Chapter 1. System Programming (FF1)
Section 400-Programming
Page 1-174
DBS Manual - Revised April 2000
DBS-2.3/9.2-400
Other Alarms Detection
Software Version: CPC-B Version 4.0 or higher
Address:
Master Cabinet: FF1 8# 4# 4# 2# 4# (0-15)#
Slave Cabinet:
FF1 8# 4# 5# 2# 4# (0-15)#
Description
Determines how long an out-of-frame (OOF), loss of signal, sync loss, or AIS
signal must be on before the system generates an alarm.
If an OOF, Sync Loss, or AIS alarm occurs, a corresponding LED on the T1
card lights. (Sync Loss alarms light the “SLIP” LED.)
The alarm relay on the T1 MDF card will also close if the corresponding relay
parameter is enabled.
Programming
Table 1-52. Other Alarms Detection timer values
Setting
Value
0
0 ms
1
250 ms
2
500 ms
3
750 ms
4
1000 ms
5
1250 ms
6
1500 ms
7
1750 ms
8
2000 ms
9
2500 ms
10
3000 ms
11
3500 ms
12
4000 ms
13
4500 ms
14
5000 ms
15
5500 ms
FF1 8# 4# (4 or 5)# 2# 4# (0-15)#
4=Master Cabinet Other Alarms Detection timer setting
5=Slave Cabinet Default:
1 (250 ms)
(see table below)