19
7
Put a check mark in the “Register”
column.
z
Select the indoor units you want to manage.
z
This procedure is not necessary if central addresses have
been automatically set. (→ “Automatically setting central
addresses” (P.20))
7
8
Touch [Register].
z
To cancel the settings, touch [Cancel].
8
Note
y
Do not allocate PAC and GHP to the same area or distribution
groups when using time distribution (P.27).
Item
Explanation
CNTR addr.
Set the central addresses (1 to 64).
Touch the text box and enter with the
touchscreen numeric keypad.
Note
y
The central address is shared with other
centralised controllers (system controllers,
etc.). Do not change unless necessary.
y
An error message is displayed if you set
an address that is already in use.
y
This cannot be set if multiple indoor units
are selected.
Fix cap
Set the fixed capacity values of the indoor
unit. (When interface adaptors are installed)
Touch the text box and enter with the
touchscreen numeric keypad.
ElecHeatrCap
Set the capacity of the electric heater if
the model has an electric heater. (when
calculating load distribution)
Touch the text box and enter with the
touchscreen numeric keypad.
Group registration
y
Control Gr.
y
SchedleGroup
y
Area
y
Distrib. Grp.
Register the group the unit belongs to.
The group names are displayed when you
touch the text boxes.
Note
y
By putting a check mark in the “Select”
column of the indoor units belonging to
the same group, you can edit the settings
at the same time and register them all
together.
Not batch
Select “
” if the device is not to be subject to
operations and select “
” if it is to be subject
to operations.
Not managed
Select “
” if the device is to be remove as
a subject of management by this unit, and
select “
” if it is to be subject of management
by this unit.
6
Touch [Register].
z
To cancel the settings, touch [Cancel].
6
Setting
CZ-256ESMC3_QR_EU.indd 19
2016/09/12 17:13:25