ー
85
ー
Operating Instructions
Intelligent Controller
78
Settings for energy saving
Energy saving
6
Set other indoor units.
z
Repeat steps
3 to 5.
7
Touch [Reg.].
z
To cancel the settings, touch [Cancel].
7
Item
Explanation
Return temperature Return time
Set the return temperatures for “Heat”, “Cool”, and “Auto” and the return time. Use
to set the temperature
or time. The setting ranges are as follows.
y
Return temperature for heating:
16 to 30
°C*
1
(1
°C intervals)
*1
The upper limit for gas heat pumps is 26
°C.
y
Return temperature for cooling (dry):
18 to 30
°C (1
°C intervals)
y
Return temperature for auto:
17 to 27
°C (1
°C intervals)
y
Return time (shared):
0 to 240
minutes (5
minute intervals)
Auto return
The auto return function is enabled for the selected indoor unit if you put a check mark here.
The following items are settings common to all indoor units.
y
Eco dirc. only
y
Always return
Select the conditions for return. When you select “Eco dirc. only”, the return to the set temperature only occurs automatically if it saves energy
.
y
Allow auto C/H
y
Fan switching
When you select “Allow auto C/H”, temperature auto return control also occurs in the automatic mode.
When you select “Fan switching”, when the running mode of the indoor units is switched to “Auto Cool/Heat” the mode switches from automatic mode to fan mode.
5
Touch [Register].
z
The “Setting” dialogue closes.
z
To cancel the settings, touch [Cancel].
5
Automatically return to set temperatures [Set temp. auto return]
79
Settings for energy saving
Energy saving
The “Set temp. auto return” screen
A:
[Select all]/[Clear all] buttons
[Select all]
Select all indoor units.
[Clear all]
Cancel selection of all indoor units.
B:
Change list order
. The list order changes each
time you touch it.
Display
The display follows the order set in “I/D unit settings” (P
.141).
O/D unit
The display follows the address order of the outdoor unit systems.
Address
The display follows the address order set in “I/D unit settings” (P
.141).
C:
The indoor units with a check mark next to them will be the subject of the changes to the settings.
D:
The temperature auto return setting is enabled for the selected indoor unit if you put a check mark here.
This is linked with
the “Auto return” (“Setting” dialogue) (P
.78)
setting.
E:
The “Setting” dialogue is displayed when you touch this.
A
B
D
E
C
Automatically return to set temperatures [Set temp. auto return]
TGR-318_ENG.indb 85
2017/04/06 10:43:24