Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
EBL128 Operating Instructions V2.0.x
123
29
FAULT Acknowledge (H6)
Regarding fault indication, etc., see chapter "Fault", page 57.
All faults are normally latched, i.e. all faults have to be acknowledged.
See also chapter "Fault acknowledge", page 70.
All fault events are stored in the event log and can be listed. See also
chapter "Event log (H4/U6)", page 109.
In this menu (H6) are up to 200 faults listed:
Not corrected and not acknowledged faults (no status info.)
Not corrected but acknowledged faults (status: Acknowledged)
Corrected but not acknowledged faults (status: Serviced)
84
The way the date is presented is different for different languages.
If there are no faults,
--- List is empty ---
will be shown.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 81.
Scroll to menu H6.
FAULT Acknowledge
ACCEPT? H6
"A"
FAULT: Xxxxxxxx
Date: MM-DD Time: HH:MM Status info.
This is a list in which
you can scroll. The first
fault in the list is the
most recent fault. Status
info., see above.
When applicable, press
"
" for more info.
To acknowledge the fault
shown in the display,
press "Fault
acknowledge" (P6).
FAULT: Xxxxxxxx
User defined Alarm text, when applicable
"Fault acknowledge"
FAULT: Xxxxxxxx
Date: MM-DD Time: HH:MM Acknowledged
The status info. is now
Acknowledged
. When
this fault is
corrected
it
will be removed from the
list. Scroll in the list e.g.
to acknowledge more
faults or press "Return"
to menu H6.
"Return"
FAULT Acknowledge
ACCEPT? H6
Scroll or press "Return"
to log off.
84
If faults are set – via EBLWin – to be "Not latched",
Serviced
will never
be shown.