Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
EBL128 Operating Instructions V2.0.x
65
AAU=1735 / 1736. (Alert Annunciation Unit)
EBL128 cannot communicate with the unit. Check / edit the address
and the S/W mode in the unit (or edit the SSD).
FAULT: No reply EPU x
EPU=1728. (Ext. Presentation Unit)
EBL128 cannot communicate with the unit. Check / edit the address
and the S/W mode in the unit (or edit the SSD).
FAULT: No reply, expansion board x
Valid for the 8 zones exp. board 4580, the 8 relays exp. board 4581
and the Inputs and outputs exp. board 4583 mounted in the c.i.e.
(EBL128). Also valid for the I/O Matrix board 4582 connected on the
COM loop, i.e. mounted outside the c.i.e.
EBL128 cannot communicate with the board. Check / edit the
address. Check the cables / connections.
FAULT: No reply FBP x
FBP=1826 / 1828. (Ext. Fire Brigade Panel)
EBL128 cannot communicate with the unit. Check / edit the address
and the S/W mode in the unit (or edit the SSD).
FAULT: Output Sx
This is valid for the EBL128 supervised voltage outputs S0 and S1.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED "
Fault / Disablements
Alarm devices" (L13)
blinking.
If the output is programmed for a fire brigade tx (type Routing
equipment), it is also indicated by LED "
Fault / Disablements
Fire
brigade tx" (L15) blinking.
*
Calibration not performed via menu H5/A1.
*
Short-circuit / break on the connected cable / equipment.
*
Blown fuse "F8" (S0) or "F6" (S1) on the main board
4556.
*
Connected equipment might be "missing".
*
End-of-line resistor(s) missing or not correct value (see
drawing 128-22). 1- 5 resistors 33K.
NOTE!
The calibrated value has to be in the range 4K7-50K.