background image

    

·

    

Press the TEST RUN button on the indoor unit, and allow preliminary operation for 5-6 minutes. (TEST RUN mode)

    

·

    

After stopping the operation, let the unit sit for about 3 minutes, then close the 2-way valve by turning the valve stem in
the clockwise direction.

    

·

    

Press the TEST RUN button on the indoor unit again, and after 2-3 minutes of operation, turn the valve stem of the 3-
way valve quickly in the clockwise direction to close it, then stop the operation.

    

·

    

Tighten the caps of the 2-way valve and 3-way valve to the stipulated torque.

    

·

    

Remove the connection pipes (liquid side and gas side).

 b. Removing the indoor and outdoor units

    

·

    

Disconnect the pipes and connecting electric cables from between the indoor and outdoor units

    

·

    

Put capped flare nuts onto all of the pipe connections of the indoor and outdoor units, to make sure no dust or other
foreign matter enters.

    

·

    

Remove the indoor and outdoor units.

 2. Installing the unit

Install the unit using new refrigerant piping. Follow the instructions in section 4.1 to evacuate the pipes connecting the indoor
and outdoor units, and the pipes of the indoor unit, and check for gas leaks.

9.4.3. AC Units Replacement (Using Existing Refrigerant Piping)

When replacing and R410A AC unit with another R410A AC unit, you should re-flare the refrigerant piping. Even though the
replacement AC unit uses the R410A, problems occur when, for example, either the AC unit maker or the refrigerating machine oil
is different.

When replacing an R22 AC unit with an R410A AC unit, the following checks and cleaning procedures are necessary but are
difficult to do because of the chemical characteristics of the refrigerating machine oil (as described in items c) and d) of section
About R410A Refrigerant(2)). In this case, you should use new refrigerant piping rather than the existing piping.

 1. Piping check

Because of the different pressure characteristics of R22 and R410A, the design pressure for the equipment is 1.6 times
different. The wall thickness of the piping must comply with that shown in Table 10, but this is not easy to check. Also, even if
the thickness is correct, there may be flattened or bent portions midway through the piping due to sharp curves. Buried sections
of the piping also cannot be checked.

 2. Pipe cleaning

A large quantity of refrigerating machine oil (mineral oil) adheres to existing pipes due to the refrigeration cycle circulation. If the
pipes are used just as they are for the R410A cycle, the capacity will be lowered due to the incompatibility of this oil with the
R410A, or irregularities may occur in the refrigeration cycle. For this reason, the piping must be thoroughly cleaned, but this is
difficult with the present technology.

9.4.4. Refrigerant Compatibility (Using R410A Refrigerant in R22 ACs and Vice Versa)

Do not operate an existing R22 AC with the new R410A refrigerant. Doing so would result in improper functioning of the equipment
or malfunction, and might lead to a major accident such as an explosion in the refrigeration cycle. Similarly, do not operate an
R410A AC with R22 refrigerant. The chemical reaction between the refrigerating machine oil used in R410A ACs and the chlorine
that is contained in R22 would cause the refrigerating machine oil to degrade and lead to malfunction.

9.4.5. Recharging Refrigerant During Servicing

When recharging is necessary, insert the specified amount of new refrigerant in accordance with the following procedure.

 1. Connect the charging hose to the service port of the outdoor unit.

 2. Connect the charging hose to the vacuum pump adaptor. At this time, fully open the 2-way valve and 3-way valve.

 3. Fully open the handle Lo of the manifold gauge, turn on the power of the vacuum pump and continue the vacuum process for

at least one hour.

 4. Confirm that the low pressure gauge shows a reading of -0.1 Mpa (-76 cmHg), then fully close the handle Lo, and turn off the

vacuum pump. Wait for 1-2 minutes, then check to make sure that the needle of the Low pressure gauge has not returned. See
Fig.13 for the remaining steps of this procedure.

 5. Set the refrigerant cylinder onto the electronic scale, then connect the hose to the cylinder and to the connection port for the

electronic scale. (1)(2)

Precaution:

Be sure to set up the cylinder for liquid charging. If you use a cylinder equipped with a siphon tube, you can charge the liquid
without having to turn the cylinder around

 6. Remove the charging hose of the manifold gauge from the vacuum pump adaptor, and connect it to the connection port of the

electronic scale. (2)(3)

32

CS-VC70KE / CU-VC70KE / CS-VC90KE / CU-VC90KE / CS-VC120KE / CU-VC120KE

Summary of Contents for CS-VC70KE

Page 1: ...Electric Industrial Co Ltd All rights reserved Unauthorized copying and distribution is a violation of law CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE Room Air Conditioners Order num...

Page 2: ...IT INSTALLATION DIAGRAM 36 11 2 Way 3 Way Valves 37 11 1 EVACUATION OF INSTALLATION 38 11 2 PUMPING DOWN 39 11 3 EVACUATION OF RE INSTALLATION 40 11 4 BALANCE REFRIGERANT OF THE 2 WAY 3 WAY VALVE 41 1...

Page 3: ...Deodorizing Air Purifying Filter Air Purifying Filter features a deodorizing function that removes unpleasant odors from the air Installation Work Improvement Long piping up to 10 m CS VC70KE CS VC90K...

Page 4: ...2 Functions 2 1 REMOTE CONTROL 4 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 5: ...2 2 INDOOR UNIT 5 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 6: ...2 3 OUTDOOR UNIT 6 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 7: ...Depth inch mm 6 29 32 175 9 21 32 245 Net Weight lb kg 18 8 0 57 26 0 Compressor Type Rotary 1 cylinder rolling piston type Motor Type Induction 2 poles Rated Output W 550 Air Circularizing Type Cros...

Page 8: ...pressor Capacitor F VAC 15 F 400VAC Fan motor Capacitor F VAC 0 6 F 400VAC 1 2 F 400VAC Specifications are subject to change without notice for further improvement 8 CS VC70KE CU VC70KE CS VC90KE CU V...

Page 9: ...ylinder rolling piston type Motor Type Induction 2 poles Rated Output W 700 Air Circularizing Type Cross flow Fan Propeller Fan Material AS Glass Fiber 30 AES Glass Fiber 12 Motor Type Transiator 4 po...

Page 10: ...ylinder rolling piston type Motor Type Induction 2 poles Rated Output W 1100 Air Circularizing Type Cross flow Fan Propeller Fan Material AS Glass Fiber 30 AES Glass Fiber 12 Motor Type Transiator 4 p...

Page 11: ...ht piping hole 290 115 55 60 2100 57 142 16 Remote control transmitter 45 410 Back View Installation plate hooks Drain ports Gas side Liquid side 40 710 40 276 7 60 110 100 100 Slot 2 places Slot 2 pl...

Page 12: ...way valve at Liquid side 13 at Gas side 3 way valve 93 27 5 780 57 Panasonic 4 3 CU VC120KE OUTDOOR UNIT 67 93 105 105 570 494 505 280 312 245 2 way valve at Liquid side 11 at Gas side 3 way valve 112...

Page 13: ...P INDOOR CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE OUTDOOR HEAT EXCHANGER C1 Capillary Tube EVAPORATOR HEAT EXCHANGER CONDENSER 2 WAY VALVE VALVE 3 WAY C1 STRAINER DRYER SENSOR INT...

Page 14: ...electronic control unit Indicates the number of core wires Example 6C 6 core wires COMP O L P CU VC90KE FAN MOTOR RY L P C B INDICATOR 4C 5C STEPPING MOTOR INDOOR UNIT OUTDOOR UNIT WIRELESS REMOTE CON...

Page 15: ...5 A BL R BL 2 MAIN SW TRANSFORMER 1 4 3 BR BR THERMAL FUSE 102 C R 3 3 2 1 1 R CN FUSE B REMOTE CONTROL CN T W T BL T BL WIRELESS REMOTE CONTROL ELECTRONIC CONTROLLER RECEIVER CN RCV W MOTOR CN STM G...

Page 16: ...ure of the indoor heat exchanger falls continuously below 2 C for 4 minutes the compressor turns off to protect the indoor heat exchanger from freezing The fan speed setting remains the same Compresso...

Page 17: ...operation Fan speed rotates in the range of Hi to Me Deodorizing Control 1 Fan Speed is Hi until the compressor stops when the set temperature is reached 2 Fan Speed is Me after the compressor restar...

Page 18: ...ll not restart for 3 minutes during Cooling operation 8 2 2 Anti Freezing Control Same as Anti Freezing Control for Cooling Mode operation For Soft Dry operation 6 minutes waiting is valid during comp...

Page 19: ...8 2 5 Soft Dry Operation Time Diagram 19 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 20: ...at the mode determined 3 After the operation mode has been determined the mode does not change However Soft Dry mode operation includes Cooling mode operation 4 If Automatic Mode operation is started...

Page 21: ...following movement will start to avoid overcooling The fan speed is automatically set to Low The setting temperature will be increased by 0 5 C at the start of operation and by 0 5 C one hour later Th...

Page 22: ...er wire J2 Refer Circuit Diagram 8 7 INDOOR FAN MOTOR CONTROL Auto Fan Speed Control When set to Auto Fan Speed the fan speed is adjusted between maximum and minimum setting as shown in the table Manu...

Page 23: ...the Airflow Direction Setting button is pressed the automatic airflow is released and the airflow direction louver moves up and down in the range shown in the diagram The louver can be stopped by rel...

Page 24: ...22 Composition wt R32 R125 50 50 R22 100 Boiling point C 51 4 40 8 Vaporizing pressure 25 C 1 56 Mpa 15 9 kgf cm 0 94 Mpa 9 6 kgf cm Saturated vapor density 64 0 kg m 44 4 kg m Flammability Non flamma...

Page 25: ...the outdoor unit has been changed Also to increase its ability to withstand pressure the opposing dimensions have been changed for the refrigerant pipe flaring size and flare nut Accordingly when inst...

Page 26: ...wrenches R410A wrenches For 1 4 opposite side x torque 17mm X 18 N m 180 kgf cm 17mm X 18 N m 180 kgf cm For 3 8 opposite side x torque 22mm X 42 N m 420 kgf cm 22mm X 42 N m 420 kgf cm For 1 2 oppos...

Page 27: ...sitivity for R134a at 1 the level for R410A will drop to 0 6 For detecting small amounts of gas leakage use the electric gas leak detector for HFC refrigerant Detection sensitivity with R410A is about...

Page 28: ...hose fitting 1 2 UNF 20 threads The packing must also be made of an HFC resistant material Fig 9 Charging orifice and packing 9 2 3 R410A Tools Which Are Usable for R22 Models Table 9 R410A tools whic...

Page 29: ...for flaring work a Cut the pipe Use a pipe cutter and cut slowly so the pipe will not be deformed b Remove burrs and clean shavings from the cut surface If the shape of the pipe end is poor after remo...

Page 30: ...kgf cm 1 4 6 35 14 18 140 180 18 180 3 8 9 52 33 42 330 420 42 420 1 2 12 70 55 550 55 550 9 3 3 Storing and Managing Piping Materials 1 Types of piping and their storage The following is a general c...

Page 31: ...minutes then check to make sure the low pressure gauge has reached 0 1 MPa 76 cmHg Once the vacuum process has finished fully close the handle Lo of the manifold gauge and stop the vacuum pump operati...

Page 32: ...sections of the piping also cannot be checked 2 Pipe cleaning A large quantity of refrigerating machine oil mineral oil adheres to existing pipes due to the refrigeration cycle circulation If the pipe...

Page 33: ...the manifold gauge and stop the operation of the unit 2 5 11 Quickly remove the charging hose from the service port 6 If you stop midway through the refrigerant that is in the cycle will be discharged...

Page 34: ...with a minimum of heating area 3 Overheating Protection In order to prevent components near the brazed part from overheating damage or quality deterioration due to flame or heat take adequate steps f...

Page 35: ...ning is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed There should not be any animal or plant which could be affected by ho...

Page 36: ...10 3 INDOOR OUTDOOR UNIT INSTALLATION DIAGRAM 36 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 37: ...h pin Operation Open With valve cap Open With valve cap Closed With cap Pumping down Transferring Closed Clockwise Open Counter clockwise Open Connected manifold gauge Evacuation Servicing Open Open O...

Page 38: ...ROCEDURE IN ORDER TO AVOID GAS LEAKAGE 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighten the service port cap at a torque of 18N m with a torqu...

Page 39: ...rate the air conditioner at the cooling cycle and stop it when the gauge indicates 0 MPa 0 kg cm G If the unit cannot be operated at the cooling condition weather is rather cool press the TEST RUN but...

Page 40: ...ith gas refrigerant from 3 way valve service port and then discharge the refrigerant until low side gas side gauge needle indicates 0 3 MPa 3 kg cm 7 Tighten the service port cap at a torque of 18 N m...

Page 41: ...rge the refrigerant until the gauge indicates 0 05 MPa 0 5 kg cm G to 0 1 MPa 1 kg cm G If there is no air in the refrigeration cycle the pressure when the air conditioner is not running is higher tha...

Page 42: ...76 cmHg vacuum of 4 mmHg or less 3 Close the valve Low side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move for approximately 5 minutes after turning off th...

Page 43: ...AN MOTOR REMOVAL PROCEDURE 1 Remove the connector CN MTR GREEN of Fan Motor and connector CN STM GREEN of stepping motor from the electronic controller Release the earth wire YELLOW GREEN from the con...

Page 44: ...an Motor securing screw at the junction with Cross Flow Fan Fig 5 Fig 5 Remove the particular piece and the Fan Motor can be taken off as shown in Fig 6 and 7 Fig 6 Fig 7 44 CS VC70KE CU VC70KE CS VC9...

Page 45: ...MOVAL PROCEDURE 1 Remove the Indoor Fan Motor Refer to the removal procedure of the Indoor Fan Motor Fig 9 2 Remove the Air Discharge Grille by taking off the screws that hold the Air Discharge Grille...

Page 46: ...t cover as shown in the Fig 12 Fig 12 12 5 REMOTE CONTROL RESET When the batteries are inserted for the first time or the batteries are replaced all the indications will blink and the remote control m...

Page 47: ...pped By adding a jumper wire to the remote control side and a carbon resistor 1 4 W 10 k to the indoor printed circuit board it is possible to select from 4 types of transmission codes including the c...

Page 48: ...13 Troubleshooting Guide 48 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 49: ...e fifteen minutes after an operationis started 13 2 DIAGNOSIS METHODS OF A MALFUNNCTION OF A COMPRESSOR Nature of fault Symptom Insuffic0ient compressing of a compressor Electric current during operat...

Page 50: ...Cooling Soft Dry 14 Technical Data 14 1 THERMOSTAT CHARACTERISTICS CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE 50 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 51: ...14 2 OPERATION CHARACTERISTICS 51 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 52: ...52 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 53: ...cated carbon resister Tolerance 5 metal oxide resister Tolerance 1 Indications for capacitor a Unit F P pF b Type Not indicated ceramic capacitor S S series aluminum electrolytic capacitor Z Z series...

Page 54: ...0 sec Soft Dry Off Off 6 min 36 sec Soft Dry 10 min operation On 10 min 60 sec Comp ON Deodorizing Control Cooling 40 sec 4 sec Comp ON 70 sec 7 sec Comp OFF 20 sec 2 sec Comp OFF Soft Dry 180 sec 18...

Page 55: ...C2 10V 100 REGULATOR AM78M05 IC2 5 12 470 25V C5 I G O 12V 10k 10k b e c Q2 UN4211 C1 35V 2200 C12 0 1 R14 5 1k AN78M12 IC5 DB1 S1VB10 CN FUSE 1 2 3 2 1 XH 3 BLUE CN T VH 2 TEMPERATURE FUSE AC BLACK R...

Page 56: ...30 50 Temperature C Temperature C 0 40 30 60 50 70 10 20 40 0 Sensor Thermistor Fig 1 Fig 5 OLP Characteristics Compressor Fig 2 Characteristics 1 Pipe Temp Sensor 2 Intake Air Temp Sensor 1 2 2 1 Vol...

Page 57: ...16 Printed Circuit Board 16 1 INDOOR UNIT MAIN 57 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 58: ...17 Exploded View Replacement Parts List 17 1 CS VC70KE CS VC90KE 17 1 1 Exploded View 58 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 59: ...R 1 M 21 CWE39C271 INDICATOR COMPLETE 1 M 22 CWA50C521 SENSOR COMPLETE 1 M 23 CWH13383 CONTROL BOARD TOP COVER 1 M 24 CWH13C256 CONTROL BOARD FRONT COVER 1 M 25 CWH13385 CONTROL BOARD COVER PIECE 1 M...

Page 60: ...17 2 CS VC120KE 17 2 1 Exploded View 60 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 61: ...21 CWE39C271 INDICATOR COMPLETE 1 M 22 CWA50C521 SENSOR COMPLETE 1 M 23 CWH13383 CONTROL BOARD COVER 1 M 24 CWH13C256 CONTROL BOARD COVER 1 M 25 CWH13385 CONTROL BOARD COVER 1 M 26 CWA75C560 REMOTE CO...

Page 62: ...17 3 CU VC70KE CU VC90KE 17 3 1 Exploded View 62 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 63: ...19 2 WAY VALVE 1 J 15 CWT01C598 CU VC70KE TUBE ASS Y STRAINER CAPAILLARY 1 J 15 CWT01C599 CU VC90KE TUBE ASS Y STRAINER CAPAILLARY 1 J 16 CWB10043 DRYER 1 J 17 CWH15266 SOUND PROOF BOARD 1 M 18 CWA67C...

Page 64: ...17 4 CU VC120KE 17 4 1 Exploded View 64 CS VC70KE CU VC70KE CS VC90KE CU VC90KE CS VC120KE CU VC120KE...

Page 65: ...10043 DRYER 1 J 17 CWH15265 SOUND PROOF BOARD 1 M 18 CWA12364 OVERLOARD PROTECTER 1 J 19 CWH17006 TERMINAL COVER 1 M 20 CWH34033 HOLDER OLP 1 M 21 CWH7080300 NUT TERMINAL COVER 1 M 22 CWG30401 SOUND P...

Page 66: ...RCUIT M L1 L2 CWA43036 V COIL M Q3 DTC143XST TRANSISTOR M Q2 DTC114EST TRANSISTOR M Q4 Q5 2SC1740STPR TRANSISTOR M Q1 2SC1741STPR TRANSISTOR M RY H RY M CWA00160 ELECTRO MAGNETIC RELAY M RY C CWA00106...

Reviews: