DAILY USER´S MANUAL
•
EBL128 VERSION 2.2.X
•
DOCUMENT NUMBER: MEW01786
•
REVISION: 1
2.1.
LED INDICATORS
See reference picture on page 4.
1
Fire
Fire alarms.
2
Alarms queued
More than one alarm point / zone have activated fire alarm.
3
Extinguishing
Output(s) for extinguishing equipment activated.
4
Ventilation
Output(s) for fire/smoke ventilation equipment activated.
5
Fire brigade tx
Output "Fire alarm" for fire brigade tx (routing equipment) activated.
6
Operation
The c.i.e. is powered via the rectifier and/or the battery.
7
General fault
Fault(s) in the system.
8
Disablements
Disablement(s) in the system.
9
Fault tx activated
Not acknowledged fault(s):
Output "Fault condition" for fault tx (routing equipment) is activated.
10
Sevice
One or more sensors have reached the service level. See menu H4/U4.
11
Alarm devices
Steady light: Output(s) type "Alarm device" are disabled.
Flashing light: Output(s) type "Alarm device" have generated fault(s).
12
Fire brigade tx
Steady light: Output(s) for "Routing equipment" disabled via menu H2/B3 or
B9 or via open door.
Flashing light: Routing equipment power supply outputs or supervised
outputs of type "Routing equipment" have generated fault(s) or the c.i.e.
has lost contact with these outputs.
13
System fault
EBL128 is not running because of:
S/W fault
CPU fault
Memory fault
C.i.e. restart (fault code ≠ 00 / 03).
14
Fire brigade tx delay
The Alert Annunciation function is enabled.
15
Test mode
Zones are in "test mode".
16
Door open
The door is open in the EBL 128 or an external FBP in the system.