13 Protection Control
13.1. Protection Control For All Operations
13.1.1.
Time Delay Safety Control
1. The compressor will not start for 3 minutes after stop of the operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
13.1.2.
30 Seconds Forced Operation
1. Once compressor starts the operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped with the remote control or the Auto Switch on the indoor unit.
13.1.3.
Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
13.1.4.
IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 110
q
C, compressor operation will stop immediately.
2. Compressor operation restarts after 3 minutes the temperature decreases to 95
q
C.
B. DC Peak Current Control
1.When electric current to IPM exceeds set value of 20.2 A, the compressor will stop operate. Then, operation will restart after
3 minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two
minutes.
3. If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute. If
this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
Model
TE15HK
Operation Mode
X (A)
Y (A)
Cooling/Soft Dry (A)
8.37
15.88
Cooling/Soft Dry (B)
7.87
15.88
Cooling/Soft Dry (C)
8.37
15.88
Heating
8.89
15.88
Summary of Contents for CS-TE15HKE
Page 8: ...8 5 Dimensions 5 1 Indoor Unit...
Page 9: ...9 5 2 Outdoor Unit...
Page 10: ...10 6 Refrigeration Cycle Diagram...
Page 11: ...11 7 Block Diagram...
Page 12: ...12 8 Wiring Connection Diagram 8 1 Indoor Unit...
Page 13: ...13 8 2 Outdoor Unit...
Page 14: ...14 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Page 15: ...15 9 2 Outdoor Unit...
Page 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Printed Circuit Board...
Page 17: ...17 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board...
Page 20: ...20 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Page 43: ...43 16 1 2 Removal of Electronic Controller...
Page 44: ...44 16 1 3 Removal of Control Board...
Page 45: ...45 16 1 4 Removal of Fan Motor and Cross Flow Fan...
Page 46: ...46...
Page 48: ...48 17 Technical Data 17 1 Operation Characteristics...
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...