 29 47 55 53 54 51 52 50 23C 41 13 8 Note The above exploded view is for the purpose of parts disassembly and replacement...

Page 100: ...ND PROOF BOARD 1 CWH151172 23A SOUND PROOF MATERIAL 1 CWG302315 23B SOUND PROOF MATERIAL 1 CWG302316 23C SOUND PROOF MATERIAL 1 CWG302317 24 SENSOR CO COMP TEMP 1 CWA50C2205 O 25 CONTROL BOARD COVER T...

Page 101: ...RT NAME DESCRIPTION QTY CU RE9QKE REMARK 54 SHOCK ABSORBER LEFT 1 CWG712970 55 C C CASE 1 CWG568357 NOTE All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended...

Page 102: ...39 21 20 9 31 11 10 15 1 16 17 4 23A 23B 23C 22 2 3 8 7 5 30 12 24 29 41 13 6 47 46 48 49 50 25 14 43 42 45 Note The above exploded view is for the purpose of parts disassembly and replacement The no...

Page 103: ...CWH7080300J 22 SOUND PROOF BOARD 1 CWH151274 23A SOUND PROOF MATERIAL 1 CWG302317 23B SOUND PROOF MATERIAL 1 CWG302701 23C SOUND PROOF MATERIAL 1 CWG302726 24 SENSOR CO COMP TEMP 1 CWA50C2894 o 25 CON...

Page 104: ...CU RE12QKE CU RE15QKE REMARK 49 SHOCK ABSORBER LEFT 1 CWG713416 50 C C CASE 1 CWG566848 NOTE All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept...

Reviews: