Alarm reset
17.1
Pre-warning reset
Pre-warnings are non-latching, i.e. they will be automatically reset
when the alarm point / zone is no longer above pre-warning level.
Outputs activated by pre-warning will be de-activated. (In some cases
after a programmable delay time.)
17.2
Fire alarm reset
In the New Zealand convention
fire alarms
= normal fire alarms
(ALM), acknowledged alarms (ACK) and isolated alarms (ISO).
NOTE!
The detectors having activated the fire alarms shall, after
reset, be inspected, tested and replaced when required.
One of the following alarm reset alternatives is valid. This is selected
via EBLWin. "All" is default.
17.2.1
All
All activated fire alarms (alarm points / zones) will be reset by
pressing "Reset" (P4) once. (This is in accordance with the EN54-2
standard).
NOTE!
The push button has to be pressed for min. 0.5 sec.
When all fire alarms are reset
, LEDs "Fire" (L1) and "Alarms
queued" (L2) are turned off. If there are other conditions (e.g. a fault
condition) the corresponding information will be shown (e.g. a fault
message), for the priority order see chapter "The display in EBL128",
page 21.
All outputs (for fire alarm) are reset, i.e. de-activated.
If a key cabinet is installed, the key (to the building) has to be put
back into the key cabinet
within 5 minutes
. If not, a fault will be
generated and a fault message will be shown in the display, see
chapter "Key cabinet alarm reset”, page 55.
NOTE!
When "Single" or "Single with automatic disablement" is used, all
alarms can be reset by pressing "Reset" (P4) and approx. 0.1 sec. later
also press "A" (in the keypad) and hold them pressed for > 0.5 sec.
17.2.2
Single
Each fire alarm (alarm point / zone) has to be reset one by one.
NOTE!
This function is available only if it is set in EBLWin.
Press "Reset" (P4) to reset the fire alarm currently shown to the left in
the display.
NOTE!
The push button has to be pressed for min. 0.5 sec.