background image

10

 Safety Precautions

8. Removal and evacuation

• When breaking into the refrigerant circuit 

to make repairs – or for any other purpose 
– conventional procedures shall be used. 
However, it is important that best practice is 
followed since 

fl

 ammability is a consideration. 

The following procedure shall be adhered to: 
remove refrigerant -> purge the circuit with 
inert gas -> evacuate -> purge with inert gas 
-> open the circuit by cutting or brazing.

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be purged with OFN to 

render the appliance safe.

• This process may need to be repeated 

several times.

• Compressed air or oxygen shall not be used 

for this task.

• Purging shall be achieved by breaking 

the vacuum in the system with OFN and 
continuing to 

fi

ll until the working pressure is 

achieved, then venting to atmosphere, and 

fi

nally pulling down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the 

fi

 nal OFN charge is used, the 

system shall be vented down to atmospheric 
pressure to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any potential ignition sources and 
there is ventilation available.

OFN = oxygen free nitrogen, type of inert gas.

9. Charging procedures

• In addition to conventional charging 

procedures, the following requirements shall 
be followed.

 

- Ensure that contamination of different 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible 

to minimize the amount of refrigerant 
contained in them. 

 

- Cylinders shall be kept in an appropriate 

position according to the instructions.

 

- Ensure that the refrigerating system is 

earthed prior to charging the system with 
refrigerant.

 

- Label the system when charging is 

complete (if not already). 

 

- Extreme care shall be taken not to over 

fi

ll 

the refrigerating system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior 

to leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant. To avoid 

fi

 re 

or explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

10. Decommissioning

• Before carrying out this procedure, it is 

essential that the technician is completely 
familiar with the equipment and all its details.

• It is recommended good practice that all 

refrigerants are recovered safely.

• Prior to the task being carried out, an oil 

and refrigerant sample shall be taken in 
case analysis is required prior to re-use of 
recovered refrigerant.

• It is essential that electrical power is available 

before the task is commenced.

a)  Become familiar with the equipment and 

its operation.

b)  Isolate system electrically.
c)  Before attempting the procedure ensure 

that: 

•  mechanical handling equipment is 

available, if required, for handling 
refrigerant cylinders; 

•  all personal protective equipment is 

available and being used correctly;

•  the recovery process is supervised at all 

times by a competent person;

•  recovery equipment and cylinders conform 

to the appropriate standards.

d)  Pump down refrigerant system, if possible.

Summary of Contents for CS-XU10XKH

Page 1: ...oughly and keep them for future reference Before installation the installer should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control...

Page 2: ...the remote control receiver on the indoor unit Quick Guide Inserting the batteries 1 2 3 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 P...

Page 3: ...purposes only and may differ from the actual unit They are subject to change without notice B Basic operation Thank you for purchasing Panasonic Air Conditioner 1 Press to start stop the operation POW...

Page 4: ...supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit Im...

Page 5: ...not wash the indoor unit with water benzine thinner or scouring powder to avoid damage or corrosion at the unit Do not use for preservation of precise equipment food animals plants artwork or other o...

Page 6: ...l the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of...

Page 7: ...he precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised a...

Page 8: ...ernally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Page 9: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also t...

Page 10: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Page 11: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Page 12: ...manually This operation can be activated even when the unit is OFF Note that the flap and fan speed will operate according to the remote control setting If a power failure occurs during this operatio...

Page 13: ...s to turn on the unit in iAUTO X mode How to Use To reach the desired temperature quickly For Wireless LAN Module operation setup please refer to Setup Instructions Manual To connect to a network This...

Page 14: ...ive setting or then press The nearest timer setting is displayed and will activate in sequence The timer operation follows the clock setting on the remote control and will repeat daily when timer has...

Page 15: ...ailure the operation will restart automatically with the last operation mode and airflow direction This control is not applicable when TIMER is set nanoe X filter deactivation Depending on the unit s...

Page 16: ...cleaned periodically by an authorised dealer Outdoor unit Clean the debris that surround the unit Clear any blockage from the drain pipe Front panel Wash gently and dry How to remove front panel AUTO...

Page 17: ...heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding the unit The dust accumulation is due to the air purification effec...

Page 18: ...refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents C...

Page 19: ...r abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mis...

Page 20: ...1 2 3 1 2 AAA R03 3 8 m A B A 1 CLOCK 12 am pm 24 CLOCK 5 2 20...

Page 21: ...B 2 DRY iAUTO X COOL 1 POWER ON 3 TEMP UP TEMP DOWN 16 0 C 30 0 C 60 F 86 F C F 10 22 33 34 36 37 38 39 40 41 45 47 AAA R03 2 2 Panasonic Burmese 21...

Page 22: ...22...

Page 23: ...ELCB RCD ELCB Burmese 23...

Page 24: ...Ni Cd nanoeTM G 24...

Page 25: ...R32 Amin m Amin m R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A Flare Nut R32 R410A R22 R32 R410A 1 2 inch R32 R410A Burmese 25...

Page 26: ...AHU 5 1 04MPa 4 15MPa 0 25 26...

Page 27: ...1 Amin m 12 2 2 1 2 2 2 2 2 8 2 m 2 m Burmese 27...

Page 28: ...2 3 2 4 CO2 2 5 2 6 2 7 28...

Page 29: ...2 8 capacitors discharged 3 Burmese 29...

Page 30: ...4 5 6 7 5 1 04MPa 4 15MPa 0 25 LFL 25 8 30...

Page 31: ...8 OFN OFN OFN OFN 9 OFN 7 Burmese 31...

Page 32: ...10 Recover Machine Recover Machine 80 11 32...

Page 33: ...12 Burmese 33...

Page 34: ...To adjust airflow direction LAN ON OFF FAN SPEED FAN AUTO iAUTO X AUTO iAUTO X QUIET FAN SPEED QUIET nanoeTM X nanoeTM G nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY OFF 34...

Page 35: ...LAN 0 5 1 2 3 4 5 6 7 8 9 OFF 0 0h iAUTO X 2 C 4 F AUTO 4 iAUTO X iAUTO X 23 C 60 iAUTO X iAUTO X iAUTO X 2 C 4 F 4 Burmese 35...

Page 36: ...2 3 1 2 1 TIMER ON TIMER OFF 22 00 OFF 2 3 36...

Page 37: ...iAUTO X COOL DRY COOL 26 0 C 28 0 C 79 F 82 F COOL DRY iAUTO X COOL DRY iAUTO X TIMER nanoe X nanoeTM X nanoeTM X COOL DRY 2 5 nanoeTM TECHNOLOGY 2 Burmese 37...

Page 38: ...C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT 38...

Page 39: ...H 99 pH 7 40 C 104 F AUTO OFF ON 2 A B 1 B A AUTO OFF ON 2 1 3 4 AUTO OFF ON nanoeTM G Burmese 39...

Page 40: ...nanoeTM G 2 2 40...

Page 41: ...POWER TIMER ON 15 TIMER ON UV Burmese 41...

Page 42: ...COOL nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY ON nanoeTM G nanoeTM TECHNOLOGY nanoeTM X nanoeTM TECHNOLOGY OFF LAN ON LAN 42...

Page 43: ...AUTO OFF ON 1 2 iAUTO X AUTO OFF ON 3 COOL 1 AUTO OFF ON 4 AUTO OFF ON 5 COOL AUTO OFF ON 15 8 C 14 4 F nanoeTM TECHNOLOGY 2 3 Burmese 43...

Page 44: ...H 00 H 11 H 12 H 14 H 15 H 16 current transformer CT H 17 H 19 H 21 Float Switch H 23 1 H 24 2 H 25 H 26 Negative H 27 H 28 1 H 30 Discharge Pipe H 31 H 32 2 H 33 H 34 H 35 H 36 Gas Pipe H 37 Liquid P...

Page 45: ...52 Limit Switch H 58 H 59 H 64 H 67 nanoe H 70 H 71 H 72 H 85 LAN H 97 H 98 H 99 F 11 4 way F 16 F 17 F 18 Dry Circuit F 87 PCB F 90 Power Factor F 91 F 93 F 94 F 95 Cooling Side F 96 F 97 F 98 F 99 D...

Page 46: ...tion with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If t...

Page 47: ...47 Pb...

Page 48: ...Printed in Malaysia Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021 ACXF55 29860 SZ0221 0...

Reviews: