<Brazing Method for Preventing Oxidation>
1. Attach a reducing valve to the nitrogen gas cylinder.
2. Attach a reducing valve to the nitrogen gas cylinder.
3. Apply a seal onto the clearance between the piping and inserted pipe for the nitrogen gas in order to prevent the nitrogen gas
from flowing backward.
4. When the nitrogen gas is flowing, be sure to keep the piping end open.
5. Adjust the flow rate of nitrogen gas so that it is lower than 0.05 m
3
/h, or 0.02 MPa (0.2 kgf/cm
2
) by means of the reducing valve.
6. After taking the steps above, keep the nitrogen gas flowing until the piping cools down to a certain extent (i.e. temperature at
which pipes are touchable with finger).
7. Completely remove the flux after brazing.
Cautions during brazing
1. General Cautions
a. The brazing strength should be high as required.
b. After operation, airtightness should be kept under pressurized condition.
c.
During brazing do not allow component materials to become damaged due to overheating.
d. The refrigerant pipe work should not become blocked with scale or flux.
e. The brazed part should not restrict the flow in the refrigerant circuit.
f.
No corrosion should occur from the brazed part.
2. Preventing of Overheating
Due to heating, the interior and exterior surfaces of treated metal may oxidize. Especially, when the interior of the refrigerant
circuit oxidizes due to overheating, scale occurs and stays in the circuit as dust, thus exerting a fatally adverse effect. So,
make brazing at adequate brazing temperature and with minimum of heating area.
3. Overheating Protection
In order to prevent components near the brazed part from overheating damaged or quality deterioration due to flame or heat,
take adequate steps for protection such as (1) by shielding with a metal plate, (2) by using a wet cloth, and (3) by means
of heat absorbent.
4. Movement during Brazing
Eliminate all vibration during brazing to protect brazed joints from cracking and breakage.
5. Oxidation Preventative
In order to improve the brazing efficiency, various types of antioxidant are available on the market. However, the
constituents of these are widely varied, and some are anticipated to corrode the piping materials, or adversely affect HFC
refrigerant, lubricating oil, etc. Exercise care when using an oxidation preventive.
10.4.7. Servicing Tips
The drier must also be replaced whenever replacing the refrigerant cycle parts. Replacing the refrigerant cycle parts first
before replacing the drier. The drier is supplied in a vacuum pack. Perform brazing immediately after opening the vacuum
pack, and then start the vacuum within two hours. In addition, the drier also needs to be replaced when the refrigerant has
leaked completely.
70
CS-VA75KE CU-VA75KE / CS-VA95KE CU-VA95KE / CS-VA125KE CU-VA125KE
Summary of Contents for CS-VA75KE
Page 12: ...4 Dimensions 12 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 13: ...13 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 14: ...5 Refrigeration Cycle Diagram 14 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 15: ...15 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 16: ...6 Block Diagram 16 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 92: ...15 Technical Data 92 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 94: ...94 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 95: ...95 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 96: ...96 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 107: ...107 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 109: ...23 1 REMOTE CONTROL 109 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE...
Page 112: ...112 CS VA75KE CU VA75KE CS VA95KE CU VA95KE CS VA125KE CU VA125KE MACC Printed in Malaysia...