 Safety Precautions

WARNING

This appliance is 

fi

 lled with R32 

(mild 

fl

 ammable refrigerant). 

If the refrigerant is leaked and exposed to 
an external ignition source, there is a risk 
of 

fi

 re.

Indoor unit and outdoor unit

The appliance shall be installed, and/or 
operated in a room with 

fl

 oor area larger 

than Amin (m²) and keep away from ignition 
sources, such as heat/sparks/open 

fl

 ame or 

hazardous areas such as gas appliances, gas 
cooking, reticulated gas supply systems or 
electric cooking appliances, etc. (Refer to Table 
A of Installation instructions table for Amin (m²))

Be aware that refrigerant may not contain an 
odour, highly recommended to ensure suitable 

fl

 ammable refrigerant gas detectors are 

present, operating and able to warn of a leak.

Keep any required ventilation openings clear of 
obstruction.

Do not pierce or burn as the appliance is 
pressurized. Do not expose the appliance to 
heat, 

fl

 ame, sparks, or other sources of ignition. 

Else it may explode and cause injury or death.

Precaution for using R32 refrigerant

The basic installation work procedures are the same as 
conventional refrigerant (R410A, R22) models.

Since the working pressure is higher than that 
of refrigerant R22 models, some of the piping 
and installation and service tools are special. 
Especially, when replacing a refrigerant R22 
model with a new refrigerant R32 model, 
always replace the conventional piping and 

fl

 are nuts with the R32 and R410A piping and 

fl

 are nuts on the outdoor unit side. 

For R32 and R410A, the same 

fl

 are nut on the 

outdoor unit side and pipe can be used.

The mixing of different refrigerants within 
a system is prohibited. Models that use 
refrigerant R32 and R410A have a different 
charging port thread diameter to prevent 
erroneous charging with refrigerant R22 and 
for safety. 
Therefore, check beforehand. [The charging 
port thread diameter for R32 and R410A is 1/2 
inch.]

 

Must always ensure that foreign matter (oil, 
water, etc.) does not enter the piping. Also, 
when storing the piping, securely seal the 
opening by pinching, taping, etc. (Handling of 
R32 is similar to R410A.)
• Operation, maintenance, repairing and 

refrigerant recovery should be carried 
out by trained and certi

fi

 ed personnel in 

the use of 

fl

 ammable refrigerants and as 

recommended by the manufacturer. Any 
personnel conducting an operation, servicing 
or maintenance on a system or associated 
parts of the equipment should be trained and 
certi

fi

 ed.

• Any part of refrigerating circuit (evaporators, 

air coolers, AHU, condensers or liquid 
receivers) or piping should not be located in 
the proximity of heat sources, open 

fl

 ames, 

operating gas appliance or an operating 
electric heater.

• The user/owner or their authorised 

representative shall regularly check the 
alarms, mechanical ventilation and detectors, 
at least once a year, where as required by 
national regulations, to ensure their correct 
functioning.

• A logbook shall be maintained. The results 

of these checks shall be recorded in the 
logbook.

• In case of ventilations in occupied spaces 

shall be checked to con

fi

 rm no obstruction.

• Before a new refrigerating system is put 

into service, the person responsible for 
placing the system in operation should 
ensure that trained and certi

fi

 ed operating 

personnel are instructed on the basis of the 
instruction manual about the construction, 
supervision, operation and maintenance of 
the refrigerating system, as well as the safety 
measures to be observed, and the properties 
and handling of the refrigerant used.

• The general requirement of trained and 

certi

fi

 ed personnel are indicated as below:

a) Knowledge of legislation, regulations 

and standards relating to 

fl

 ammable 

refrigerants; and,

b) Detailed knowledge of and skills in 

handling 

fl

 ammable refrigerants, personal 

protective equipment, refrigerant leakage 
prevention, handling of cylinders, charging, 
leak detection, recovery and disposal; and,

c)  Able to understand and to apply in practice 

the requirements in the national legislation, 
regulations and Standards; and,

d) Continuously undergo regular and further 

training to maintain this expertise.

e)  Air-conditioner piping in the occupied 

space shall be installed in such a way 
to protect against accidental damage in 
operation and service.

Summary of Contents for CS-XU10XKH

Page 1: ...oughly and keep them for future reference Before installation the installer should Read the Installation Instructions then request the customer keep them for future reference Remove the remote control...

Page 2: ...the remote control receiver on the indoor unit Quick Guide Inserting the batteries 1 2 3 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 P...

Page 3: ...purposes only and may differ from the actual unit They are subject to change without notice B Basic operation Thank you for purchasing Panasonic Air Conditioner 1 Press to start stop the operation POW...

Page 4: ...supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit Im...

Page 5: ...not wash the indoor unit with water benzine thinner or scouring powder to avoid damage or corrosion at the unit Do not use for preservation of precise equipment food animals plants artwork or other o...

Page 6: ...l the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of...

Page 7: ...he precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised a...

Page 8: ...ernally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Page 9: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also t...

Page 10: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Page 11: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Page 12: ...manually This operation can be activated even when the unit is OFF Note that the flap and fan speed will operate according to the remote control setting If a power failure occurs during this operatio...

Page 13: ...s to turn on the unit in iAUTO X mode How to Use To reach the desired temperature quickly For Wireless LAN Module operation setup please refer to Setup Instructions Manual To connect to a network This...

Page 14: ...ive setting or then press The nearest timer setting is displayed and will activate in sequence The timer operation follows the clock setting on the remote control and will repeat daily when timer has...

Page 15: ...ailure the operation will restart automatically with the last operation mode and airflow direction This control is not applicable when TIMER is set nanoe X filter deactivation Depending on the unit s...

Page 16: ...cleaned periodically by an authorised dealer Outdoor unit Clean the debris that surround the unit Clear any blockage from the drain pipe Front panel Wash gently and dry How to remove front panel AUTO...

Page 17: ...heat sun light UV light or environmental factors After extended use dust may cover the front panel grilles and the wall surrounding the unit The dust accumulation is due to the air purification effec...

Page 18: ...refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference between the air inlet and outlet vents C...

Page 19: ...r abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mis...

Page 20: ...1 2 3 1 2 AAA R03 3 8 m A B A 1 CLOCK 12 am pm 24 CLOCK 5 2 20...

Page 21: ...B 2 DRY iAUTO X COOL 1 POWER ON 3 TEMP UP TEMP DOWN 16 0 C 30 0 C 60 F 86 F C F 10 22 33 34 36 37 38 39 40 41 45 47 AAA R03 2 2 Panasonic Burmese 21...

Page 22: ...22...

Page 23: ...ELCB RCD ELCB Burmese 23...

Page 24: ...Ni Cd nanoeTM G 24...

Page 25: ...R32 Amin m Amin m R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A Flare Nut R32 R410A R22 R32 R410A 1 2 inch R32 R410A Burmese 25...

Page 26: ...AHU 5 1 04MPa 4 15MPa 0 25 26...

Page 27: ...1 Amin m 12 2 2 1 2 2 2 2 2 8 2 m 2 m Burmese 27...

Page 28: ...2 3 2 4 CO2 2 5 2 6 2 7 28...

Page 29: ...2 8 capacitors discharged 3 Burmese 29...

Page 30: ...4 5 6 7 5 1 04MPa 4 15MPa 0 25 LFL 25 8 30...

Page 31: ...8 OFN OFN OFN OFN 9 OFN 7 Burmese 31...

Page 32: ...10 Recover Machine Recover Machine 80 11 32...

Page 33: ...12 Burmese 33...

Page 34: ...To adjust airflow direction LAN ON OFF FAN SPEED FAN AUTO iAUTO X AUTO iAUTO X QUIET FAN SPEED QUIET nanoeTM X nanoeTM G nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY OFF 34...

Page 35: ...LAN 0 5 1 2 3 4 5 6 7 8 9 OFF 0 0h iAUTO X 2 C 4 F AUTO 4 iAUTO X iAUTO X 23 C 60 iAUTO X iAUTO X iAUTO X 2 C 4 F 4 Burmese 35...

Page 36: ...2 3 1 2 1 TIMER ON TIMER OFF 22 00 OFF 2 3 36...

Page 37: ...iAUTO X COOL DRY COOL 26 0 C 28 0 C 79 F 82 F COOL DRY iAUTO X COOL DRY iAUTO X TIMER nanoe X nanoeTM X nanoeTM X COOL DRY 2 5 nanoeTM TECHNOLOGY 2 Burmese 37...

Page 38: ...C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT 38...

Page 39: ...H 99 pH 7 40 C 104 F AUTO OFF ON 2 A B 1 B A AUTO OFF ON 2 1 3 4 AUTO OFF ON nanoeTM G Burmese 39...

Page 40: ...nanoeTM G 2 2 40...

Page 41: ...POWER TIMER ON 15 TIMER ON UV Burmese 41...

Page 42: ...COOL nanoeTM TECHNOLOGY nanoeTM TECHNOLOGY ON nanoeTM G nanoeTM TECHNOLOGY nanoeTM X nanoeTM TECHNOLOGY OFF LAN ON LAN 42...

Page 43: ...AUTO OFF ON 1 2 iAUTO X AUTO OFF ON 3 COOL 1 AUTO OFF ON 4 AUTO OFF ON 5 COOL AUTO OFF ON 15 8 C 14 4 F nanoeTM TECHNOLOGY 2 3 Burmese 43...

Page 44: ...H 00 H 11 H 12 H 14 H 15 H 16 current transformer CT H 17 H 19 H 21 Float Switch H 23 1 H 24 2 H 25 H 26 Negative H 27 H 28 1 H 30 Discharge Pipe H 31 H 32 2 H 33 H 34 H 35 H 36 Gas Pipe H 37 Liquid P...

Page 45: ...52 Limit Switch H 58 H 59 H 64 H 67 nanoe H 70 H 71 H 72 H 85 LAN H 97 H 98 H 99 F 11 4 way F 16 F 17 F 18 Dry Circuit F 87 PCB F 90 Power Factor F 91 F 93 F 94 F 95 Cooling Side F 96 F 97 F 98 F 99 D...

Page 46: ...tion with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If t...

Page 47: ...47 Pb...

Page 48: ...Printed in Malaysia Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021 ACXF55 29860 SZ0221 0...

Reviews: